■ Warnings
The device is operating normally and normal measurement is being executed, however, a warning has
occurred.
NE107
Error messages
Analog
output
Pulse
output
Frequency
output
Status
output
Vortex
frequency
Built-in
temperature
Analog
input
Instantaneous
flow rate
Fluid
temperature
Fluid
pressure
Fluid
density
Fluid
density
ratio
Specific
enthalpy
Flow rate
total
Indicator
HART
M
AL-070
070:Sensor
communication
error
Operation
Operation
Operation
Operation
Operation
Operation
Interlocked
to input
Interlocked
to input
Interlocked
to input
Interlocked
to input
Operation
M
AL-071
071:Flow sensor
error
Operation
Operation
Operation
Operation
Operation
Operation
Interlocked
to input
Interlocked
to input
Interlocked
to input
Interlocked
to input
Operation
M
AL-072
072:Clogging
Operation
Operation
Operation
Operation
Operation
Operation
Interlocked
to input
Interlocked
to input
Interlocked
to input
Interlocked
to input
Operation
M
AL-073
073:Degradation
Operation
Operation
Operation
Operation
Operation
Operation
Interlocked
to input
Interlocked
to input
Interlocked
to input
Interlocked
to input
Operation
S
AL-074
074:Board
temperature out
of range
Operation
Operation
Operation
Operation
Operation
Operation
Interlocked
to input
Interlocked
to input
Interlocked
to input
Interlocked
to input
Operation
C
AL-080
080:Simulation
running
Operation
Operation
Operation
Operation
Operation
Operation
Interlocked
to input
Interlocked
to input
Interlocked
to input
Interlocked
to input
Operation
C
AL-081
081:Verification
running
Operation
Operation
Operation
Hold
Hold
Hold
Interlocked
to input
Interlocked
to input
Interlocked
to input
Interlocked
to input
Operation
-
AL-082
082:Incorrect
PIN
Operation
Operation
Operation
Operation
Operation
Operation
Interlocked
to input
Interlocked
to input
Interlocked
to input
Interlocked
to input
Operation
Operation: Operation state in which output is being correctly output
Interlocked to input: Operation state in which the same processing as when there is no alarm is performed
Example 1) The volumetric flow rate also is held if the vortex frequency to be input is held when the volumetric
flow rate is in use.
Example 2) When a Temperature sensor failure occurs
When the vortex flowmeter is used for the volumetric flow rate, the vortex frequency to be input becomes
normal action and the volumetric flow rate also becomes normal action.
When the vortex flowmeter is used for the mass flow rate, temperature and pressure are to be input in addition
to the vortex frequency. Accordingly, the combination becomes vortex frequency (normal), temperature (error)
and pressure (normal). Output becomes the mass flow rate calculated according to the temperature error as a
result of specifying handling of the temperature error by setting in Temp sensor alarm action.
<6. Parameters>
38