5.4  Parameter List

BRAIN communication parameters for SISD are as follows.

No.

Symbol

Parameter Name

Setting Range

Unit

Factory-set Value Setting Type

01

MODEL

Model Name

––––

Display

02

TAG NO

Tag Number

––––

Display

03

SELF CHK

Self Check

GOOD/ERROR

––––

Display

<Display Parameters>

A

DISPLAY1

Menu Name

A01

INPUT1

Input Display

V

Display

A09

OUTPUT1

Output1 Display

%

Display

A10

OUTPUT2

Output2 Display

%

Display

A54

STATUS

Status Display (Note1)

0000 to FFFF

––––

Display

A55

WRT PROTECT

Parameter Write Protect

ON/OFF

––––

OFF

Display

A56

REV NO.

Revision number

––––

Display

A58

MENU REV

Menu Revision number

––––

Display

A60

SELF CHK

Self Check

GOOD/ERROR

––––

Display

B

DISPLAY2

Menu Name

B01

INPUT1

Input Display

V

Display

B09

OUTPUT1

Output1 Display

%

Display

B10

OUTPUT2

Output2 Display

%

Display

B60

SELF CHK

Self Check

GOOD/ERROR

––––

Display

<Setting Parameters>

D

SET(I/O)

Menu Name

D01

TAG NO.1

Tag Number1

Up to 8-single-byte

––––

Alphanumeric

D02

TAG NO.2

Tag Number2

Up to 8-single-byte

––––

Alphanumeric

D03

COMMENT1

Comment1

Up to 8-single-byte

––––

Alphanumeric

D04

COMMENT2

Comment2

Up to 8-single-byte

––––

Alphanumeric

D17

LINEARIZE1

Linearize

OFF/SQR

––––

OFF

SQR for SISD-101

Selection

D19

LOW CUT1

Low Cut

0.3 to 100.0

%

1.0

Real Number

D33

OUT1 DR

Output1 Direction

DIRECT/REVERSE

––––

DIRECT

Selection

D34

OUT2 DR

Output2 Direction

DIRECT/REVERSE

––––

DIRECT

Selection

D60

SELF CHK

Self Check

GOOD/ERROR

––––

Display

<Adjustment Parameters>

P

ADJUST

Menu Name

P03

ZERO ADJ1

Zero Adjustment

Note2

Selection

P04

SPAN ADJ1

Span Adjustment

Note2

Selection

P13

OUT1     0%

Output1  0%

-20.00 to 20.00

%

0.00

Real Number

P14

OUT1 100%

Output1 100%

-20.00 to 20.00

%

0.00

Real Number

P15

OUT2     0%

Output2  0%

-20.00 to 20.00

%

0.00

Real Number

P16

OUT2 100%

Output2 100%

-20.00 to 20.00

%

0.00

Real Number

P60

SELF CHK

Self Check

GOOD/ERROR

––––

Display

<Test Parameters>

Q

TEST

Menu Name

Q02

OUT1 TEST

Output1 Test

-25.0 to 125.0

%

0.0

Real Number

Q03

OUT2 TEST

Output2 Test

-25.0 to 125.0

%

0.0

Real Number

Q60

SELF CHK

Self Check

GOOD/ERROR

––––

Display

Note 1: The condition of the instrument is displayed.

Note 2: V RST/V INC/V HINC/V HDEC/V DEC

Summary of Contents for YS80 Series

Page 1: ...User s Manual Y okogawa Electric Corporation IM 01B04N01 02E 10th Edition Model SISD Style S Isolator...

Page 2: ......

Page 3: ...1 Names of Components 5 2 5 2 Setting Jumper 5 3 5 2 1 Check of Setting Jumper and Its Position 5 3 5 3 Setting of Parameters 5 4 5 3 1 Configuration of Parameters 5 5 5 3 2 Description of Parameters...

Page 4: ...Blank...

Page 5: ...g of the controller Maintenance of equipment Related Documents The following documents all relate to the SISD Isolator Read them as necessary Manual Title Manual No Description Rack Mounted Instrument...

Page 6: ...nsure that the product is as specified in the order F0101 ai 100 120VAC 50 60Hz ISOLATOR SISD 100 S XXXXXXXXX 1 5VDC 100mA 7 0VA 24 110VDC 100 120VAC 50 60Hz ISOLATOR SISD 100 S XXXXXXXXX 1 5VDC 100mA...

Page 7: ...o complement the present topic and or describe terms specific to this document Gives reference locations for further information on the topic Description of Displays Some of the representations of pro...

Page 8: ...must be connected to ground prior to operating the equipment Function ground terminal This symbol indicates that the terminal must be connected to ground prior to operating the equipment AC voltage Th...

Page 9: ...mA DC signals which are isolated from the input signal and the power supply With the VJ77 Parameter Setting Tool you can do the following Read write all parameters at once Save read parameters to a f...

Page 10: ...2 2 IM 01B04N01 02E 2 1 Standard Specifications Please see the General Specifications GS 01B04N01 02E at the end of this manual...

Page 11: ...d Style Code S Style S Option Codes 1 2 NHR FBP LOCK WSW REK TB A2TB A2ER Without rack case Power supply fuse bypass Power supply plug with lock With spring washer Mount to same line with EK series ra...

Page 12: ...Blank...

Page 13: ...tallation 1 2 3 App 1 2 3 5 6 7 8 4 Installation For details of the installation procedure and wiring precautions refer to the instruction manual Installation of Rack Mounted Instruments IM 1B4F2 01E...

Page 14: ...C B A 8 7 6 5 4 3 2 1 OUT IN Terminal arrangement Figure 3 1 Terminal Layout Table 3 1 Terminal Wiring Terminal Designation Description A Output1 1 to 5 V DC B C D F Output2 4 to 20 mA DC H J K Do not...

Page 15: ...etc in micro processor to be Pulse Width Modulation PWM then is converted into 1 to 5 V DC or 4 to 20 mA DC signals in output circuit through optical isolation circuit Output Circuit Input Processing...

Page 16: ...Blank...

Page 17: ...hen inserting the internal unit into the rack case firmly connect the multi pin connectors for connecting the internal unit and the case 3 Make sure that power plugs are properly connected to the powe...

Page 18: ...Name plate Output terminal block Main board Terminal cover and handle for drawing out the internal unit Two pole plug with earthing contact Multi pin connector Input terminal block Rack case F0501 ai...

Page 19: ...he internal unit out from the rack case b Check that the jumper on the main board of the internal unit is set to obtain the desired action c Use the tweezers to change the position of jumper d Put the...

Page 20: ...munication cable of 5 pin connector type model F9182EE and the adapter for modularjack model E9786WH are required For details of operation and adjusting procedures of VJ77 Parameters Setting Tool refe...

Page 21: ...low cut point is shown in the figure below A 0 2 hysteresis is used for the low cut point Y X Output Signal Y Input Signal X Low cut point Hysteresis fixed to 0 2 0 3 D33 OUT1 DR and D34 OUT2 DR Sets...

Page 22: ...AG NO 2 Tag Number2 Up to 8 single byte Alphanumeric D03 COMMENT1 Comment1 Up to 8 single byte Alphanumeric D04 COMMENT2 Comment2 Up to 8 single byte Alphanumeric D17 LINEARIZE1 Linearize OFF SQR OFF...

Page 23: ...6 1 IM 01B04N01 02E Maintenance 1 2 3 App 1 2 3 5 6 7 8 4 Maintenance This chapter describes the calibration procedures that can be done in the instrument room or service shop Chapter 6 Maintenance...

Page 24: ...following test equipment manufactured by Yokogawa or their equivalent DC Voltage Current Standard Yokogawa GS200 or the equivalent 1 set Digital Voltmeter Yokogawa DM7560 or the equivalent 1 set PC V...

Page 25: ...dy Terminal for adjustment The procedure is shown below using the JHT200 Handy Terminal as an example Adjust SISD using JHT200 Handy Terminal a Connect the equipment as illustrated in Figure 6 1 b Set...

Page 26: ...put value and the in put display of P04 SPAN ADJ1 If the input value does not correspond to the display value select P04 SPAN ADJ1 to enter the adjustment mode Mainly select INC addi tion or DEC subtr...

Page 27: ...use S9510VK Approx 3 years If the fuse breaks or if the replacement period elapses please have the item replaced Power supply unit L3510YA Standard L3510YF Option codes TB FBP or REK L3510YT Option co...

Page 28: ...Blank...

Page 29: ...7 1 IM 01B04N01 02E Troubleshooting 1 2 3 App 1 2 3 5 6 7 8 4 Troubleshooting If any fault occurs in the instrument note the symptoms and follow Section 7 1 Chapter 7 Troubleshooting...

Page 30: ...OM error 0002 ERROR EEPROM SUM ERROR Output 0 or less Communication Undefined Parameter error 1000 ERROR AD ERROR Output 0 or less Communication Normal action A D conversion error 0008 ERROR INPUT OVE...

Page 31: ...ecify the terminal block to which the power source is directly connected option codes TB A2TB and REK the external wiring to the terminal block is necessary therefore drawing out the internal unit req...

Page 32: ...nal Block Output Terminal Cover Power Fuse Power Terminal Cover Input Terminal Cover Power Terminal Input Terminal Block Power and Ground Terminal connection Connection screw M4 Symbol L N Description...

Page 33: ...S C3307 Vinyle sheathed cables for electric appliances KIV stranded wires conforming to JIS C3316 Note Power supply cables should be determined from the instrument power consumption they must have con...

Page 34: ...Blank...

Page 35: ...AND APPEARANCE Mounting Rack mounting Wiring Signal Wiring ISO M4 size 4mm screws on terminal block Power and Ground Wiring 100 V version JIS C 8303 two pin plug with earthing contact IEC A5 15 UL458...

Page 36: ...less above sea level Warm up time 15 minutes or more after the power is turned on n TRANSPORT AND STORAGE CONDITIONS Temperature 25 to 70 C Temperature change rate 20 C per hour or less Humidity 5 to...

Page 37: ...eral tolerance value of tolerance class IT18 based on JIS B 0401 2016 2 Cable length 300 mm Power supply terminal type option TB or A2TB F02 ai 136 22 71 300 52 48 180 L N Trigonometry Unit mm General...

Page 38: ...r supply terminal type option REK F03 ai 52 71 300 32 136 48 200 190 5 L N 2 7 Trigonometry Unit mm General tolerance value of tolerance class IT18 based on JIS B 0401 2016 2 Power supply terminal blo...

Page 39: ...yle S Option Codes 1 2 NHR FBP LOCK WSW REK TB A2TB A2ER Without rack case Power supply fuse bypass Power supply plug with lock With spring washer Mount to same line with EK series rack With power sup...

Page 40: ......

Page 41: ...May 2004 Change of the company name 9th Edition Oct 2019 Change of the style number 10th Edition Jan 2021 VJ77 parameter setting tool R3 01 or later support n Written by Yokogawa Electric Corporation...

Page 42: ...4th Floor 129090 Moscow RUSSIA Phone 7 495 737 7868 Fax 7 495 737 7869 YOKOGAWA CHINA CO LTD 3F Tower D Cartelo Crocodile Building No 568 West Tianshan Road Shanghai 200335 CHINA Phone 86 21 62396262...

Reviews: