<B4. Power, ground, and signal cable connection>
B4-4
IM 01W02D02-01EN
l
Wiring to spring terminals: 1 (without sleeve)
• When using a solid conductor, strip the insulated cover and connect it.
Strip the solid conductor by 10 mm.
• When using a stranded conductor, strip the insulated cover and twist and connect it.
Strip the stranded conductor for 10 mm.
Never solder the stranded conductor when connecting cables.
Be careful not to cause the loosely stranded conductor to come in contact with adjacent
terminals or others. Insert the cable leads into the terminal block securely.
Cable
Core wire
Length of exposed wire
l
Wiring to spring terminals: 2 (with sleeve)
The sleeve can prevent cable leads from untwist when you connect the cable. Select a sleeve to
match the cable size. If the length of cable leads does not match the length of sleeve (I
2
), strip the
cable to the correct length. Strip the cable for a length so that the core wire slightly extends from
the metal tube of the sleeve. If this causes the length of the metal tube of the sleeve to be slightly
shorter than the stripping length, this is no problem.
The wiring cables and applicable sleeves are listed in the table below.
Use the same manufacturer for sleeves and tools.
Example of tool: Phoenix Contact’s CRIMPFOX 6
For details on sleeves and crimp tools, contact to Phoenix Contact Inc.
l
1
l
2
d
1
s
1
s
2
d
1
Summary of Contents for YFGW610
Page 2: ...Blank Page...