If at any time the economizer output goes above the minimum position, the timer stops and resets when the economizer output
returns to minimum position.
If the demand for cooling from the space/return is satisfied, the economizer output modulates to the minimum position and the
compressor outputs are de-energized as long as their minimum run timers have expired.
Economizer loading
Power exhaust
Setpoints
a. Economizer Enable ON
b. Power Exhaust Enable ON
c. Modulating Power Exhaust OFF
d. Exhaust VFD Installed OFF
e. Building Pressure Sensor Enabled OFF
f. Econo Damper Position For Exh Fan ON Percent
g. Econo Damper Position For Exh Fan OFF Percent
Inputs
No inputs are present for non-modulating power exhaust.
Outputs
a. 2-10 VDC from ECON on Economizer Expansion module
b. 24 VAC from EX-FAN to energize exhaust fan on Economizer Expansion module
Operation
Operation details include:
a. Compares economizer output to the Economizer Damper Position For Exhaust Fan On and OFF.
b. Energizes exhaust fan when economizer output is above Economizer Damper Position For Exhaust Fan On.
c. De-energizes exhaust fan when economizer output is below the Economizer Damper Position for Exhaust Fan OFF