<9. Connection Device Type>
9-11
IM 01W03D02-01EN
9.1.10 Parameter Summary
Table 9.4
Parameter Summary
Object ID Attribute
ID
Label
Description
Default value Handling
*
1
1.
UAPMO
block
1
Version Revision
Indicates the application revision of FN310. This
revision changes when the application software is
downloaded.
---
R
10
Static Revision
Indicates the revision level of the fixed parameters
of UAP. Used, for example, to check whether
parameters have been changed. This attribute is
updated when information of Modbus devices is
obtained.
---
R
64
Identification
Number
Indicates the vendor ID, model ID, and revision of
the device.
---
R
65
CTS Version
Indicates the version of the communication stack
test system (CTS).
0
R
66
ITS Version
Indicates the version of the interoperability test
system (ITS).
0
R
67
Diagnostic
Status
Indicates the diagnostic results of the device based
on the NAMUR NE107 *
2
model.
Setting Enable diagnostic status configuration in
UAP Option to Enable allows turning Off and On the
display of the diagnostic results for each summary,
and changing Categorize.
---
R
68
UAP Option
Allows setting the Diagnostic Status and write
protection of UAP.
1. Software write protect
1: On, 0: Off (default)
2. Enable hardware write protect
1: Enable, 0: Disable (default)
3. Enable diagnostic status configuration
1: Enable, 0: Disable (default)
The following table shows the relationship between
the hardware write protection and software write
protection.
Enable
hardware
write
protect
Hardware
write
protect
Software
write
protect
Write
protect
Disable
Off or On
Off
No
Disable
Off or On
On
Protected
Enable
Off
Off or On
No
Enable
On
Off or On Protected
1. Off
2. Disable
3. Disable
W(P)
69
Diagnostic
Switch
Allows setting On/Off for each summary of
Diagnostic Status when Enable diagnostic status
configuration in UAP Option is set to Enable.
On
W(P)
70
Diagnostic
Configuration
Allows Categorize for each summary of Diagnostic
Status when Enable diagnostic status configuration
in UAP Option is set to Enable.
0x08: F:Failure status
0x04: C:Function check status
0x02: O:Out of specification status
0x01: M:Maintenance required status
Refer to Table
9.5.
W(P)
71
Find Device
When set a value other than 0, FN310 displays
“Squ.” on the LCD. The value means the display
duration. After displaying, this value returns to 0.
Unit: second
Range: 0 to 60
0
W