Electric Heating (ZJ/ZR/ZF***C/E Models)

Nickel chromium electric heating elements shall be provided as 
required by the application with 1 or 2 stage control, as 
required, from 13.5 KW to 72 KW capacities. The heating 
section shall have a primary limit control(s) and automatic reset 
to prevent the heating element system from operating at an 
excessive temperature. Units with Electric Heating shall be 
wired for a single point power supply with branch circuit fusing 
(where required). 

Unit Operating Characteristics

Unit shall be capable of starting and running at 125° F outdoor 
temperature, exceeding maximum load criteria of ARI Standard 
340/360. The compressor, with standard controls, shall be 
capable of operation down to 25° F outdoor temperature. 
Accessory low ambient kit shall be available for operation to 0° 
F. Unit shall be provided with fan time delay to prevent cold air 
delivery before heat exchanger warms up (Gas heat only). 

Electrical Requirements

All unit power wiring shall enter unit cabinet at a single factory 
provided location and be capable of side or bottom entry, to 
minimize roof penetrations and avoid unit field modifications. 
Separate side and bottom openings shall be provided for the 
control wiring. 

Standard Limited Warranties

• Compressor 5 Years

• Heat Exchanger 10 Years

• Electric Heat Element 5 Years

• Other Parts 1 Year

Optional Outdoor Air (Shall be made available by either/or): 

Electronic Enthalpy Automatic Economizer - 

Outdoor 

and return air dampers that are interlocked and positioned 
by a fully-modulating, spring-return damper actuator. The 
maximum leakage rate for the outdoor air intake dampers 
shall not exceed 2% when dampers are fully closed and 
operating against a pressure differential of 0.5 IWG. A 
unit-mounted potentiometer shall be provided to adjust 
the outdoor and return air damper assembly to take in 
CFM of outdoor air to meet the minimum ventilation 
requirement of the conditioned space during normal 
operation. During economizer operation, a mixed-air 
temperature control shall modulate the outdoor and return 
air damper assembly to prevent the supply air 
temperature from dropping below 55°F. Changeover from 
compressor to economizer operation shall be provided by 
an integral electronic enthalpy control that feeds input into 
the basic module. The outdoor intake opening shall be 
covered with a rain hood that matches the exterior of the 
unit. Water eliminator/filters shall be provided. 
Simultaneous economizer/compressor operation is also 
possible. Dampers shall fully close on power loss. 

Motorized Outdoor Air Dampers - 

Outdoor and return 

air dampers that are interlocked and positioned by a 2-

position, spring-return damper actuator. The maximum 
leakage rate for the outdoor air intake dampers shall not 
exceed 2% when dampers are fully closed and operating 
against a pressure differential of 0.5 IWG. A unit-mounted 
potentiometer shall be provided to adjust the outdoor and 
return air damper assembly to take in the design CFM of 
outdoor air to meet the ventilation requirements of the 
conditioned space during normal operation. Whenever the 
indoor fan motor is energized, the dampers open up to 
one of two pre-selected positions - regardless of the 
outdoor air enthalpy. Dampers return to the fully closed 
position when the indoor fan motor is de-energized. 
Dampers shall fully close on power loss. 

Other Pre-engineered Accessories Available

Roof Curb - 

14" high, full perimeter curb with wood nailer 

(shipped knocked-down). 

100% Barometric Relief Damper - 

Contains a rain hood, 

air inlet screen, exhaust damper and mounting hardware. 
Used to relieve internal air pressure through the unit. 

Propane Conversion Kit - 

Contains new orifices and gas 

valve parts to convert from natural to L.P. gas. One per 
unit required. 

High Altitude - Natural Gas - 

Contains orifices required 

for applications between 2000 and 6000 feet altitude. 

High Altitude - Propane Gas

 - Contains orifices required 

for applications between 2000 and 6000 feet altitude. 
Must be used with propane conversion kit. 

Burglar Bars - 

Designed to work with above roof curbs, 

depending on unit model. Fits duct openings of curb 
supply and return air openings. 

Side Duct Flange - 

Supply and return air duct flanges for 

side duct applications. Do not use on units with power 
exhaust. 

High Static Drive - 

May include a belt, blower pulley, 

motor pulley or a motor change to enhance blower 
performance. 

Wood Skid - 

Allows unit to be handled with 90" forks. 

Economizer/motorized Damper Rain Hood
(ZJ/ZR/ZFN/E/C300 only) - 

Contains all hood panels and 

the hardware for assembling. 

Anti-Recycle Timer - 

Assures 5-minute off time between 

compressor cycles.

Low Ambient Kit - 

Provides unit cooling operation down 

to 0 °F. 

Coil Guard Kit

 - Guard for cooling coil. 

OTHER FACTORY INSTALLED OPTIONS

Power Exhaust Option

 - To work in conjunction with 

economizers.

• Stainless Steel Heat Exchanger

• Stainless Steel Drain Pan

• Technicoat Phenolic Coated Condenser And 

Evaporator Coil

Electronic Single Enthalpy Economizer

Summary of Contents for 251934-YTG-J-0910

Page 1: ...steel beams above a finished roof All ZJ ZR ZF units are self contained and assembled on rigid full perimeter base rails allowing for overhead rigging Every unit is completely charged wired piped and...

Page 2: ...of Contents Description 1 Table of Contents 2 Component Location 3 Nomenclature 4 Features and Benefits 5 Guide Specifications 9 Physical Data 15 Capacity Performance 21 Airflow Performance 49 Sound...

Page 3: ...r Motor Electric Heater Location Optional Electric Electric Units Belt Drive Blower Motor 14 Gauge Base Rails with Lifting Holes Filter Drier Solid Core Thermal Expansion Valve Copper Tube Aluminum Fi...

Page 4: ...APS Johnson Controller UNT 1126 N2 protocol DFS APS Honeywell Controller DFS APS Novar Controller DFS APS Simplicity IntelliComfort Controller Simplicity IntelliComfort Controller Simplicity LINC York...

Page 5: ...option The assembly includes a rain hood with a damper that can be set for 10 15 or 25 outdoor air With bottom duct connections the fixed outdoor air intake assembly should be mounted over the opening...

Page 6: ...air and determines when the air is cool enough and dry enough to provide free cooling The rainhood is painted to match the basic unit and must be field assembled before installing BAS Ready Economizer...

Page 7: ...s a switch sized to the largest electric heat available for the particular unit is provided Factory installed option only Double Wall Construction Optional double wall construction is available to pro...

Page 8: ...ch the basic unit and must be field assembled before installing Motorized Outdoor Air Intake Damper Includes a slide in plug in damper assembly with a 2 position spring return motor actuator which ope...

Page 9: ...mounted installation The 15 ton unit shall have a minimum EER rating of 12 4 The 17 5 ton unit shall have a minimum EER rating of 12 1 The 20 ton unit shall have a minimum EER rating of 11 6 The 25 to...

Page 10: ...system shall provide at least 15 F of sub cooling at design conditions e All models shall have four independent circuits f Hot gas bypass option shall be factory installed on compressor 1 discharge l...

Page 11: ...that matches the exterior of the unit Water eliminator filters shall be provided Simultaneous economizer compressor operation is also possible Dampers shall fully close on power loss Motorized Outdoo...

Page 12: ...t calls for second stage cooling the RCB senses a signal through Y1 Y2 and engages circuit 1 and circuit 2 in the cooling mode Indoor blower operation is initiated upon a call for first stage cooling...

Page 13: ...TG J 0910 Johnson Controls Unitary Products 13 Reheat Control Board Reheat Controls Part 1 R Y1 Y2 G W1 OCC C W2 P4 P5 P6 P3 COM HGRR HGR HUM K1 K2 K4 K3 MODE SELECTION JUMPER DEHUMIDISTAT HARNESS CON...

Page 14: ...roducts Reheat Controls Part 2 UCB UNIT CONTROL BOARD RHB REHEAT CONTROL BOARD RHTB REHEAT TERMINAL BLOCK HUM HUMIDIFY TERMINAL RHR REHEAT RELAY REHEAT SOLENOID 3 REHEAT SOLENOID 1 REHEAT SOLENOID 2 R...

Page 15: ...40 320 240 320 240 320 240 320 AFUE Steady state efficiency 80 80 80 80 80 80 80 80 No burners 6 8 6 8 6 8 6 8 No stages 2 2 2 2 2 2 2 2 Temperature Rise Range F 20 50 30 60 20 50 30 60 20 50 30 60 20...

Page 16: ...15 18 X 15 Type Centrifugal Centrifugal Centrifugal Centrifugal Motor Sheave 1VP65 1VP65 1VP60 1VP60 1VP60 1VP60 1VP60 1VP75X 1VP75X Blower Sheave BK110 BK090 BK110 BK090 BK110 BK090 1B5V94 1B5V110 1...

Page 17: ...burners 6 8 6 8 6 8 No stages 2 2 2 2 2 2 Temperature Rise Range F 20 50 30 60 20 50 30 60 20 50 30 60 Gas Limit Setting F 195 195 195 195 195 195 Gas piping connection in 1 1 1 1 1 1 DIMENSIONS inche...

Page 18: ...5 18 X 15 18 X 15 Type Centrifugal Centrifugal Centrifugal Motor Sheave 1VP65 1VP65 1VP60 1VP60 1VP60 1VP75X 1VP75X Blower Sheave BK110 BK090 BK110 BK090 1B5V94 1B5V110 1B5V94 Belt BX85 BX81 BX78 BX75...

