17
<Read Me First>
IM 01W02E02-11EN
n
FM Approval (Canada)
C
aution for FM Nonincendive Approval (Canada).
(1) Technical Data
Note 1. Model YFGW510 Field Wireless Access Point with optional code CN17 is applica
-
ble for use in hazardous area.
• Certificate: FM17CA0150X
• Applicable standards:
C22.2 No. 94-2:2015, C22.2 No. 213:2017, CAN/CSA-C22.2 No. 60079-0:2015,
CAN/CSA-C22.2 No. 60079-11:2014, CAN/CSA-C22.2 No. 60079-15:2016,
CAN/CSA-C22.2 No. 60529:2016, CAN/CSA-C22.2 No. 61010-1-12
• Hazardous Location Ratings:
Nonincendive for Class I, Division 2, Groups A, B, C, D;
Suitable for Class II, Division 2, Groups F,G; Class III, Division 1
Ex nA [ic] IIC T4 Gc
• Temperature Class: T4
• Ambient Temperature: –30 to 70°C (-22 to 158°F)
• Altitude: ≤ 3000 m
• Enclosure: Type 4X, IP66
• Power Supply: Rated Voltage: 24 V DC
Voltage Range*
1
: 10.0-26.4 V DC
*1:
The equipment shall not be operated outside the range.
• Power dissipation: ≤ 3.5 W
• RF Power: ≤ 60 mW
(2) Electrical Connection
The type of electrical connection depends on the marking below on YFGW520.
Marking
The type of electrical connection
Note
M
M20 (ISO)
M20 X 1.5
A or N
ANSI 1/2 NPT
1/2-14 NPT
• This marking is incused at the back side of the electrical connection block.
Marking
F05.ai