IM 01C22T02-01E
A-4
APPENDIX 1. LIST OF PARAMETERS FOR EACH BLOCK OF THE EJA
19
4019
4119
–
FIELD_VAL
TA0102-2.EPS
–
20
4020
4120
–
UPDATE_EVT
–
Raw value of the field device in percent of thePV
range, with a status reflecting the Transducer
condition, before signal characterization (L_TYPE)
or filtering (PV_FTIME).
21
4021
4121
–
BLOCK_ALM
The block alarm is used for all configuration,
hardware, connection failure or system problems in
the block. The cause of the alert is entered in the
subcode field. The first alert to become active will
set the Active status in the Status attribute. As soon
as the Unreported status is cleared by the alert
reporting task, another block alert may be reported
without clearing the Active status, if the subcode
has changed.
–
22
4022
4122
Enable
ALARM_SUM
The current alert status, unacknowledged states,
unreported states, and disabled states of the alarms
associated with the function block.
–
23
4023
4123
0xFFFF
ACK_OPTION
Selection of whether alarms associated with the
block will be automatically acknowledged.
AUTO
24
4024
4124
0.5%
ALARM_HYS
Amount the PV must return within the alarm limits
before the alarm condition clears. Alarm Hysteresis
is expressed as a percent of the PV span.
AUTO
AUTO
25
4025
4125
0
HI_HI_PRI
Priority of the high high alarm.
AUTO
26
4026
4126
+INF
HI_HI_LIM
The setting for high high alarm in engineering units.
AUTO
27
4027
4127
0
HI_PRI
Priority of the high alarm.
AUTO
28
4028
4128
+INF
HI_LIM
The setting for high alarm in engineering units.
AUTO
29
4029
4129
0
LO_PRI
Priority of the low alarm.
AUTO
30
4030
4130
–INF
LO_LIM
The setting for the low alarm in engineering units.
AUTO
31
4031
4131
0
LO_LO_PRI
Priority of the low low alarm.
AUTO
32
4032
4132
–INF
LO_LO_LIM
The setting of the low low alarm in engineering units.
–
33
4033
4133
–
HI_HI_ALM
The status for high high alarm and its associated time stamp.
–
34
4034
4134
–
HI_ALM
The status for high alarm and its associated time stamp.
–
35
4035
4135
–
LO_ALM
The status of the low alarm and its associated time stamp.
–
36
4036
4136
–
LO_LO_ALM
The status of the low low alarm and its associated
time stamp.
This alert is generated by any change to the static data.
17
4017
4117
Linear: 0%
Square root: 10%
LOW_CUT
Limit used in square root processing. A value of
zero percent of scale is used in block processing if
the transducer value falls below this limit, in % of
scale. This feature may be used to eliminate noise
near zero for a flow sensor.
AUTO
18
4018
4118
2sec
PV_FTIME
Time constant of a single exponential filter for the
PV, in seconds.
AUTO
Relative
Index
Index
AI1
Explanation
Write Mode
Factory Default
Parameter Name
Index
AI2
14
4014
4114
0
STATUS_OPTS
Options which the user may select in the block
processing of status
O/S
15
4015
4115
AI1: 1
AI2: 2
CHANNEL
The number of the logical hardware channel that is
connected to this I/O block. This information
defines the transducer to be used going to or from
the physical world.
O/S
16
4016
4116
Specified at the
time of order
L_TYPE
Determines if the values passed by the transducer
block to the AI block may be used directly (Direct)
or if the value is in different units and must be
converted linearly (Indirect), or with square root (Ind
Sqr Root), using the input range defined by the
transducer and the associated output range.
MAN