Page 19: ...80 80 80 80 80 No burners 6 8 6 8 6 8 6 8 No stages 2 2 2 2 2 2 2 2 Temperature Rise Range F 20 50 30 60 20 50 30 60 20 50 30 60 20 50 30 60 Gas Limit Setting F 195 195 195 195 195 195 195 195 Gas pip...

Page 20: ...BX85 BX81 BX78 BX75 BX78 BX75 BX78 5VX840 5VX860 Motor HP each 5 5 5 7 5 5 7 5 7 5 10 15 RPM 1725 1725 1725 1725 1725 1725 1725 1725 1725 Frame size 184T 184T 184T 213T 184T 213T 213T 215T 254T FILTE...

Page 21: ...0 5 152 4 124 3 96 3 67 225 5 10 2 225 5 194 5 166 9 139 3 111 6 212 9 11 6 212 9 191 0 162 9 134 8 106 7 62 208 2 10 1 208 2 208 2 208 2 180 6 152 9 125 3 197 1 11 5 197 1 197 1 197 1 169 0 140 9 112...

Page 22: ...106 7 80 9 157 0 18 1 157 0 152 6 126 8 100 9 75 1 62 158 1 16 3 158 1 158 1 162 5 136 7 110 9 85 1 145 8 18 0 145 8 145 8 145 8 129 5 103 6 77 8 57 159 3 16 3 159 3 159 3 157 2 131 4 105 6 79 8 148...

Page 23: ...7 12 0 262 7 234 8 201 5 168 1 134 8 246 5 13 5 246 5 229 7 195 7 161 8 127 8 62 227 5 11 7 227 5 227 5 227 5 194 2 160 8 127 5 224 9 13 4 224 9 224 9 224 9 190 9 157 0 123 0 57 239 2 11 8 239 2 239 2...

Page 24: ...3 4 154 0 124 7 95 3 172 5 20 9 172 5 172 5 147 9 118 5 89 0 62 185 9 19 0 185 9 185 9 180 1 150 8 121 5 92 1 173 0 20 9 173 0 173 0 168 3 138 8 109 3 79 8 57 184 3 18 9 184 3 184 3 180 5 151 1 121 8...

Page 25: ...3 307 3 260 5 224 3 188 0 151 8 288 4 16 2 288 4 252 8 216 6 180 3 144 1 62 284 5 14 1 284 5 284 5 270 0 233 8 197 6 161 3 270 8 16 0 270 8 270 8 262 2 226 0 189 7 153 4 57 276 1 14 3 276 1 276 1 276...

Page 26: ...7 8 175 3 142 8 110 3 198 3 24 8 198 3 198 3 167 8 134 9 102 0 62 209 0 22 5 209 0 209 0 208 4 175 9 143 4 110 9 192 7 24 8 192 7 192 7 192 7 163 9 131 0 98 1 57 208 1 22 5 208 1 208 1 206 8 174 3 141...

Page 27: ...68 0 333 1 305 4 277 8 250 1 346 8 23 1 346 8 317 5 287 8 258 1 228 4 62 342 2 21 2 342 2 342 2 342 2 314 5 286 9 259 2 322 2 22 7 322 2 322 2 322 2 292 5 262 8 233 1 57 328 7 20 9 328 7 328 7 328 7 3...

Page 28: ...276 5 249 3 215 6 182 0 148 4 253 4 32 1 253 4 240 5 207 3 174 1 140 9 62 258 6 28 9 258 6 258 6 267 4 233 8 200 1 166 5 238 2 31 6 238 2 238 2 238 2 224 8 191 6 158 4 57 254 7 29 0 254 7 254 7 282 7...

Page 29: ...0 127 7 90 5 67 232 3 11 5 232 3 208 9 171 7 134 4 97 2 218 2 12 7 218 2 204 6 167 3 130 1 92 8 62 214 5 11 3 214 5 214 5 214 5 177 3 140 0 102 7 201 9 12 5 201 9 201 9 201 9 164 6 127 4 90 1 57 211...

Page 30: ...161 2 16 8 161 2 161 2 157 7 128 5 99 4 70 2 150 2 18 4 150 2 150 2 146 3 117 1 88 0 58 8 6750 72 190 0 17 1 170 7 137 5 104 2 71 0 175 2 18 6 164 4 131 2 98 0 64 8 67 172 6 17 0 172 6 167 6 141 5 10...

Page 31: ...13 1 110 0 106 8 56 8 25 0 107 2 8 9 107 2 105 0 94 6 48 9 20 0 7500 72 156 9 10 2 146 7 10 8 67 141 0 9 4 92 8 55 6 18 3 131 8 10 0 87 8 50 6 13 3 62 122 5 8 5 112 9 110 0 85 0 65 0 115 1 9 2 107 4 1...

Page 32: ...0 9 47 7 14 4 83 6 12 0 83 6 75 4 42 2 9 0 57 89 6 11 1 89 6 87 0 58 2 24 9 83 8 11 9 90 0 83 4 46 0 17 0 7500 72 115 9 12 5 105 7 13 1 67 104 3 11 9 72 8 35 5 95 1 12 5 67 8 30 5 62 92 9 11 3 91 0 85...

Page 33: ...7 301 4 258 9 209 2 159 5 109 9 282 3 16 2 282 3 254 1 204 4 154 7 105 0 62 273 9 14 6 273 9 273 9 260 1 210 4 160 8 111 1 259 7 16 0 259 7 259 7 252 2 202 5 152 8 103 2 57 270 8 14 4 270 8 270 8 270...

Page 34: ...66 8 57 207 3 21 2 207 3 207 3 187 2 148 4 109 5 70 6 193 6 23 1 193 6 193 6 164 6 125 7 86 8 47 9 9000 72 244 2 21 5 217 3 173 0 128 8 84 5 223 8 23 3 207 9 163 6 119 4 75 1 67 223 2 21 3 223 2 220 7...

Page 35: ...9 1 11 0 149 1 148 4 104 1 59 8 15 6 139 5 11 8 139 5 138 7 94 4 50 1 5 8 10000 72 180 6 12 8 37 7 169 7 13 5 32 4 67 165 5 12 0 124 4 51 4 1 7 155 0 12 8 114 8 46 5 62 159 0 11 1 138 0 129 7 80 0 30...

Page 36: ...19 5 14 4 98 0 95 2 50 9 6 6 109 1 15 2 95 0 89 4 45 1 0 8 57 110 7 14 3 110 7 109 5 65 2 20 9 101 1 15 1 101 1 99 8 55 5 11 2 10000 72 137 1 15 7 16 7 126 3 16 5 11 5 67 123 7 15 0 86 0 31 7 113 2 15...

Page 37: ...370 6 314 9 252 8 190 7 128 6 347 6 23 0 347 6 306 8 244 7 182 6 120 5 62 337 7 20 6 337 7 337 7 303 9 241 8 179 7 117 6 319 8 22 3 319 8 319 8 292 6 230 5 168 4 106 3 57 332 2 20 6 332 2 332 2 317 0...

Page 38: ...133 0 84 4 57 250 4 28 5 250 4 250 4 244 1 195 5 146 9 98 3 231 0 31 1 231 0 231 0 224 9 176 3 127 7 79 1 11250 72 307 0 29 9 263 0 207 6 152 3 96 9 283 0 32 7 246 1 190 8 135 4 80 1 67 278 3 29 5 278...

Page 39: ...9 25 3 159 9 16 0 150 0 141 8 83 9 21 9 12500 72 199 6 18 0 65 6 55 0 190 8 19 2 64 2 52 0 67 175 0 17 4 99 8 85 0 169 0 18 6 94 4 80 0 62 166 9 16 4 137 0 135 0 53 8 27 2 159 7 17 6 126 0 104 0 50 3...

Page 40: ...4 65 0 9 6 62 136 2 20 4 120 0 99 0 40 0 127 5 21 6 120 0 91 0 35 7 57 131 5 18 6 131 5 125 0 69 0 12 0 122 1 21 2 122 1 119 4 64 0 8 7 12500 72 164 4 23 0 60 0 43 0 155 7 24 2 58 6 40 0 67 151 0 22 3...

Page 41: ...2 126 4 99 6 67 227 8 11 7 227 8 194 4 167 5 140 6 113 7 212 2 12 9 212 2 194 0 167 2 140 4 113 6 62 208 0 11 4 208 0 208 0 208 0 181 1 154 2 127 3 194 3 12 7 194 3 194 3 194 3 167 5 140 7 113 9 57 26...

Page 42: ...107 5 84 5 150 4 18 3 150 4 147 3 124 4 101 6 78 7 62 151 4 16 7 151 4 151 4 139 3 116 3 93 2 70 2 138 4 18 1 138 4 138 4 122 5 99 7 76 8 53 9 57 157 5 16 8 157 5 157 5 153 9 130 9 107 9 84 9 146 7 1...

Page 43: ...14 2 259 6 232 5 200 7 168 8 137 0 243 7 15 6 243 7 222 6 191 6 160 5 129 4 62 240 1 14 1 240 1 240 1 240 1 208 2 176 4 144 6 225 0 15 4 225 0 225 0 225 0 194 0 162 9 131 8 57 241 5 14 0 241 5 241 5 2...

Page 44: ...5 4 127 1 98 7 179 4 21 7 179 4 179 4 150 5 121 4 92 3 62 185 5 19 9 185 5 185 5 180 8 152 4 124 1 95 7 174 5 21 6 174 5 174 5 168 7 139 6 110 5 81 4 57 184 0 19 9 184 0 184 0 183 1 154 7 126 3 97 9 1...

Page 45: ...317 0 279 3 235 1 190 9 146 7 299 0 21 2 299 0 264 8 225 1 185 5 145 8 62 290 5 19 0 290 5 290 5 284 7 240 5 196 3 152 1 275 5 20 8 275 5 275 5 272 6 232 9 193 2 153 5 57 283 0 18 9 283 0 283 0 283 0...

Page 46: ...13 3 184 5 155 6 126 8 230 3 29 1 230 3 207 4 178 5 149 7 120 8 62 227 6 26 5 227 6 227 6 223 7 194 9 166 0 137 2 212 0 28 6 212 0 212 0 212 0 185 7 156 8 127 9 57 228 7 26 6 228 7 228 7 225 1 196 2 1...

Page 47: ...343 6 305 9 258 1 210 3 162 5 324 5 22 5 324 5 296 7 250 1 203 4 156 8 62 319 2 20 0 319 2 319 2 319 2 271 4 223 6 175 8 301 0 22 0 301 0 301 0 301 0 254 4 207 7 161 1 57 308 1 20 1 308 1 308 1 308 1...

Page 48: ...29 0 271 7 246 4 212 4 178 5 144 5 249 0 31 1 249 0 236 7 203 4 170 1 136 8 62 259 7 28 6 259 7 259 7 256 6 222 7 188 7 154 8 242 9 30 8 242 9 242 9 242 9 209 6 176 3 142 9 57 257 9 28 9 257 9 257 9 2...

Page 49: ...rmance includes gas heat exchangers and 2 filters See STATIC RESISTANCE table for additional applications 2 See RPM SELECTION table to determine desired motor sheave setting and to determine the maxim...

Page 50: ...4 85 6000 699 2 11 735 2 60 772 3 06 808 3 49 844 3 88 879 4 24 913 4 55 946 4 80 977 5 01 1007 5 15 1036 5 24 1062 5 25 6400 719 2 55 756 3 03 792 3 49 828 3 92 864 4 32 899 4 67 933 4 98 966 5 24 99...

Page 51: ...7 14 35 1129 14 92 1160 15 47 1192 15 98 1223 16 47 1255 16 94 High Static 15 HP Drive Air Flow CFM Available External Static Pressure IWG1 1 Blower performance includes gas heat exchangers and 2 filt...

Page 52: ...es gas heat exchangers and 2 filters See STATIC RESISTANCE table for additional applications 2 See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous...

Page 53: ...53 1017 4 67 1045 4 74 1071 4 75 6000 734 2 25 770 2 70 806 3 13 841 3 53 877 3 90 911 4 23 944 4 52 977 4 77 1008 4 96 1038 5 09 1066 5 17 1092 5 18 6400 757 2 71 793 3 17 829 3 60 864 4 00 899 4 37...

Page 54: ...includes gas heat exchangers and 2 filters See STATIC RESISTANCE table for additional applications 2 See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum cont...

Page 55: ...ide Duct Air Flow CFM Available External Static Pressure IWG1 1 Blower performance includes gas heat exchangers and 2 filters See STATIC RESISTANCE table for additional applications 2 See RPM SELECTIO...

Page 56: ...12200 1212 15 90 1244 16 34 1276 16 75 1308 17 14 High Static 15 HP Drive 15 HP Field Supplied Drive Air Flow CFM Available External Static Pressure IWG1 1 Blower performance includes gas heat exchang...

Page 57: ...5 HP Field Supplied Drive ZR240 20 Ton Bottom Duct Air Flow CFM Available External Static Pressure IWG1 1 Blower performance includes gas heat exchangers and 2 filters See STATIC RESISTANCE table for...

Page 58: ...10 48 1110 10 89 1141 11 28 1172 11 64 1203 11 99 1234 12 32 1265 12 64 1297 12 94 1330 13 24 1363 13 52 1398 13 79 1434 14 06 10600 1115 11 59 1147 12 00 1178 12 38 1209 12 75 1240 13 10 1271 13 43...

Page 59: ...tional applications 2 See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP 3 kW BHP x 0 838 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 2 2 2 4 2 6 RPM...

Page 60: ...717 2 17 754 2 65 790 3 10 826 3 52 862 3 90 897 4 25 931 4 55 964 4 81 996 5 01 1026 5 15 1054 5 23 1081 5 24 6400 740 2 64 776 3 11 812 3 57 848 3 99 884 4 37 919 4 72 953 5 02 986 5 28 1018 5 48 10...

Page 61: ...5 1129 14 92 1160 15 47 1192 15 98 1223 16 47 1255 16 94 High Static 15 HP Drive Air Flow CFM Available External Static Pressure IWG1 1 Blower performance includes gas heat exchangers and 2 filters Se...

Page 62: ...onal applications 2 See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP 3 kW BHP x 0 838 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 2 2 2 4 2 6 RPM B...

Page 63: ...75 1089 4 76 6000 754 2 35 790 2 79 826 3 21 862 3 61 897 3 97 931 4 29 965 4 58 997 4 81 1028 5 00 1058 5 14 1086 5 21 1112 5 22 6400 779 2 85 814 3 29 850 3 71 886 4 11 921 4 47 955 4 79 989 5 08 10...

Page 64: ...es gas heat exchangers and 2 filters See STATIC RESISTANCE table for additional applications 2 See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous...

Page 65: ...0 11 50 1VP60 BK090 905 950 990 1035 1075 1120 N A 300 25 ZR 7 5 8 63 1VP60 1B5V94 810 850 885 920 960 1000 N A 10 11 50 1VP75X 1B5V110 975 1005 1040 1070 1100 1135 1165 15 17 25 1VP75X 1B5V94 1140 11...

Page 66: ...5 0 HP motor The 7 5 HP motor is required 6 1020 RPM is within the range of the 7 5 HP drives 7 Using the 7 5 HP motor and drive 3 5 turns open will achieve 1020 RPM Example Supply Air Blower Performa...

Page 67: ...Air Size Tons Heat Size Supply Air CFM Cooling Heating Min Max Min Max 180 15 24 4500 7000 4500 7000 32 4500 7000 4500 7000 210 17 5 24 6000 8750 6000 8750 32 6000 8750 6000 8750 240 20 24 6000 9400 6...

Page 68: ...4 1 BK110 BX85 5 1725 0 89 1 15 184T 5 2 6 4 1 1 8 1VP65 8 4 1 BK090 BX81 210 17 5 ZJ ZF 5 1725 0 89 1 15 184T 4 2 5 5 1 1 8 1VP60 10 4 1 3 16 BK110 BX78 7 5 1725 0 91 1 15 213T 4 2 5 5 1 3 8 1VP60 8...

Page 69: ...82 78 75 70 300 25 10000 1 3 1 160 12 5 92 91 91 89 88 88 84 81 76 1 These values have been accessed using a model of sound propagation from a point source into the hemispheric free field The dBA val...

Page 70: ...1 1 7 2 0 0 None 44 3 50 E18 18 0 1 21 7 44 3 50 E36 36 0 2 43 3 63 1 70 E54 54 0 2 65 0 74 0 90 E72 72 0 2 86 6 95 6 110 575 3 60 6 4 40 10 0 0 9 5 9 0 0 None 36 7 40 E18 18 0 1 17 3 36 7 40 E36 36...

Page 71: ...one 141 8 150 E18 13 5 1 37 5 141 8 150 E36 27 0 2 74 9 141 8 150 E54 40 6 2 112 7 175 9 200 E72 54 1 2 150 2 185 2 200 230 3 60 23 0 160 31 5 3 7 26 0 0 0 None 139 3 150 E18 18 0 1 43 3 139 3 150 E36...

Page 72: ...8 110 E18 13 5 1 37 5 104 8 110 E36 27 0 2 74 9 125 4 150 E54 40 6 2 112 7 172 6 175 E72 54 1 2 150 2 181 9 200 230 3 60 16 7 120 26 0 2 1 14 4 10 0 None 103 8 110 E18 18 0 1 43 3 103 8 110 E36 36 0 2...

Page 73: ...9 13 0 5 0 None 77 7 90 E18 18 0 1 21 7 77 7 90 E36 36 0 2 43 3 77 7 90 E54 54 0 2 65 0 87 5 90 E72 72 0 2 86 6 109 1 110 575 3 60 8 7 62 13 5 1 5 10 3 4 0 None 57 7 60 E18 18 0 1 17 3 57 7 60 E36 36...

Page 74: ...0 2 110 E18 13 5 1 37 5 100 2 110 E36 27 0 2 74 9 118 7 125 E54 40 6 2 112 7 165 9 175 E72 54 1 2 150 2 175 2 200 230 3 60 16 7 120 26 0 2 1 20 0 0 0 None 100 2 110 E18 18 0 1 43 3 100 2 110 E36 36 0...

Page 75: ...3 0 0 None 80 5 90 E18 18 0 1 21 7 80 5 90 E36 36 0 2 43 3 80 5 90 E54 54 0 2 65 0 89 1 100 E72 72 0 2 86 6 110 7 125 575 3 60 8 7 62 13 5 1 5 15 4 0 0 None 60 1 70 E18 18 0 1 17 3 60 1 70 E36 36 0 2...

Page 76: ...2 125 E18 13 5 1 37 5 110 2 125 E36 27 0 2 74 9 131 2 150 E54 40 6 2 112 7 178 4 200 E72 54 1 2 150 2 187 7 200 230 3 60 16 7 120 26 0 2 1 20 0 10 0 None 110 2 125 E18 18 0 1 43 3 110 2 125 E36 36 0...

Page 77: ...3 5 0 None 85 5 100 E18 18 0 1 21 7 85 5 100 E36 36 0 2 43 3 85 5 100 E54 54 0 2 65 0 95 3 110 E72 72 0 2 86 6 117 0 125 575 3 60 8 7 62 13 5 1 5 15 4 4 0 None 64 1 70 E18 18 0 1 17 3 64 1 70 E36 36...

Page 78: ...2 13 5 1 5 8 2 0 0 None 51 2 60 E18 18 0 1 17 3 51 2 60 E36 36 0 2 34 6 53 6 60 E54 54 0 2 52 0 62 2 70 E72 72 0 2 69 3 79 5 90 ZJ300 Low Static Drive With Powered Convenience Outlet Size Tons Volt Co...

Page 79: ...60 30 1 225 47 0 3 7 20 0 0 0 None 102 5 125 E18 13 5 1 37 5 102 5 125 E36 27 0 2 74 9 118 7 125 E54 40 6 2 112 7 165 9 175 E72 54 1 2 150 2 175 2 200 230 3 60 30 1 225 47 0 3 7 20 0 0 0 None 102 5 1...

Page 80: ...1 225 47 0 3 7 20 0 10 0 None 112 5 125 E18 13 5 1 37 5 112 5 125 E36 27 0 2 74 9 131 2 150 E54 40 6 2 112 7 178 4 200 E72 54 1 2 150 2 187 7 200 230 3 60 30 1 225 47 0 3 7 20 0 10 0 None 112 5 125 E1...

Page 81: ...0 1 225 47 0 3 7 28 0 0 0 None 109 1 125 E18 13 5 1 37 5 109 1 125 E36 27 0 2 74 9 126 9 150 E54 40 6 2 112 7 174 1 175 E72 54 1 2 150 2 183 4 200 230 3 60 30 1 225 47 0 3 7 26 6 0 0 None 109 1 125 E1...

Page 82: ...1 225 47 0 3 7 28 0 10 0 None 119 1 125 E18 13 5 1 37 5 119 1 125 E36 27 0 2 74 9 139 4 150 E54 40 6 2 112 7 186 6 200 E72 54 1 2 150 2 195 9 200 230 3 60 30 1 225 47 0 3 7 26 6 10 0 None 119 1 125 E1...

Page 83: ...0 23 0 1 5 8 2 0 0 None 47 3 60 E18 18 0 1 17 3 47 3 60 E36 36 0 2 34 6 53 6 60 E54 54 0 2 52 0 62 2 70 E72 72 0 2 69 3 79 5 90 ZR300 Low Static Drive With Powered Convenience Outlet Size Tons Volt Co...

Page 84: ...6 110 E18 13 5 1 37 5 85 6 110 E36 27 0 2 74 9 112 9 125 E54 40 6 2 112 7 160 1 175 E72 54 1 2 150 2 169 4 200 230 3 60 27 2 27 2 203 203 42 5 43 4 3 14 4 0 0 None 84 2 110 E18 18 0 1 43 3 84 2 110 E3...

Page 85: ...2 13 0 0 0 None 62 2 80 E18 18 0 1 21 7 62 2 80 E36 36 0 2 43 3 70 4 80 E54 54 0 2 65 0 81 2 90 E72 72 0 2 86 6 102 9 110 575 3 60 15 1 15 3 135 9 114 23 7 24 1 7 10 3 0 0 None 50 2 60 E18 18 0 1 17 3...

Page 86: ...E18 13 5 1 37 5 95 6 110 E36 27 0 2 74 9 125 4 150 E54 40 6 2 112 7 172 6 175 E72 54 1 2 150 2 181 9 200 230 3 60 27 2 27 2 203 203 42 5 43 4 3 14 4 10 0 None 94 2 110 E18 18 0 1 43 3 94 2 110 E36 36...

Page 87: ...2 2 13 0 5 0 None 67 2 80 E18 18 0 1 21 7 67 2 80 E36 36 0 2 43 3 76 6 80 E54 54 0 2 65 0 87 5 90 E72 72 0 2 86 6 109 1 110 575 3 60 15 1 15 3 135 9 114 23 7 24 1 7 10 3 4 0 None 54 2 70 E18 18 0 1 1...

Page 88: ...18 13 5 1 37 5 90 2 110 E36 27 0 2 74 9 118 7 125 E54 40 6 2 112 7 165 9 175 E72 54 1 2 150 2 175 2 200 230 3 60 27 2 27 2 203 203 42 5 42 5 4 3 20 0 0 0 None 89 8 110 E18 18 0 1 43 3 89 8 110 E36 36...

Page 89: ...2 19 3 0 0 None 68 5 80 E18 18 0 1 21 7 68 5 80 E36 36 0 2 43 3 78 3 80 E54 54 0 2 65 0 89 1 100 E72 72 0 2 86 6 110 7 125 575 3 60 15 1 15 3 135 9 114 23 7 24 1 7 15 4 0 0 None 55 3 70 E18 18 0 1 17...

Page 90: ...18 13 5 1 37 5 100 2 125 E36 27 0 2 74 9 131 2 150 E54 40 6 2 112 7 178 4 200 E72 54 1 2 150 2 187 7 200 230 3 60 27 2 27 2 203 203 42 5 42 5 4 3 20 0 10 0 None 99 8 125 E18 18 0 1 43 3 99 8 125 E36 3...

Page 91: ...2 2 19 3 5 0 None 73 5 90 E18 18 0 1 21 7 73 5 90 E36 36 0 2 43 3 84 5 90 E54 54 0 2 65 0 95 3 110 E72 72 0 2 86 6 117 0 125 575 3 60 15 1 15 3 135 9 114 23 7 24 1 7 15 4 4 0 None 59 3 70 E18 18 0 1 1...

Page 92: ...3 7 24 1 7 8 2 0 0 None 48 1 60 E18 18 0 1 17 3 48 1 60 E36 36 0 2 34 6 53 6 60 E54 54 0 2 52 0 62 2 70 E72 72 0 2 69 3 79 5 90 ZF180 300 Low Static Drive With Powered Convenience Outlet Size Tons Vol...

Page 93: ...4 Second stage heating not required on single stage heating units Jumper is required if there is no Smoke Detector circuit Jumper is required for any combination of R RC or RH 5 5 OCC is an output fr...

Page 94: ...ammable Thermostat 2ET0770010024 includes subbase 2 Terminals A1 and A2 provide a relay output to close the outdoor economizer dampers when the thermostat switches to the set back position 3 TO REMOTE...

Page 95: ...MINALS ON A LIMITED NUMBER OF THERMOSTATS 3 1 2 4 3 1 2 4 Second stage heating not required on single stage heating units Second stage cooling not required on single stage cooling units Jumper is requ...

Page 96: ...8 313 210 17 5 ZJ 2670 2665 85 25 44 477 797 870 520 293 401 580 633 437 320 240 20 ZJ 2702 2697 85 05 44 485 805 878 529 298 406 585 638 443 326 300 25 ZJ 2788 2783 85 25 44 498 833 908 544 306 419 6...

Page 97: ...ood 60 55 Econ Power Exhaust Rain Hood 95 90 Wood Skid 220 220 Roof Curb 190 185 Hot Gas Bypass 10 10 Supply Fan VFD See Supply Fan VFD Weights 1 Weight given is for the maximum heater size available...

Page 98: ...R INTAKE AIR AND POWER EXHAUST RAIN HOODS See detail Y 92 46 5 8 35 1 4 33 2 3 4 3 3 4 B POWER WIRING ENTRY BOTTOM SUPPLY AND RETURN AIR OPENINGS See Note A CONTROL WIRING ENTRY 21 1 2 11 1 8 D GAS SU...

Page 99: ...UST RAIN HOODS See detail Y FIELD SUPPLIED DISCONNECT SWITCH LOCATION BLOWER COMPARTMENT ACCESS Auxiliary DOT PLUG For pressure Drop Reading FRONT VIEW CONTROL BOX ACCESS 21 5 9 3 4 11 1 2 2 3 4 21 1...

Page 100: ...wer exhaust option The covering consists of a heavy black paper composition 3 Replace the side supply and return air compartment panels For side duct applications 1 Replace the side panels on the supp...

Page 101: ...00 Unit Clearances Direction Distance in Direction Distance in Top1 1 Units must be installed outdoors Over hanging structure or shrubs should not obscure condenser air discharge outlet 72 With 36 Max...

Page 102: ...251934 YTG J 0910 102 Johnson Controls Unitary Products Unit Accessory Dimensions ZJ ZR180 300 ZF210 300 Roof Curb ZF180 Roof Curb 25 1 4 14 1 4 115 1 4...

Page 103: ...overall dimension of the ducts allows ductwork penetration between roof joists that are spaced on 72 centers NOTE Ducts can be installed into the curb from the roof All electrical and gas line connec...

Page 104: ...change without notice Printed in U S A 251934 YTG J 0910 Copyright 2010 by Johnson Controls Inc All rights reserved Supersedes 251934 YTG I 1008 Johnson Controls Unitary Products 5005 York Drive Norma...

Reviews: