YOKOGAWA YFGW410 User Manual Download Page 58

 

 

<9.  Connection Device Type>

9-11

IM 01W03D02-01EN

9.1.10  Parameter Summary

Table 9.4 

Parameter Summary

Object ID Attribute

ID

Label

Description

Default value Handling 

*

1

1.

UAPMO

block

1

Version Revision

Indicates the application revision of FN310. This 

revision changes when the application software is 

downloaded.

---

R

10

Static Revision

Indicates the revision level of the fixed parameters 

of UAP. Used, for example, to check whether 

parameters have been changed. This attribute is 

updated when information of Modbus devices is 

obtained.

---

R

64

Identification 

Number

Indicates the vendor ID, model ID, and revision of 

the device.

---

R

65

CTS Version

Indicates the version of the communication stack 

test system (CTS).

0

R

66

ITS Version

Indicates the version of the interoperability test 

system (ITS).

0

R

67

Diagnostic 

Status

Indicates the diagnostic results of the device based 

on the NAMUR NE107 *

2

 model.

Setting Enable diagnostic status configuration in 

UAP Option to Enable allows turning Off and On the 

display of the diagnostic results for each summary, 

and changing Categorize.

---

R

68

UAP Option

Allows setting the Diagnostic Status and write 

protection of UAP.

1.  Software write protect

 

1: On, 0: Off (default)

2.  Enable hardware write protect

 

1: Enable, 0: Disable (default)

3.  Enable diagnostic status configuration

 

1: Enable, 0: Disable (default)

The following table shows the relationship between 

the hardware write protection and software write 

protection.

Enable

hardware

write

protect

Hardware

write

protect

Software

write

protect

Write 

protect

Disable

Off or On

Off

No

Disable

Off or On

On

Protected

Enable

Off

Off or On

No

Enable

On

Off or On Protected

1. Off

2. Disable

3. Disable

W(P)

69

Diagnostic 

Switch

Allows setting On/Off for each summary of 

Diagnostic Status when Enable diagnostic status 

configuration in UAP Option is set to Enable.

On

W(P)

70

Diagnostic 

Configuration

Allows Categorize for each summary of Diagnostic 

Status when Enable diagnostic status configuration 

in UAP Option is set to Enable.

0x08: F:Failure status

0x04: C:Function check status

0x02: O:Out of specification status

0x01: M:Maintenance required status

Refer to Table 

9.5.

W(P)

71

Find Device

When set a value other than 0, FN310 displays 

“Squ.” on the LCD. The value means the display 

duration. After displaying, this value returns to 0.

Unit: second

Range: 0 to 60

0

W

Summary of Contents for YFGW410

Page 1: ...User s Manual FN310 Field Wireless Multi Protocol Module RS485 Modbus Protocol IM 01W03D02 01EN IM 01W03D02 01EN 5th Edition...

Page 2: ...ECEx Certification 2 12 2 7 EMC Conformity Standards 2 14 2 8 Safety Requirement Standards 2 14 3 Component Names 3 1 4 Installation 4 1 4 1 Precautions 4 1 4 2 Mounting 4 1 4 2 1 Installation of FN11...

Page 3: ...Information 7 4 7 3 5 Setup the Integral Indicator 7 4 7 3 6 Parameters for Modbus Device 7 4 7 3 7 Assignment to AI Object 7 4 7 3 8 Write Protect 7 5 7 3 9 Switching to the Deep Sleep Mode 7 5 7 3...

Page 4: ...1 9 1 3 Preparation for Starting Operation 9 1 9 1 4 Parameters for Wireless Communication 9 1 9 1 5 SENCOM Specific Parameters 9 1 9 1 6 Assignment to AI Object 9 2 9 1 7 Function Block and Menu Tree...

Page 5: ...al including but not limited to implied warranty of merchantability and fitness for a particular purpose If any question arises or errors are found or if any information is missing from this manual pl...

Page 6: ...a soft dry cloth d Explosion Protected Type Instrument Users of explosion protected instruments should refer first to section 2 6 Installation of an Explosion Protected Instrument of this manual The...

Page 7: ...f the product in question after delivery Reason of force majeure such as fires earthquakes storms floods thunder lightening or other natural disasters or disturbances riots warfare or radioactive cont...

Page 8: ...assessment of electrical and electronic products with respect to the restriction of hazardous substances China RoHS This is an explanation for the product based on Control of Pollution caused by Elec...

Page 9: ...ions Wired tag plate optional specifications EU DECLARATION OF CONFORMITY F9090HZ if optional specification KS27 is specified 2 1 Check the Model Name and Configuration The model name and configuratio...

Page 10: ...ended to put the FN310 in Deep Sleep mode to conserve the batteries For details on how to switch to Deep Sleep mode refer to subsection 7 3 9 Switching to the Deep Sleep Mode 2 4 Selecting the Install...

Page 11: ...and the instrument is not restored to its original condition its intrinsically safe construction may be compromised and the instrument may be hazardous to operate Please contact Yokogawa before makin...

Page 12: ...s aluminum and is considered a potential risk of ignition caused by impact or friction When the equipment is mounted in Zone 0 it shall be installed in such a way that even in the event of rare incide...

Page 13: ...cation Class I Division 1 Groups C D Class II Division 1 Groups E F G Class III Division 1 or Class I Zone 0 Group IIB Temperature Class T4 Hazardous Classified Location Class I Division 1 Groups A B...

Page 14: ...the National Electrical Code NFPA 70 ANSI ISA RP12 06 01 and relevant local codes 4 For Canada Installation must be in accordance with the Canadian Electrical Code Part I C22 1 ANSI ISA RP12 06 01 an...

Page 15: ...re contains aluminum and is considered a potential risk of ignition caused by impact or friction When the equipment is mounted in Zone 0 it shall be installed in such a way that even in the event of r...

Page 16: ...cation Class I Division 1 Groups C D Class II Division 1 Groups E F G Class III Division 1 or Class I Zone 0 Group IIB Temperature Class T4 Hazardous Classified Location Class I Division 1 Groups A B...

Page 17: ...the National Electrical Code NFPA 70 ANSI ISA RP12 06 01 and relevant local codes 4 For Canada Installation must be in accordance with the Canadian Electrical Code Part I C22 1 ANSI ISA RP12 06 01 an...

Page 18: ...1 Technical Data Caution for ATEX Intrinsically safe type Note 1 Model FN310 Field Wireless Multi Protocol Module RS485 Modbus Protocol with optional code KS27 for potentially explosive atmospheres C...

Page 19: ...mounted in a potentially explosive atmosphere requiring Equipment Category 1 G it shall be installed in such a way that even in the event of rare incidents an ignition source due to impact and or fri...

Page 20: ...umber IECEx FMG 15 0042X Applicable Standards IEC60079 0 IEC60079 11 IEC60079 28 Type of Protection and Marking code Ex ia op is ia IIC Ga IIB T4 Ga Enclosure IP66 in accordance with only IEC 60529 Am...

Page 21: ...pment is mounted in a potentially explosive atmosphere requiring EPL Ga it shall be installed in such a way that even in the event of rare incidents an ignition source due to impact and or friction sp...

Page 22: ...2 7 EMC Conformity Standards EN61326 1 Class ATable 2 EN55011 Class A CAUTION This instrument is a Class A product and it is designed for use in the industrial environment Please use this instrument i...

Page 23: ...Write Protection Switch WR Write Protection Switch Position 1 F0303 ai F0304 ai Write Protection No Write enabled Yes 2 Write disabled 1 Initialization switch is not used Set to D side disabled alway...

Page 24: ...age the FN310 Do not use the FN310 as a foothold NOTE Before using FN310 install FN110 For detail on how to install FN110 refer to subsection 4 2 1 Installation of FN110 To connect FN310 to the field...

Page 25: ...bout the winding 3 To protect the butyl rubber self bonding tape from the environment such as ultraviolet rays and so on wind vinyl tape or a vinyl type self bonding tape on it 4 When the tape is nece...

Page 26: ...ch pipe U bolt FN 310 mounting bracket F0405 ai Figure 4 5 Horizontal Pipe Mounting To install FN310 on a 50A 2 inch pipe follow the procedure below 1 Assemble the FN310 mounting bracket 2 Install FN3...

Page 27: ...housed in the same conduit NOTE When wiring where the ambient temperature is high or low use the cable or wire that appropriate to that place When the maximum operating temperature is more than 60 C u...

Page 28: ...so on The FN110 must be mounted vertically Fixing of FN110 Fix the FN110 on a 50A 2 inch pipe with the mounting bracket provided as the remote antenna cable option To install FN110 with mounting brack...

Page 29: ...able CAUTION Use the dedicated remote antenna cable provided by Yokogawa as accessories for FN110 The remote antenna cable and other cables should not be bundled together Remove the battery pack befor...

Page 30: ...length so that the core wire slightly extends from the metal tube of the sleeve If this causes the length of the metal tube of the sleeve to be slightly shorter than the stripping length this is no pr...

Page 31: ...with other devices Ground Wiring Connect the grounding cable to ground terminal on the top of the housing Grounding terminal F0509 ai Figure 5 9 Grounding Terminal CAUTION Grounding is required for s...

Page 32: ...he Modbus device and the FN310 operate properly Check parameter values or change the setpoints as necessary The integral indicator can be used to confirm that this product is operating properly For de...

Page 33: ...r for the provisioning device the distance between the front panel of this product and the infrared surface of the near infrared adapter should be within 30 cm For details on the Yokogawa recommended...

Page 34: ...work and the device goes into the join state when the field wireless gateway is found If the field wireless gateway is not found and a specified time based on the silence mode has elapsed a cycle of 1...

Page 35: ...e 6 4 Display Contents of the Integral Indicator Write Protect Status When the write protection is enabled the lock icon is displayed in the upper left corner of the integral indicator For details on...

Page 36: ...nstalled in the device configuration tool Refer to the following website for the latest information on CF DD and DeviceDTM http www field wireless com CF Capabilities File DD Device Description A CF f...

Page 37: ...by following the on line instructions you can configure the parameters easily 7 3 Setting Parameters 7 3 1 Parameter Usage and Selection Before setting a parameter please see the following table for a...

Page 38: ...NDPOINT Network address of remote endpoint Transport layer port at remote endpoint Object ID at remote endpoint Stale data limit Data publication period Ideal publication phase Publish Auto Retransmit...

Page 39: ...t process value returns to the configured mode Refer to subsection 8 6 Switching LCD Display for details NOTE When the FN310 detects AL 01 AL 02 and AL 03 error the LCD display does not dim regardless...

Page 40: ...iving infrared communication Use the wireless field device configuration tool for infrared or device provisioning tool Magnet Switch Operation Start by touching a magnet to magnet switch 1 for 10 seco...

Page 41: ...stic Switch parameter Follow the example below to change Out of Service to invalid 1 UAPMO block UAP Option Enable diagnostic status configuration select enable 2 UAPMO block Diagnostic Switch turns O...

Page 42: ...r element F Bit25 Installation calibration problem C Bit24 Out of service C Bit23 Outside sensor limits O Bit22 Environmental conditions out of device specification O Bit21 Fault prediction Maintenanc...

Page 43: ...ry Pack WARNING To ensure the installation minimizes the risk from electrostatic discharge To prevent electrostatic discharge caused by static charge built up on the operator ground the operator throu...

Page 44: ...s to a torque of 0 7 N m F0803 ai Figure 8 2 Remounting the Battery Pack 8 4 Replacing the Batteries The batteries in the battery pack can be replaced Batteries are not installed when shipped from the...

Page 45: ...please purchase F9090GD F9090GD is a set of F9090GC and instruction manual Batteries Part number F9915NR Alternatively following batteries may be purchased and used Tadiran TL 5930 S or SL 2780 S VITZ...

Page 46: ...the FN110 and install a new FN110 4 Remounting the battery pack 5 Restore the backed up configuration of the FN310 6 Performing provisioning work 7 Update the configuration of field wireless gateway...

Page 47: ...Connection Type 8 10 2 Example of Troubleshooting Flow The following shows an example of the flow for troubleshooting Refer to this example and Table 8 3 Locate the problem and take the corresponding...

Page 48: ...yellow 84 green 86 white 87 brown Figure 9 1 Connection of SENCOM 9 1 3 Preparation for Starting Operation Setting the FN310 Confirm the following settings of the FN310 SENCOM Interface block Transmi...

Page 49: ...depends on the setting of the Sensor Type parameter of TRANSDUCER block Table 9 1 shows the relation between Sensor Type and assignment to AI Object Table 9 1 Assignment to AI Object AI Object TRANSD...

Page 50: ...y Left Power Supply Status Power Supply Voltage Power Status Connected Device Maintenance Required Alert Other Faults Alert Faults Non Compliance Alert Faults Process Influence Alert Simulation Active...

Page 51: ...ctual Mode Permitted Mode Normal Block Mode Process Value Simulation Dynamic Variables Block Mode Concentrator OID Scale PV Energy Left Enable Configuration Process Value Status Process Value Value Pr...

Page 52: ...fo Model Serial Number Wireless Status Display Selection LCD Intermittent Time LCD Exp Mode Measurement Rate Configuration Calibration Diagnostic Status Diagnostic Status Detail 1 Diagnostic Status De...

Page 53: ...put 2 Impedance Setting Input 1 Impedance Input 2 Impedance Stable Time Configuration Status pH Value Temperature Value ORP Value rH Value Process Value Tag Description Block Info Simulate Switch Simu...

Page 54: ...4 OUT OF SERVICE AI4 O S Mode Environmental conditions out of device specification 73 O ADAPTER TEMP HI FN310 temperature is above 85 C ADAPTER TEMP LO FN310 temperature is below 40 C ANTENNATEMP HI F...

Page 55: ...0 None Output value Hold previous value Output status BAD Sensor Failure Check the installation environment of Modbus devise and connecting method of Modbus devices and FN310 AL 20 M 20 Power is criti...

Page 56: ...of service AI1 OUT OF SERVICE AI1 block is O S mode Recover when the mode target of alert block is other than O S Output value Hold previous value Output status BAD Configuration Err Check the AI1 bl...

Page 57: ...the calibration of SENCOM using SPS24 SENCOM PC software AL 81 DEVICE IMPEDANCE1 TOO LOW Input1 impedance value of SENCOM is low AL 82 DEVICE IMPEDANCE2 TOO HIGH Input2 impedance value of SENCOM is h...

Page 58: ...egorize R 68 UAP Option Allows setting the Diagnostic Status and write protection of UAP 1 Software write protect 1 On 0 Off default 2 Enable hardware write protect 1 Enable 0 Disable default 3 Enable...

Page 59: ...t Indicates the status of the hardware write protection switch 0 Off 1 On R 111 Antenna Temperature Indicates the temperature of the FN110 R 112 Adapter Temperature Indicates the temperature of the FN...

Page 60: ...r Low Alert The On Off or priority for Power Low Alert can be set 1 On Off setting 0 On 255 Off default 2 Alert report priority 0 to 15 default 15 1 Off 2 15 W P 141 Power Critical Low Alert The On Of...

Page 61: ...maximum data size of APDU R 14 LAST_BLOCK_ DOWNLOADED Indicates the last downloaded block number 0 means that no block has been downloaded R 16 ERROR_CODE Indicates the error codes for DL Error 0 no...

Page 62: ...ndicator 0 radix notation default 1 exponential notation radix notation W P 7 Wireless Status Indicates the wireless communication status Bits Contents Value Bit7 3 reserved Bit2 Contract status Clien...

Page 63: ...lert Mask Set the impedance error to detect when the Transmitter Status has changed When enabled and detecting the state of the target FN310 sends an Alert It is disabled by setting the Bit each of th...

Page 64: ...tatus mode of the object 1 Auto 2 Auto 3 Auto 4 Auto W P 3 Concentrator OID Indicates the Concentrator object value that corresponds to the data update of the Process Value R 4 Scale Allows specifying...

Page 65: ...g battery voltage Bit20 M 7 ADAPTER TEMP HI FN310 temperature is above 85 C Bit22 O 6 ADAPTER TEMP LO FN310 temperature is below 40 C Bit22 O 5 ANTENNATEMP HI FN110 temperature is above 85 C Bit22 O 4...

Page 66: ...ment No YFGW410 Field Wireless Management Station GS 01W02D01 01EN YFGW610 Field Wireless Media Converter GS 01W02D02 01EN YFGW510 Field Wireless Access Point GS 01W02E01 01EN YFGW520 Field Wireless A...

Page 67: ...dian Safety Standards 4th Apr 2017 Add section 1 3 and 1 5 Update CE Conformity RoHS 5th July 2021 1 4 2 4 2 7 2 10 2 12 2 14 10 1 Delete ATEX documentation 1 4 Add the description for EU RoHS and Chi...

Reviews: