The  YKN2Open  board  (A1)  indicates  smoke  faults  with  a  4-5  flashing  sequence  of  the  red  LED.  If

thermostat DPC-1 is fitted, the incident is indicated on the screen where the time is displayed along with

fault code 45.
Once  the  presence  of  smoke  has  disappeared,  the  thermostat  must  be  manually  reset  and  the

YKN2Open board (A1) reset to delete the incident.
Where the economiser accessory is fitted, check the position of jumper J20 on the economiser board.

Jumper J20 (outside damper closed with high temperature-smoke alarm) is open by default. If the jumper

is closed, outside damper open with high temperature-smoke alarm is selected.
In units equipped with a supply probe connected to the YKN2Open board, with hot water coil (accessory)

or economiser, if a supply temperature of over 80 °C is detected the equipment will stop and fault code

45 is displayed.

1.6 Installation

1.6.1 Installation

1. Disconnect the main switch on the unit.
2. Fit the optical sensor. In accordance with instructions in the section 

Assembly

, see on page 3.

3. Fit the DAD control.
4. Fit the temperature/smoke control board in the electrical box.

  N O T E

If the temperature detection accessory is also fitted, a temperature/smoke control board is fitted and

the two normally closed contacts fitted in series in input J4.

5. Connect the cables supplied according to the wiring diagram.
6. Once all of the connections are made, reconnect the unit main switch.
7. Check that the green LED on board A9 remains lit. Next, search and configure the accessories by

pressing the test button on the YKN2Open board (A1) for more than three seconds, until the red

LED lights up. When the search and configuration process starts, the red LED on the board will light

up and will remain on until the operation is completed. Once it has switched off, check that the green

LED (V1) on board A9 is flashing to indicate that the accessory has been configured.

8. To check the electrical operation, disconnect the wires of terminals J4 on board A9 or apply smoke

directly to the optical sensor and check that the YKN2Open board (A1) indicates the high temperature

fault with a 4-5 flashing sequence of the red LED. Reconnect the wires and reset the YKN2Open (A1)

board to delete the fault.

  C A U T I O N

Loose connection terminals produce overheating of cables and terminals. The unit will work incorrectly

and there is a risk of fire.

Data and measurements subject to changes without prior notice.

1

Smoke detector

1.6

Installation

8

Summary of Contents for ACTIVA 175

Page 1: ...Smoke detector for Roof Top ACTIVA 017 175 Options and Accessories Installation manual Ref N 40438_EN 0913...

Page 2: ...x 1 Smoke detector 1 1 1 General information 2 1 2 Technical specifications 2 1 3 General dimensions 2 1 4 Assembly 3 1 5 Operation 7 1 6 Installation 8 1 6 1 Installation 8 1 6 2 Wiring diagram 9 Ind...

Page 3: ...1 Smoke detector...

Page 4: ...act on the accessory board relay 1 2 Technical specifications This accessory includes the following components Ionic sensor with Ref IX010310E4 DAD smoke control with battery and Ref 4485 Temperature...

Page 5: ...4 Assembly The ion sensor is fitted inside the Rooftop on the return air side The DAD control and the smoke detector board are fitted to the inside of the electrical box in the holes provided for this...

Page 6: ...section Models 100 175 A Control board access B Ionic sensor C Access to the supply air section Assembly of units without economiser Models 017 040 A Smoke sensor location B Lower filter guide Models...

Page 7: ...units with economiser optional Models 017 040 Models 100 175 A Smoke sensor location B Economiser side frame Assembly in units with or without economiser models 045 090 A B B A B A Smoke detector 1 As...

Page 8: ...017 040 1 Control board 2 DAD control 3 Support attached to the interior partition panel the holes for the bolts are covered by the insulation Models 045 090 1 Control board 2 DAD control 1 2 3 B4 2...

Page 9: ...section that is 0 75 mm 1 5 Operation The first time that the DAD control is powered contact 11 COM of the thermostat is on standby and 10 NC is open Press the reset button to close contact NC and pr...

Page 10: ...perature detection accessory is also fitted a temperature smoke control board is fitted and the two normally closed contacts fitted in series in input J4 5 Connect the cables supplied according to the...

Page 11: ...e reset 3 Black E Coil J1 Connection cables F Connect red wire to terminal L1 OUT Brown G Accessories L2 White H1 APOLLO sensor L1 IN Red H2 Sensor C Scan O J2 Connection cables 2 Brown 5 White 1 Red...

Reviews: