17.4.5 Valve Position Output and Feedback Input Wiring
CAUTION
1) Use an auxiliary relay for load-switching if the contact rating is exceeded.
2) Keep the relay output wires and the feedback input wires at least 30 cm apart.
3) The output relay has a limited service life. Be sure to connect a CR filter (for AC)
or diode (for DC) to the load.
4) If there is a risk of external lightning surges, use a lightning arrester etc.
5) This should always be used with a load of 10 mA or more.
► When using auxiliary relay: 17.4.4 Control Output (Relay, Current, and Voltage Pulse) Wiring
Relay contact output
507
508
509
VALV
HIGH
(direct)
LOW
(reverse)
COM
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
Note: This should always be used with a load of 10 mA or more.
Feedback input (resistor)
100%
0%
510
511
512
VALV
Shield
Resistance:
100
Ω
to 2.5 k
Ω
Grounding
Feedback input (current)
510
512
VALV
4 to 20 mA DC
–
+
Shield
Grounding
*: Always set the terminal 511 in open state.
17.4 Wiring
Summary of Contents for UTAdvanced UP55A
Page 3: ......
Page 21: ...Blank Page ...
Page 37: ...Blank Page ...
Page 47: ...Blank Page ...
Page 125: ...Blank Page ...
Page 147: ...Blank Page ...
Page 155: ...8 8 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 159: ...8 12 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 167: ...8 20 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 175: ...8 28 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 221: ...Blank Page ...
Page 275: ...Blank Page ...
Page 351: ...Blank Page ...
Page 381: ...Blank Page ...
Page 403: ...Blank Page ...
Page 491: ...Blank Page ...
Page 505: ......
Page 513: ...Blank Page ...
Page 515: ...Blank Page ...