GUIDE SPECIFICATIONS

GENERAL

Units shall be manufactured by York International Unitary 
Products Group in an ISO 9001 certified facility.

York's Sunline 2000

TM

 units are convertible single package-

units. Although the units are primarily designed for curb 
mounting on a roof, they can also be slab-mounted at ground 
level or set on steel beams above a finished roof. Cooling 
only and cooling with gas heat models are available with a 
wide variety of factory-mounted options and field-installed 
accessories to make them suitable for almost every applica-
tion. All units are self-contained and assembled on full perim-
eter base rails with holes in the four corners for overhead 
rigging. Every unit is completely piped, wired, charged and 
tested at the factory to simplify the field installation and to 
provide years of dependable operation. All models (including 
those with an economizer) are suitable for either bottom or 
horizontal duct connections. Models with power exhaust are 
suitable for bottom duct connections only. For bottom duct, 
remove the sheet metal panels from the supply and return air 
openings through the base of the unit. For horizontal duct, 
remove the supply and return air panels on the rear of the 
unit. 

All non-Scroll compressors include crankcase heaters and all 
compressors have internal pressure relief. Every refrigerant 
circuit includes a liquid line filter-drier, a discharge line high 
pressure switch and a suction line with a freezestat and low 
pressure/loss of charge switch.The unit control circuit 
includes a 75 VA transformer, a 24-volt circuit breaker and a 
relay board with a compressor lockout circuit, a terminal strip 
for thermostat wiring, plus an additional set of pin connectors 
to simplify the interface of additional field controls. All units 
have long lasting powder paint cabinets with 1000 hour salt 
spray test approval under ASTMB117 procedures. All models 
are CSA listed. All models include a 1-year limited warranty 
on the complete unit. Compressors and electric heater ele-
ments carry a 5-year warranty. Aluminized steel tubular heat 
exchangers carry a 10-year warranty.

DESCRIPTION

Units shall be factory-assembled, single packaged, Electric 
Cooling/Gas Heat,  Electric Cooling/Optional Electric Heat 
and designed for outdoor mounted installation.

The 3 thru 5 ton units shall have SEER ratings of 10.0 and 
the 6 ton unit shall have minimum EER ratings of 9.0. They 
shall have built-in field convertible duct connections for down 
discharge supply/return or horizontal discharge supply/return, 
and be available with factory installed options or field installed 
accessories. The units shall be factory wired, piped, charged 
with R-22 refrigerant and factory tested prior to shipment. All 
unit wiring shall be both numbered and color coded. All units 
the cooling performance shall be rated in accordance with 
DOE and ARI test procedures. Units shall be CSA listed, 
classified to ANSI Z21.47, UL 1995/CSA No. 236 standards.

UNIT CABINET

Unit cabinet shall be constructed of G90 galvanized steel, 
with exterior surfaces coated with a non-chalking, powdered 
paint finish, certified at 1000 hours salt spray test per 
ASTMB117 standards. Indoor blower section shall be insu-
lated with a minimum 1/2” thick insulation, coated on the air-
side. Aluminum foil faced insulation shall be used in the 
furnace compartment and be fastened with ridged fasteners 
to prevent insulation from entering the air stream. Cabinet 
panels shall be “large” size, easily removable for servicing 
and maintenance. Full perimeter base rails shall be provided 
to assure reliable transit of equipment, overhead rigging and 
proper sealing on roof curb applications. Disposable 1" filters 
shall be furnished and be accessible through a removable 
access door, sealed airtight. Units filter track shall be 
designed to accommodate either 1” or 2” filters. Fan perfor-
mance measuring ports shall be provided on the outside of 
the cabinet to allow accurate air measurements of evaporator 
fan performance without removing panels or creating air by-
pass of the coils. Condensate pan shall be internally sloped 
and conform to ASHRAE 62-89 self-draining standards. Con-
densate connection shall be a minimum of 3/4” I.D. female 
and be a ridged mount connection.

INDOOR (EVAPORATOR) FAN ASSEMBLY

The indoor fan shall be direct drive, multi-speed, or a factory 
installed belt drive assembly that includes an adjustable pitch 
motor pulley. Job site selected brake horsepower (B.H.P.) shall 
not exceed the motors nameplate horsepower rating, plus the 
service factor. Units shall be designed not to operate above 
service factor. Fan wheel shall be double-inlet type with for-
ward-curved blades, dynamically balanced to operate 
smoothly throughout the entire range of operation. Airflow 
design shall be constant air volume. Bearings shall be sealed 
and permanently lubricated for longer life and no maintenance.

OUTDOOR (CONDENSER) FAN ASSEMBLY

The outdoor fan shall be of the direct-driven propeller type, 
discharge air vertically, have aluminum blades riveted to a 
corrosion resistant steel spider bracket and shall be dynami-
cally balanced for smooth operation. The outdoor fan motor 
shall be totally enclosed with permanently lubricated bear-
ings, internally protected against overload conditions and 
staged independently.

REFRIGERANT COMPONENTS

Compressor:

a.

Shall be  internally protected with internal high-pres-
sure relief and over temperature protection.

b.

Shall have internal spring isolation and sound muf-
fling to minimize vibration and noise, and be exter-
nally isolated on a dedicated, independent 
mounting.

Coils:

a.

Evaporator and condenser coils shall have alumi-
num plate fins mechanically bonded to seamless 

Summary of Contents for 36

Page 1: ...oof curb slab roof jack or frame All units include Powder Paint finish that meets ASTM B 117 1000 hour salt spray standards Permanently lubricated motors Bottom or side air discharge configuration cap...

Page 2: ...COOLING UNIT POWER CIRCUIT 460 3 60 BELT DRIVE INDOOR BLOWER DIAGRAM 36 19 COOLING UNIT POWER CIRCUIT 575 3 60 DIRECT DRIVE INDOOR BLOWER DIAGRAM 37 20 COOLING UNIT POWER CIRCUIT 575 3 60 BELT DRIVE I...

Page 3: ...072 6 Ton 3 0 6 2 5 NOMINAL COOLING CAPACITY FACTORY INSTALLED HEAT A Cooling Only D 8 C G 4 N PRODUCT GENERATION 3 3rd Generation 8 8th Generation PRODUCT CATEGORY D Single Package Air Conditioner A...

Page 4: ...applicable and the temperature limit switch on gas heat units The unit control board will alarm on ignition failures compressor lockouts and repeated limit switch trips Nuisance Trip Protection To pr...

Page 5: ...ng return motor actuator capa ble of introducing up to 100 outdoor air with nominal 1 leakage type dampers The enthalpy system contains one sensor that monitors the outdoor air and determines when the...

Page 6: ...er the outdoor air intake dampers are opened for free cooling the exhaust fan will be energized to prevent the condi tioned space from being over pressurized during econo mizer operation The power exh...

Page 7: ...of each system This constitutes and expectation to any specification or guaran tee requiring a dBA value or sound data in any other form than sound power level ratings 2 At a distance of 10 feet from...

Page 8: ...0 34 33 29 25 21 17 13 62 33 3 7 33 33 33 29 25 21 17 31 4 0 31 31 31 27 23 19 15 57 34 3 6 34 34 34 30 26 22 18 32 4 0 32 32 32 28 24 20 16 72 39 3 7 27 24 20 17 14 37 4 1 26 23 20 16 13 67 36 3 6 34...

Page 9: ...45 42 37 32 27 22 17 62 43 4 9 43 43 43 38 33 28 23 40 5 4 40 40 40 35 30 26 21 57 43 4 9 43 43 43 38 33 28 23 40 5 4 40 40 40 35 30 25 20 72 53 5 0 36 32 28 23 19 51 5 5 35 31 26 22 17 67 46 4 9 44...

Page 10: ...5 50 47 42 36 30 24 18 62 48 5 8 48 48 48 42 37 31 25 44 6 4 44 44 44 38 32 26 20 57 46 5 8 46 46 46 40 35 29 23 42 6 4 42 42 42 36 31 25 19 72 60 6 0 42 37 32 26 21 57 6 6 41 36 30 25 20 67 54 5 8 52...

Page 11: ...9 66 61 54 47 40 32 25 62 64 7 0 64 64 64 56 49 42 35 58 7 8 58 58 58 51 43 36 29 57 64 7 0 64 64 64 56 49 42 34 58 7 7 58 58 58 50 43 36 29 72 75 7 1 56 49 43 36 29 76 8 0 55 48 41 34 27 67 70 7 1 68...

