1133391-YIM-A-1014
50
Johnson Controls Unitary Products
b. If the second stage of heat is required, heater relay (RB)
will be energized.
c. The thermostat will cycle the electric heat to satisfy the
heating requirements of the conditioned space.
Electric Heat Operation Errors
Temperature Limit Interlock
If the UCB senses zero volts from the high temperature limit
interlock, the indoor blower motor is immediately energized.
This limit interlock is monitored regardless of unit operation
status, i.e. the limit is monitored at all times.
If the temperature limit interlock opens three times within one
hour, it will lock-on the indoor blower motor.
Safety Controls
The UCB monitors the temperature limit switch of electric heat
units.
The control circuit includes the following safety controls:
Limit Switch (Ls)
This control is located inside the heater compartment and is set
to open at the temperature indicated in the Electric Heat Limit
Setting Table 23. It resets automatically. The limit switches
operate when a high temperature condition, caused by
inadequate supply air flow occurs, thus shutting down the
heater and energizing the blower.
Reset
Remove the call for heating by lowering the thermostat setting
lower than the conditioned space temperature.
Electric Heat Anticipator Setpoints
It is important that the anticipator setpoint be correct. Too high
of a setting will result in longer heat cycles and a greater
temperature swing in the conditioned space. Reducing the
value below the correct setpoint will give shorter “ON” cycles
and may result in the lowering of the temperature within the
conditioned space. Refer to Table 24 for the required electric
heat anticipator setting, for electronic thermostats refer to
thermostat manufacturer’s installation instructions.
Table 23: Electric Heat Limit Setting
UNIT (TONS)
VOLTAGE
HEATER
kW
LIMIT
SWITCH
OPENS °F
ZR037 (3)
208/230
3
155
6
155
9
170
15
170
ZR049 (4)
208/230
6
155
9
170
15
170
20
170
ZR061 (5)
208/230
6
155
9
170
15
170
20
170
24
170
ZR037 (3)
480
3
155
6
155
9
170
15
170
ZR049 (4)
480
6
155
9
170
15
170
20
170
ZR061 (5)
480
6
155
9
170
15
170
20
170
24
170
ZR037 (3)
600
9
170
15
170
ZR049 (4)
600
9
170
15
170
20
170
ZR061 (5)
600
9
170
15
170
20
170
24
170
Table 24: Electric Heat Anticipator Setpoints
SETTING, AMPS
W1
W2
0.13
0.1