661693-UIM-E-1212
Johnson Controls Unitary Products
11
TABLE 8:
ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY - 208/230-3-60
Air Handler Models
Heater
Models
Heater
Amps
@ 240V
Field Wiring
Min. Circuit Ampacity
MOP
1
Min. Wire Size (AWG)
2
208V
230V
208V
230V
208V
230V
AHR24B
6HK06501025
23.1
26.8
30.7
30
35
10
10
6HK06501525
34.6
39.2
45.0
40
45
8
8
AHR30B
AHR42C
6HK06501025
23.1
28.8
32.7
30
35
10
8
6HK06501525
34.6
41.2
47.0
45
50
8
8
AHR36B
AHR48D
6HK06501025
23.1
28.8
32.7
30
35
10
8
6HK06501525
34.6
41.2
47.0
45
50
8
8
6HK06501825
41.6
48.8
55.8
50
60
8
6
6HK16502025
3
46.2
53.8
61.5
60
70
6
6
AHR60D
6HK06501025
23.1
28.8
32.7
30
35
10
8
6HK06501525
34.6
41.2
47.0
45
50
8
8
6HK06501825
41.6
48.8
55.8
50
60
8
6
6HK16502025
3
46.2
53.8
61.5
60
70
6
6
6HK16502525
3
57.7
66.3
75.9
70
80
4
4
1. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
2. Stated sizes are for 75°C, copper wire only. If wire other than non-plated, 75°C ambient, copper wire is used, consult applicable tables of the NEC and local codes.
3. The 20kW and 25kW heater models (6HK16502025 and 6HK16502525) come with circuit breakers standard. Single source power MCA and MOP requirements are
given here only for reference if used with field installed single point power modification.
TABLE 9:
ELECTRICAL DATA FOR MULTI-SOURCE POWER SUPPLY: 208/230-3-60
Air Handler Models
Heater
Models
Total Heater
Amps
@ 240V
Min. Circuit Ampacity
MOP
1
Min. Wire Size (AWG)
2
208V
230V
208V
230V
208V
230V
Circuit
Circuit
Circuit
1st
3
2nd
1st
3
2nd
1st
3
2nd
1st
3
2nd
1st
3
2nd
1st
3
2nd
AHR36B
AHR48D
6HK16502025
46.2
28.8
25.0
32.6
28.9
30
25
35
30
10
10
8
10
AHR60D
6HK16502025
46.2
28.8
25.0
32.6
28.9
30
25
35
30
10
10
8
10
6HK16502525
57.7
35.0
31.3
39.8
36.1
35
35
40
40
8
8
8
8
1. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
2. Stated sizes are for 75°C, copper wire only. If wire other than non-plated, 75°C ambient, copper wire is used, consult applicable tables of the NEC and local codes.
3. 1st Circuit includes the blower motor amps.
TABLE 10:
AIR FLOW DATA (CFM)
1
Models
Blower
Motor Speed
External Static Pressure (in. wc.)
0.10
0.20
0.30
0.40
0.50
0.60
0.70
208 Volt
AHR18B3XH21
High
1024
1000
970
930
860
810
NA
Medium
756
731
700
670
620
550
NA
Low
557
531
495
445
375
315
195
AHR24B3XH21
High
995
970
935
900
925
795
645
Medium
820
810
780
745
695
545
485
Low
715
695
640
405
370
375
220
AHR30B3XH21
High
1380
1315
1245
1160
1075
990
885
Medium
1060
1040
1005
955
890
860
820
Low
1035
980
910
825
770
685
485
AHR36B3XH21
High
1410
1335
1270
1190
1110
990
820
Medium
1215
1170
1115
1050
935
850
740
Low
950
935
895
855
NA
NA
NA
AHR42C3XH21
High
1800
1725
1645
1545
1360
1200
1050
Medium
1535
1480
1415
1280
1155
1010
870
Low
1225
1195
1095
1025
925
825
680
Continuation on Page 12.