Page 12: ...0 580 RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 1700 1600 1500 1400 1055 875 1300 1036 780 1066 850 1200 1011 735 1047 765 1075 800 1100 987 690 1028 720 1060 750 1084 775...

Page 13: ...WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2000 1103 1270 1900 1085 1210 1800 1064 1145 1102 1180 1700 1040 1075 1081 1115 1121 1140 1600 1020 1005 1060 1050 1100 1085 1500 1003...

Page 14: ...5 830 RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2500 2400 1193 1665 2300 1170 1580 1202 1620 2200 1148 1480 1180 1530 2100 1121 1385 1155 1425 1190 1475 2000 1100 1285 1133...

Page 15: ...PM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 3200 3000 2800 1245 2190 2600 1193 1920 1222 1990 1250 2060 2400 1142 1675 1173 1730 1205 1800 1234 1885 2200 1090 1380 1124 1450 1155 1550 1...

Page 16: ...24 800 1644 770 1531 710 6 1 HI 2101 1260 2000 1205 1914 1155 1830 1110 5 1 0 60 0 20 0 30 0 40 0 50 UNIT TONNAGE MOTOR SPEED UNIT TONNAGE MOTOR SPEED 3 1 4 1 5 1 AVAILABLE EXTERNAL STATIC PRESSURE IW...

Page 17: ...h the economizer is greater for 100 outdoor air than for 100 return air If the resistance of the return air duct system is less than 0 25 IWG the unit will deliver less CFM during full economizer oper...

Page 18: ...45107462 6 8 8 2 13 15 2CE045110462 10 1 12 1 17 9 20 2CE045115462 13 6 16 4 23 2 25 2CE045120462 19 5 23 5 32 1 35 575 3 60 5 0 36 0 0 8 2 2 None 8 7 15 2CE04511058 10 6 10 2 14 9 15 2CE04511558 15 9...

Page 19: ...15 3 22 4 25 2CE04512058 21 2 20 4 28 8 30 2CE04513058 30 4 29 3 39 9 40 D CE CG 072 6 0 208 3 60 18 9 146 0 1 3 6 8 None 31 7 40 2CE045105252 4 11 1 31 7 40 2CE045107252 5 6 15 5 31 7 40 2CE04511025...

Page 20: ...07462 6 8 8 2 13 5 15 2CE045110462 10 1 12 1 18 4 20 2CE045115462 13 6 16 4 23 7 25 2CE045120462 19 5 23 5 32 6 35 575 3 60 5 0 36 0 0 8 2 0 None 8 9 15 2CE04511058 10 6 10 2 15 2 20 2CE04511558 15 9...

Page 21: ...8 15 9 15 3 21 6 25 2CE04512058 21 2 20 4 28 30 2CE04513058 30 4 29 3 39 1 40 D CE CG 072 6 0 208 3 60 18 9 146 0 1 3 5 0 None 29 9 40 2CE045105252 4 11 1 29 9 40 2CE045107252 5 6 15 5 29 9 40 2CE0451...

Page 22: ...400 3400 3400 CONDENSER COILS Rows Deep 1 1 1 2 Fins Per Inch 16 16 22 16 Face Area Sq Ft 17 1 17 1 17 1 16 7 COMPRESSOR Qty Per Unit Scroll Type 1 1 1 1 AIR FILTERS Quantity Per Unit 15 X 20 X 1 or 2...

Page 23: ...S WHEN THE THERMOSTAT SWITCHES TO THE SET BACK POSITION COOLING HEATING ELECTRONIC THERMOSTAT MULTI STAGE RH RC Y W G R Y1 W1 C G ADD JUMPER THERMOSTAT1 TERMINALS UNIT TERMINAL STRIP TB1 24 VOLT TRANS...

Page 24: ...255040 YTG A 0506 24 Unitary Products Group FIGURE 3 UNIT DIMENSIONS 3 6 TON COOLING ONLY ELECTRIC HEAT FRONT VIEW FIGURE 4 UNIT DIMENSIONS 3 6 TON COOLING GAS HEAT FRONT VIEW...

Page 25: ...255040 YTG A 0506 Unitary Products Group 25 FIGURE 5 UNIT WITH ECONOMIZER RAINHOOD DETAIL A FIGURE 6 UNIT WITH FIXED OUTDOOR AIR MOTORIZED DAMPER RAINHOOD DETAIL B...

Page 26: ...RY See Detail B MOUNTING BRACKET FOR DICONNECT SWITCH Shipped attached to the blower housing inside the blower compartment FIELD SUPPLIED DISCONNECT SWITCH LOCATION BLOWER MOTOR ACCESS FILTER ACCESS D...

Page 27: ...255040 YTG A 0506 Unitary Products Group 27 FIGURE 9 TYPICAL APPLICATIONS...

Page 28: ...CG036N040 605 134 132 168 171 90 89 88 112 113 114 DCG036N079 625 139 136 173 177 93 92 91 115 117 118 DCE048 Cooling Electric 615 137 134 171 174 91 90 89 113 115 116 DCG048N060 665 148 145 184 188 9...

Page 29: ...SIC UNIT DCE Cooling Only 565 615 640 720 DCG Gas Electric N040 605 N060 665 N079 625 700 780 N099 685 710 790 OPTIONS OR ACCY Economizer 50 Motorized Damper 26 Electric Heater 5 7 kW 18 10 15 kW 23 2...

Page 30: ...255040 YTG A 0506 30 Unitary Products Group FIGURE 12 COOLING UNIT WITH GAS HEAT CONTROL CIRCUIT 208 230V AND 460V DIAGRAM...

Page 31: ...255040 YTG A 0506 Unitary Products Group 31 FIGURE 13 COOLING UNIT WITH GAS HEAT CONTROL CIRCUIT 575 VOLT DIAGRAM...

Page 32: ...255040 YTG A 0506 32 Unitary Products Group FIGURE 14 COOLING UNIT WITH ELECTRIC HEAT CONTROL CIRCUIT 208 230V 460V AND 575V DIAGRAM...

Page 33: ...255040 YTG A 0506 Unitary Products Group 33 FIGURE 15 COOLING UNIT POWER CIRCUIT 208 230 3 60 DIRECT DRIVE INDOOR BLOWER DIAGRAM...

Page 34: ...255040 YTG A 0506 34 Unitary Products Group FIGURE 16 COOLING UNIT POWER CIRCUIT 208 230 3 60 BELT DRIVE INDOOR BLOWER DIAGRAM...

Page 35: ...255040 YTG A 0506 Unitary Products Group 35 FIGURE 17 COOLING UNIT POWER CIRCUIT 460 3 60 DIRECT DRIVE INDOOR BLOWER DIAGRAM...

Page 36: ...255040 YTG A 0506 36 Unitary Products Group FIGURE 18 COOLING UNIT POWER CIRCUIT 460 3 60 BELT DRIVE INDOOR BLOWER DIAGRAM...

Page 37: ...255040 YTG A 0506 Unitary Products Group 37 FIGURE 19 COOLING UNIT POWER CIRCUIT 575 3 60 DIRECT DRIVE INDOOR BLOWER DIAGRAM...

Page 38: ...255040 YTG A 0506 38 Unitary Products Group FIGURE 20 COOLING UNIT POWER CIRCUIT 575 3 60 BELT DRIVE INDOOR BLOWER DIAGRAM...

Page 39: ...ent All unit wiring shall be both numbered and color coded All units the cooling performance shall be rated in accordance with DOE and ARI test procedures Units shall be CSA listed classified to ANSI...

Page 40: ...gas valve Venter wheel shall be constructed of stainless steel for corrosion resistance The heat exchanger shall be of the tubular type constructed of T1 40 aluminized steel for corrosion resistance...

Page 41: ...unit Water eliminator fil ters shall be provided Simultaneous economizer com pressor operation is also possible Dampers shall fully close on power loss OTHER PRE ENGINEERED ACCESSORIES AVAILABLE ROOF...

Page 42: ...255040 YTG A 0506 42 Unitary Products Group...

Page 43: ...255040 YTG A 0506 Unitary Products Group 43...

Page 44: ...bject to change without notice Printed in U S A 255040 YTG A 0506 Copyright 2006 by Unitary Products All rights reserved Supersedes 530 18 TG1Y 500 Unitary 5005 Norman Products York OK Group Drive 730...

Reviews: