background image

 

 

<2.  Configuration>

2-2

IM 11B06F01-01E

The following software is required as an engineering tool.

CD-ROM Code

Item

Remarks

NT203AJ-PC11E

Resource configurator

It is supplied by CD ROM.

Loading a license for installation

Modification of IP address

4th Edition : Nov. 22, 2011-00

Summary of Contents for Vigilantplant NFAI135

Page 1: ...User s Manual ASIU Analyzer Server Interface Unit Software IM 11B06F01 01E IM 11B06F01 01E 4th Edition ...

Page 2: ...or how to operate GC8000 or GC1000 MarkII refer to their corresponding user s manuals l Applicatable Readers The description of the installation method assumes that the reader has a basic knowledge of hardware and software that is necessary for installing the ASIU and Windows as well For further details of Windows refer to the respective manuals l Contents of the Package The contents of the packag...

Page 3: ...y questions or you find mistakes or omissions in the user s manuals please contact our sales representative or your local distributor n Warning and Disclaimer The product is provided on an as is basis YOKOGAWA shall have neither liability nor respon sibility to any person or entity with respect to any direct or indirect loss or damage arising from using the product or any defect of the product tha...

Page 4: ...dicated in this manual as shown in the following example Inscription example Shift F1 Meaning Indicates that the operator must press the F1 key while pressing the Shift key n Menu Inscriptions Menu operations are indicated in this manual as shown in the following example Inscription example Click on Connect in the System menu Meaning Click on the System menu then click on the Connect command n Dra...

Page 5: ...on line manual may be transferred sold distributed including delivery via a com mercial PC network or the like or registered or recorded on video tapes n Trademark Acknowledgments Microsoft Windows and Windows NT are either registered trademarks or trademarks of Microsoft Corporation in the United States and or other countries Ethernet is a registered trademark of XEROX Corporation Modbus is a reg...

Page 6: ...guration 2 1 3 Functions 3 1 3 1 I O card 3 1 3 2 Alarm information 3 2 3 3 Modbus interface table 3 2 4 Engineering 4 1 4 1 Installation 4 1 4 1 1 Preparation 4 1 4 1 2 Initial setting 4 1 4 2 Modification work 4 3 4 3 Supplement 4 4 4 3 1 Modification of IP addressing setting 4 4 4 3 2 Modification of serial port setting 4 8 5 OPC DA 2 0 Interface 5 1 5 1 System Configuration 5 1 5 2 Software Re...

Page 7: ...g is realized with address table and programming is not necessary FCN is described as ASIU is in this document F0101 ai Ethernet Redundancy is available Modbus TCP Serial Modbus RTU AI DO DI CPU Power Empty slot Space Figure 1 1 System Configuration Network Ethernet Redundancy is available Port 1 is used on the single communication Serial RS 232C Power card Single CPU card Single DI card 1 pc Read...

Page 8: ...le 32 points 24 V DC NFDR541 Relay output module 16 points 24 to 110 V DC 100 to 240 V AC NFAI135 Analog input module 4 to 20 mA 8 points channel isolation NFAI143 Analog input module 4 to 20 mA 16 points system isolation NFDCV01 Dummy cover Cover for empty I O module NFDCV02 Dummy cover Cover for empty power module 2 2 Software configuration ASIU Model Suffix Code Option Code Description ASIU Sof...

Page 9: ...1E The following software is required as an engineering tool CD ROM Code Item Remarks NT203AJ PC11E Resource configurator It is supplied by CD ROM Loading a license for installation Modification of IP address 4th Edition Nov 22 2011 00 ...

Page 10: ...a read and write even IOP check l DI card Max 16 points of the digital inputs are read periodically l DO card Max 16 points of the digital output are written and read back the output status periodically l AI card Max 16 points of the analog data is read periodically Data type Real number Range 0 0 to 1 0 Accuracy It follows the specification of each module used Refer to the GS of the relevant ana ...

Page 11: ...125 words Read input registers 4 0x04 WORD 125 words Write coil 5 0x05 BIT 1 bit Write single register 6 0x06 WORD 1 word Loopback test 8 0x08 WORD 1 word Write multiple coils 15 0x0F BIT 800 bits Write multiple registers 16 0x10 WORD 100 words Read device ID 43 0x2B ASCII string Device ID consists of vendor product code and revision number Vendor YOKOGAWA Product ASIU REVISION 1 01 01 example l M...

Page 12: ...1 to AI16 A 1 is displayed when it is IOP status Input register 30001 to 39999 Data Address Description AI read Real data 30401 to 30432 The average value during 1 second with 10 scans times However when it is IOP status IOP value which is 0 or 1 is displayed When real number format is selected the data is displayed with 2 words address The data range is 0 0 to 1 0 AI read 9999 30501 to 30516 The ...

Page 13: ...stallation of the engineering tool Install the resource configurator software from CD ROM NT203AJ PC11E to PC Resource configurator software is an engineering tool for STARDOM FCN FCJ l Installation of the ASIU software Set the ASIU application software CD on PC Uncompress the following compressed file on PC CD Drive ASIU INSTALL_ASIU ZIP Confirm the following folder is created Uncompressed folder...

Page 14: ... IP address 2 Downloading the license file Download the license file that is loaded from the STARDOM web site to ASIU with the re source configurator Refer to on line help of resource configurator 3 Setting the network Specify the Ethernet connection for ASIU if it is single or duplex Ethernet of ASIU has dual or single type and dual type has duplex and separated mode After completing the above 3 ...

Page 15: ...SIU_AI_01 ASIU_AI_02 ASIU_AI_16 0 0 1 0 0 0 1 0 0 0 1 0 Correspond to AI01 in Modbus table Correspond to AI02 in Modbus table Correspond to AI16 in Modbus table Degital input ASIU_DI_01 ASIU_DI_02 ASIU_DI_16 _____ Correspond to DI01 in Modbus table Correspond to DI02 in Modbus table Correspond to DI16 in Modbus table Degital output ASIU_DO_01 ASIU_DO_02 ASIU_DO_16 _____ Correspond to DO01 in Modbu...

Page 16: ...is use of web browser on PC the other is use of switches on CPU module Select one depending on the location of FCN During the IP address setting mode LEDs on CPU module of FCN are indicated as follows HRDY Flashing quickly RDY Flashing slowly CTRL Not lit To release this mode press the RESET button or turn off the power l Method of use the switch on CPU module of FCN 1 Turn on FCN or press RESET b...

Page 17: ... 4 Engineering 4 5 IM 11B06F01 01E 2 Click the Maintenance Menu 3 Click the Reboot 4th Edition Nov 22 2011 00 ...

Page 18: ... 4 Engineering 4 6 IM 11B06F01 01E 4 Select the Reboot IPAddress Setting Mode and press OK FCN restarts on IP address setting mode 4th Edition Nov 22 2011 00 ...

Page 19: ...or software on PC and wait for a message A new controller is con nected When the message appears select the Setting IPAddress on File menu IP address Subnet mask Gateway and Time zone parameters are set on this dialogue window Reboot the FCN after the setting 4th Edition Nov 22 2011 00 ...

Page 20: ...d all initial setting data are as follows Baudrate 9600 DataBitLength 8 StopBitLength 1 Parity NONE After FCN mode is changed to maintenance mode the communication port is set with the main tenance window on web browser Refer to the guide of STARDOM FCN FCJ IM 34P02Q01 01E about the method of modifica tion Setting parameters are COM1 Port Setting File or COM2 Port Setting File 4th Edition Nov 22 2...

Page 21: ...he STARDOM software listed below is required for a PC on which an OPC server is to be installed Model Item Remark NT781AJ FCN FCJ OPC Server for Windows NT783AJ Redundant Network Function License for FCN FCJ OPC Server Required only for redundant network 5 3 Installation and Settings For installation and settings of the OPC server and the duplexed package refer to their respec tive user s manuals ...

Page 22: ... n VT_BOOL Modbus Address 04001 to 05000 n 1 to 1000 Node GV COIL5 n VT_BOOL Modbus Address 05001 to 06000 n 1 to 1000 Node GV COIL6 n VT_BOOL Modbus Address 06001 to 07000 n 1 to 1000 Node GV COIL7 n VT_BOOL Modbus Address 07001 to 08000 n 1 to 1000 Node GV COIL8 n VT_BOOL Modbus Address 08001 to 09000 n 1 to 1000 l DSCI 10001 to 19000 Read only Writing through the OPC interface does not cause an...

Page 23: ...he DSCI mapped address since the DCS may read wrong values until ASGW ASIU reads the next data from devices Unmapped address data is always read as 0 OPC Data Name OPC Data Type Function Remark Node GV HREG0 n VT_UI2 Modbus Address 40001 to 41000 n 1 to 1000 Node GV HREG1 n VT_UI2 Modbus Address 41001 to 42000 n 1 to 1000 Node GV HREG2 n VT_UI2 Modbus Address 42001 to 43000 n 1 to 1000 Node GV HRE...

Page 24: ...r Sever Interface Unit Software Manual No IM 11B06F01 01E Oct 2006 1st Edition Newly published Jan 2010 2nd Edition P 3 3 Addition of Input register Jun 2011 3rd Edition Addition of chapter 5 Nov 2011 4th Edition Revised for GC8000 4th Edition Nov 22 2011 00 ...

Reviews: