IM 04P02B01-01E
6-10
6.10 Setting the Alarm Delay Duration
This section explains the details of setting the duration of the delay alarm.
Procedure
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Press the
key or
SHIFT
+
key to select
Aux
and then press the
key.
3.
Press the
key or
SHIFT
+
key to select
Alarm delay
and then press
the
key.
4.
Set each item and press the
key.
Use the
key or
SHIFT
+
key to select values.
For the procedure on how to enter values or characters, see section 4.2.
If you press the
ESC
key in the middle of the operation, the settings entered up
to then are cancelled, and the display returns to a higher level menu.
5.
When the
Setting complete
screen appears, do either of the following:
Press the
key to set other channels.
If you are done, press the
ESC
key.
6.
Hold down the
MENU
key for 3 seconds to return to Operation mode.
Set the channel range.
Set the alarm delay time.
The new setting takes effect.
ESC/?
First channel
Last channel
Set=Aux
Aux=Alarm delay time
CH=01-01
Duration= 10
01-01 Channel
Setting complete
Explanation
Duration
The duration can be set to a value in the range of 1 to 3600 s.
However, the alarm delay time is an integer multiple of the scan interval. For example, if
the scan interval on the dot model is 2.5 s, the actual duration is an integer multiple of
2.5 s. If the set value is not equal to an integer multiple of 2.5 s, the duration is the
smallest integer multiple of 2.5 s greater than the set value.
Example: The actual duration for 1 s and 2 s is 2.5 s.
<Related Topics>
Enabling the alarm delay function: Section 7.15