YOKOGAWA UT351 User Manual Download Page 6

IM 05D01D02-03E (2)

2. Lists of Parameters

Operating Parameters

Parameter 

Symbol

Name of Parameter

Setting Range and Description

Initial Value

User Setting

Target Item 

in CD-ROM

Alarm 1-setpoint

Alarm 2-setpoint

Alarm 3-setpoint

PV alarm / SP alarm: -100.0 to 100.0% of PV 
input range 
Deviation alarm: -100.0 to 100.0% of PV input 
range span
Output alarm: -5.0 to 105.0% 
An alarm common to the 1.SP to 4.SP parameters. 

PV high limit/SP high limit alarm: 
100.0% of PV input range 
Deviation alarm:  0.0% of PV 
input range span 
Other PV/SP low limit alarm: 
0.0% of PV input range 
Output high limit alarm: 100.0% 
Output low limit alarm: 0.0% 

Auto-tuning

OFF: No auto-tuning 
1: Auto-tuning for 1.SP  2: Auto-tuning for 2.SP 
3: Auto-tuning for 3.SP  4: Auto-tuning for 4.SP 
AUTO: Performs auto-tuning to all groups 1 to 4. 

OFF

Target setpoint 
number selection

0: Uses target setpoint via communication
1: Selects target setpoint 1 (1.SP).
2: Selects target setpoint 2 (2.SP).
3: Selects target setpoint 3 (3.SP).
4: Selects target setpoint 4 (4.SP).

1

PID parameter display 
number

MENU: Move to FL parameter display
1Gr to 4Gr: Display of each PID 
parameter

MENU

PV input filter

OFF, 1 to 120 second.
Used when the PV input fluctuates.

OFF

PV input bias

-100.0% to 100.0% of PV input 
range span 
Used to correct the PV input range.

0.0% of PV input range 
span

Setpoint ramp-up-rate

Setpoint ramp-down-
rate

OFF 
0.0% + 1 digit of PV input range span 
to 100.0% of PV input range span 
Set ramp-up-rate or ramp-down-rate 
per hour or minute. 
Sets unit in ramp-rate-time unit (TMU). 

OFF

OFF

1.0% of PV input range 
span

ON/OFF rate detection 
band

ON/OFF rate high limit

ON/OFF rate low limit

0.0 to 100.0% of PV input range span 

ORL + 1 digit to 105.0%

100.0%

-5.0% to ORH - 1 digit

0.0%

Target setpoint-1

Target setpoint-2

Target setpoint-3

Target setpoint-4 

0.0 to 100.0% of PV input range
However, between target setpoint limiter 
lower limit (SPL) and upper limit (SPH). 

0.0% of PV input range

LL communication 
interface selection

(A1)

(A2)

(A3)

(AT)

(SP.NO)

(PID)

(FL)

(BS)

(UPR)

(DNR)

(ORB)

(ORH)

(ORL)

(1.SP)

(2.SP)

(3.SP)

(4.SP)

OFF: Communication is carried out via the 
RS485 communication terminals. 
ON: Communication is carried out via the light-loader 
adapter.

with communication : OFF
without communication : ON

Ref.2.1(5)

Ref.2.1(6)

Ref.4.1(1)

Ref.1.1(1)

Ref.2.1(1)

Ref.3.3(5)

Ref.3.3(4)

Ref.4.1(1)

Heater burnout current 
measurement 2

(HC2)

The current value of the 
heater burnout detector 
is shown on the display of 
the HC1 or HC2 parameter.

Heater burnout current 
measurement 1

These are not setpoints.

(HC1)

Heater burnout current 
setpoint 2

(HB2)

OFF

When PCMD = 6 or 7 :
PCCH = 100.0%, 
PCCL = 0.0 %
When PCMD = 8 or 9 :
PCCH and PCCL = 1.0 %

Heater burnout current 
setpoint 1

Low limit for
PV color change

High limit for
PV color change

OFF, or 1 to 50 A

When PCMD (PV color mode parameter) = 6 or 7 :
-100.0 to 100.0 % of PV input range
When PCMD (PV color mode parameter) = 8 or 9 :
-100.0 to 100.0 % of PV input range span

(HB1)

ON/OFF rate

This is not a setpoint.

The moving average (for 5 
cycle times) of the control 
output is shown.

(OR)

Output high limit
Heating-side output high limit 
(in heating/cooling control)

Output low limit 
Cooling-side output high limit 
(in heating/cooling control)

-5.0 to 105.0% 
Heating-side limiter in heating/cooling 
control: 0.0 to 105.0% (OL < OH) 

-5.0 to 105.0%
Cooling-side limiter in heating/cooling control: 0.0 to 
105.0% (OL < OH) 

100% 
Heating/cooling control: 
100.0% 

0.0% 
Heating/cooling control: 
100.0% 

ON/OFF control hysteresis 
Heating-side/cooling-side
ON/OFF control hysteresis
(in heating/cooling control) 

In ON/OFF control: 0.0 to 100.0% of PV input 
range span 
In heating/cooling control: 0.0 to 10.0% 

ON/OFF control: 0.5% of PV 
input range span 
Heating/cooling control: 0.5% 

(OH)

(OL)

(H)

Direct/reverse action 
switching

0: reverse action, 1: direct action

0

(DR)

(PCCH)

(PCCL)

(LL)

“Super” function

(SC)

Deviation

(PV-SP)

+

-

Direct 

action

Reverse 

action

Control output

0%

100%

Ref.4.1(4)

Ref.2.1(3)

OFF

OFF: Disable
1: Overshoot suppressing function

Suppresses overshoots generated by abrupt changes 
in the target setpoint or by disturbances. 

2: Hunting suppressing function (Stable mode)

Suitable to stabilize the state of control when the load 
varies greatly, or the target setpoint is changed.
Enables to answer the wider characteristic changes 
compared with Response mode.

3: Hunting suppressing function (Response mode)

Enables quick follow-up and short converging time of 
PV for the changed target setpoint.

Note: Use “SUPER” function (SC) 2 or 3 in PID control or PI control.

“SUPER” function 2 or 3 is not available in the following control:

 1) ON/OFF control
 2) P control (control for proportional band only)
 3) PD control (control for proportional band and derivative item only)
 4) Heating/cooling control
Do not use hunting suppressing function when control processes 
with response such as flow or pressure control. 

PID-related Parameters

The following parameters are displayed when “1Gr” is set to PID parameter display number (PID). In this case, the corresponding target setpoint is 1.SP
(target setpoint-1).
To set PID corresponding to target setpoint 2 to 4, set “2Gr”, “3Gr”, or “4Gr” to PID. The relevant parameters will then be displayed.

Parameter 

Symbol

Name of Parameter

Setting Range and Description

Initial Value

Proportional band/Heating-
side proportional band 
(in heating/cooling control) 

0.1 to 999.9% 
In heating/cooling control: 0.0 to 999.9% 
(heating-side ON/OFF control applies when 0.0) 

5.0%

Integral time 
Heating-side integral time 
(in heating/cooling control) 

OFF, 1 to 6000 second 

OFF, 1 to 6000 second

240 second 

60 second

Derivative time 
Heating-side derivative time 
(in heating/cooling control) 

Manual reset

-5.0 to 105.0% 
(enabled when integral time “1.I” is OFF) 
The manual reset value equals the output value 
when PV = SP is true.  
For example, if the manual reset value is 50%, 
the output value is 50% when PV = SP 
becomes true.

50.0%

User Setting

Target Item 

in CD-ROM

(1.P)

(1.I)

(1.D)

(1.MR)

Cooling-side integral 
time

OFF, 1 to 6000 second

240 second

(1.Ic)

Cooling-side 
proportional band

0.0 to 999.9% 
(Cooling-side ON/OFF control applies 
when 0.0) 

5.0%

(1.Pc)

Ref.4.1(1)

Parameters relating to PV or setpoints should all be set in real numbers. 

For example, use temperature values to define target setpoints and 
alarm setpoints for temperature input. 

*

The “User Setting” column in the table below is provided for the customer to record setpoints. 

*

The “Target Item in CD-ROM” column in the table below provides references from User’s Manual (Reference) (CD-ROM 
Version) which describes items in more detail and items that are not contained in this manual. 

60 second

Ref.4.1(1)

OFF, 1 to 6000 second

Cooling-side derivative 
time

Deadband

-100.0 to 50.0% 
In heating/cooling control, a reagion where 
both of the heating- and cooling-side outputs 
are presented, or none of them is presented, 
can be set.

3.0%

(1.Dc)

(1.DB)

Zone PID reference 
point-1 

100% value of 
PV input range 

(1.RP)

0.0 to 100.0% of PV input range. 
Note that 1.RP 

 2.RP.

Refer to the table below for recording setpoints when two sets or more of PID parameters are used.

Parameter

n=2

n=3

n=4

n.P

n.I

n.D

n.MR

n.Pc

n.Ic

n.Dc

n.DB

None

None

n.RP

Reference deviation 

OFF, 0.0 to100.0% of PV input range span
Used to select PID constants according to a deviation from 
the setpoint. The 4th group of PID constants is used when 
the controller fails to keep track of the deviation.

OFF

Ref.4.1(1)

(RDV)

Auto-tuning

Auto-tuning is a function with which the controller
automatically measures the process characteristics
to automatically set the optimum PID constants. This
function does not work when the controller is per-
forming on-off control. The UT351/UT321 employ
the “Limit Cycle Method.” As shown in the figure
on the right, the controller temporarily changes its
control output in a step-waveform manner. Then, it
calculates the optimum proportional band (P), inte-
gral time (I) and derivative time (D) from the result-
ing response to set them in their respective param-
eters. If the Output High Limit (OH) and Output Low Limit (OL) parameters are already configured, the control output turns on and off only
between the output’s high and low limits during auto-tuning.

Auto-tuning Using Zone PID (see “

 PID Switching (Zone PID)” later in this manual)

Setting of 

AT Parameter

Auto-tuned Setpoint

OFF

-

Auto-tuning is turned off (disabled).

1

Determines the values of 1.P, 1.I and 1.D parameters by auto-tuning.

2

Determines the values of 2.P, 2.I and 2.D parameters by auto-tuning.

3

Determines the values of 3.P, 3.I and 3.D parameters by auto-tuning.

4

The setpoints when auto-
tuning is started

Determines the values of 4.P, 4.I and 4.D parameters by auto-tuning.

AUTO

Median value of each zone 
width

Determines the values of all PID parameters in use by auto-tuning.

Remarks

The AT parameter settings numbered 1 to 4 in the table above are dependent on how many zones have been set.  For example, if you have set
two zones, you can use AT parameter settings 1 and 2.  Likewise, if you have set three zones, you can use AT parameter settings 1, 2 and 3.

Hysteresis (for Target Setpoints (On-Off Control) and Alarm Setpoints)

Hysteresis can be set in on-off control setpoints and alarm setpoints as well.  With the hysteresis settings, it is possible to prevent relays from
chattering.

 When hysteresis is set in a target setpoint 

 When hysteresis is set in an alarm setpoint

PV value

Point of on-off action

 (Target setpoint)

Hysteresis

Output

On

Off

Output

On

Off

PV value

Point of on-off action

 (Alarm setpoint)

Hysteresis

Example of hysteresis set in PV high limit alarm

 Target Setpoint Ramp Setting Function

Use this function to prevent the target setpoint from changing suddenly.  The ramp setting function works when:

[1] the target setpoint is changed (example: change in “1.SP” from 100

°

C to 150

°

C);

[2] the target setpoint number is switched (example: switch from “1.SP” to “3.SP”);
[3] the power is turned on or the controller is recovered from power failure;
[4] a change is made from manual operation to automatic operation; or
[5] a change is made from the STOP state to the RUN state.

If the target setpoint before switching is smaller than the target setpoint
after switching, the controller operates according to the settings of the
Setpoint Ramp UP (UPR) and Ramp Time Unit (TMU) parameters.  If the
target setpoint before switching is greater than the target setpoint after switch-
ing, the controller operates according to the settings of the Setpoint Ramp
Down (DNR) and Ramp Time Unit (TMU) parameters.  The figure on the
right shows an example when the Target Setpoint Number (SP.NO) param-
eter is switched. The 1.SP and 2.SP parameters are set to 500

°

C and 640

°

C,

respectively. Thus, there is a temperature difference of 140

°

C between the

1.SP and 2.SP parameters. This example shows how the temperature is
changed by as much as this temperature difference over a period of two minutes. In this
example, the UPR parameter is 70

°

C and the TMU parameter is 1 minute.

 PID Switching (Zone PID)

Using a zone PID, you can automatically switch between groups of PID constants according to the temperature zone.  You can set a maximum
of three temperature zones.

Setting Method:
[1] Set the Zone PID Selection (ZON) parameter to

“ON”.

[2] Define a reference point.

When using two zones, define only reference point 1
(1.RP) between the minimum and maximum values of
the PV input range.
When using three zones, define reference points 1 and
2 (1.RP and 2.RP) in the same way as noted above.

Note: Set the maximum and minimum values, as close as possible to those of the actual range to be controlled, in the Maximum Value of PV Input Range

(RH) and Minimum Value of PV Input Range (RL) parameters.  Otherwise, the controller may fail to determine the optimum values when auto-
tuning is carried out.

Setup Parameters

Control Function-related Parameters

Alarm-1 type

1

1

Alarm-2 type

2

Alarm-3 type

1

Alarm-1 hysteresis

Alarm-2 hysteresis

Alarm-3 hysteresis

Alarm-1 delay timer

Alarm-2 delay timer

Alarm-3 delay timer

0.0 to 100.0% of PV input range span 
Output alarm: 0.0 to 100.0% 

0.5% of PV 
input range span
Output alarm: 
0.5% 

An alarm is output when the delay timer expires after the 
alarm setpoint is reached.
0.00 to 99.59 (min, sec.) (enabled when alarm-1 type 

AL1  is 1 to 20 or 28 to 31) 

0.00 to 99.59 (min, sec.) (enabled when alarm-2 type 

AL2  is 1 to 20 or 28 to 31) 

0.00 to 99.59 (min, sec.) (enabled when alarm-3 type 

AL3  is 1 to 20 or 28 to 31) 

0.00

(AL1)

(AL2)

(AL3)

(HY1)

(HY2)

(HY3)

(DY1)

(DY2)

(DY3)

Target setpoint
limiter upper limit

Target setpoint
limiter lower limit

PV color mode

100.0% of 
PV input range

Ref.3.3(4)

Ref.3.3(2)

Ref.3.3(4)

Ref.2.1(8)

Ref.2.1(2)

Ref.4.1(2)

Ref.2.1(4)

Ref.4.1(4)

communi-

cation

function

0.0% of 
PV input range

0.0 to 100.0% of PV input range where, SPL < SPH
Places a limit on the range within which the target 
setpoint is changed.

(SPH)

(SPL)

(PCMD)

Control output cycle time 
Heating-side control output cycle 
time (in heating/cooling control) 

Cooling-side control 
output cycle time

1 to 1000 second

30 second

1 to 1000 second

30 second

(CT)

(CTc)

Preset output/Heating-side 
preset output
(in heating/cooling control) 

Cooling-side preset 
output

-5.0 to 105.0%
In heating/cooling control: Heating side 0.0 to 105.0%  
In Stop mode, fixed control output can be generated. 

0.0%

0.0 to 105.0% 
In Stop mode, cooling-side fixed control output can be 
generated. 

0.0%

(PO)

(POc)

PID control mode

0: Standard PID control (with output bump at SP change) 
1: Fixed point control (without output bump at SP change) 
Choose  fixed point control  when controlling pressure or flow rate. 

0

Zone PID selection 

OFF: SP selection 
ON: Zone PID 

ON

(C.MD)

Ramp-rate time unit 
setting

0: hour, 1: minute
Time unit of setpoint ramp-up (UPR) and setpoint 
ramp-down (DNR) 

0

(TMU)

Protocol selection 

0

Baud rate

0: 600, 1: 1200, 2: 2400, 3: 4800, 4: 9600 (bps)

4

Parity 0: 

None 

1: Even 
2: Odd 

1

Stop bit 

1, 2

1

Data length 

7, 8: Fixed at 7, when the P.SL parameter is set to MODBUS (ASCII). 
Fixed at 8, when the P.SL parameter is set to MODBUS (RTU) 
or Ladder Communication. 

8

Address 

1 to 99 
However, the maximum number of stations connectable 
is 31. 

1

Minimum response 
time 

0 to 10 (

 10 ms) 

0

0: PC link communication 
1: PC link communication (with sum check) 
2: Ladder communication 
3: Coordinated master station 

4: Coordinated slave station 

7: MODBUS (ASCII) 

8: MODBUS (RTU) 

10: Coordinated slave station (loop-1 mode) 
11: Coordinated slave station (loop-2 mode) 

(P.SL)

(BPS)

(PRI)

(STP)

(DLN)

(ADR)

(RP.T)

If this parameter symbol appears, press the SET/ENT key to return to the FUNC menu. 
Caution: Do not change the setpoint of the TEST parameter, otherwise the controller will be disabled. 

(TEST)

Parameter 

Symbol

Name of Parameter

Setting Range and Description

Initial Value

User Setting

Target Item 

in CD-ROM

AUTO

Anti-reset windup 
(Excess integration 
prevention) 

AUTO (0), 50.0 to 200.0% 
Used when the control output travels up to 100% or down 
to 0% and stays at this point. 
The larger SP, the sooner PID computation 
(integral computation) stops.

(AR)

(ZON)

Point of 

on-off action

(Alarm setpoint)

PV value

Output

On

Off

Hysteresis

OFF, 1 to 25, 28 to 31 
1: PV high limit (energized, no stand-by action) 
2: PV low limit (energized, no stand-by action) 
3: Deviation high limit (energized, no stand-by action) 
4: Deviation low limit (energized, no stand-by action)
5: Deviation high limit (de-energized, no stand-by action) 
6: Deviation low limit (de-energized, no stand-by action)
These Alarm Type parameters are common to the 
parameters 1.SP to 4.SP. See  List of Alarm Types  on the 
back for other alarm types.

0: Fixed in green 
1: Fixed in red 
2: Link to alarm 1 (Alarm OFF:green, Alarm ON:red) 
3: Link to alarm 1 (Alarm OFF:red, Alarm ON:green) 
4: Link to alarm 1 and 2 (Alarm OFF:green, Alarm ON:red)
5: Link to alarm 1 and 2 (Alarm ON:red, Alarm OFF:green) 
6: PV limit (Within PV range:green, Out of PV range:red)
7: PV limit (Within PV range:red, Out of PV range:green)
8: SP deviation (Within deviation:green, Out of deviation:red)
9: SP deviation (Within deviation:red, Out of deviation:green)

Hysteresis for PV high limit alarm

Time

Hysteresis

Alarm setpoint

Alarm output

Delay timer

PV

on

off

Delay timer

Input-/Output-related Parameters

Parameter 

Symbol

Name of Parameter

Setting Range and Description

Initial Value

PV input type (PV INPUT 
terminals) 
     -       -      terminals 

OFF, 1 to 18, 30, 31, 35 to 37, 40, 41, 50, 51, 55, 56 
See Instrument Input Range Codes in  

Initial Settings 

 

User’s Manual  

 

.

 

OFF

PV input unit

C: degree Celsius

F: Fahrenheit

(This parameter is not shown for voltage input.) 

C

Max. value of PV input 
range

Min. value of PV input 
range 

Max. value of 
instrument 
input range 

Min. value of 
instrument 
input range 

Set the PV input range, however RL < RH
-Temperature input
Set the range of temperature that is actually controlled.
- Voltage input
Set the range of a voltage signal that is applied.
The scale across which the voltage signal is actually controlled 
should be set using the parameters Maximum Value of PV Input 
Scale (SH) and Minimum Value of PV Input Scale (SL).

PV input decimal point 
position (displayed 
at voltage input)

Max. value of PV input 
scale 
(displayed at voltage input)

Min. value of PV input 
scale 
(displayed at voltage input)

0 to 3
Set the position of the decimal point of voltage-mode PV  input.
0: No decimal place

1: One decimal place

2 , 3: Two, three decimal places

1

100.0

-1999 to 9999, however SL < SH
Set the read-out scale of voltage-mode PV input.

0.0

User Setting

Target Item 

in CD-ROM

(IN)

(UNIT)

(RH)

(RL)

(SDP)

(SH)

(SL)

Selection of PV input 
burnout action

External RJC setpoint

OFF
1: Up scale 
2: Down scale

-50.0 to 50.0 

C

-58.0 to 122.0 

F

ON

(BSL)

1

0.0 

C

32.0 

F

Presence/absence of 
PV input reference 
junction compensation

OFF, ON

(RJC)

Control output 
type

0

(OT)

13

12

11

0

1

2

3

Time proportional PID relay contact output (terminals     -     -     )

Time proportional PID voltage pulse output (terminals     -     )

Current output (terminals     -     )

ON/OFF control relay contact output (terminals     -     -     )

3

2

1

3

2

1

17

16

17

16

(ERJC)

DI function selection

1

(DIS)

Retransmission output 
type

1: PV,  2: SP,  3: OUT, 4: Loop power supply for sensor (15 V)
In position proportional control, a valve opening signal (0 to 100%) is 
transmitted if setpoint “3” is selected.
In heating/cooling control, an output value before allocation to heating 
and cooling control (0 to 100%) is transmitted if setpoint “3” is selected 
(0 to 50%: Cooling-side output; 50 to 100%: Heating-side output). 

1

Max. value of 
retransmission output 
scale 

Min. value of 
retransmission output 
scale

RET=1, 2: RTL + 1 digit to 100.0% of PV input range 
RET=3: RTL + 1 digit to 100.0% 

RET=1, 2: 0.0% of PV input range to RTH - 1 digit 
RET=3: 0.0% to RTH - 1 digit 

100.0% of 
PV input range 

0.0% of 
PV input range 

(RET)

(RTH)

(RTL)

Disables the external contact input.

DI1: 2.SP (on)/1.SP (off), DI2: AUTO (on)/MAN (off)

DI1: Hides (on)/shows (off) the LOCK setup parameter.
DI2: Unused.

See the table below.

DI1: 2.SP (on)/1.SP (off), DI2: STOP (on)/RUN (off)

OFF

1

2

3

4

Control output 
type

Continued

Heating/cooling
type: 4

Ref.2.2(1)

Ref.3.1(1)

(OT)

The following 4 to 12 are displayed only for heating/ cooling type controllers.

4

5

6

7

8

9

10

11

12

Heating-side relay output (terminals      -      -     ), 
cooling-side relay output (terminals      -     )

Heating-side pulse output (terminals      -     ), 
cooling-side relay output (terminals      -     ) 

Heating-side current output (terminals      -     ), 
cooling-side relay output (terminals      -     )

Heating-side relay output (terminals      -     -     ), 
cooling-side pulse output (terminals      -     )

Heating-side pulse output (terminals      -     ), 
cooling-side pulse output (terminals      -     )

Heating-side current output (terminals      -     ), 
cooling-side pulse output (terminals      -     )

Heating-side relay output (terminals      -     -     ), 
cooling-side current output (terminals      -     )

Heating-side current output (terminals      -     ), 
cooling-side current output (terminals      -     ) 

3

2

1

7

4

7

4

7

4

3

2

1

3

2

1

17

16

15

14

15

14

15

14

15

14

15

14

15

14

17

16

17

16

17

16

17

16

17

16

Heating-side pulse output (terminals      -     ), 
cooling-side current output (terminals      -     )

SP Selection when DIS = 3 is set

DI1

DI2

1.SP

4.SP

3.SP

2.SP

ON

ON

ON

ON

OFF

OFF

OFF

OFF

SELECT display-1
registration 

SELECT display-2
registration 

SELECT display-3
registration  

SELECT display-4
registration 

OFF

OFF

OFF, 201 to 1015
Select the desired parameter from among the operating and setup 
parameters, then register the number (D register No.) accompanying that 
parameter. 
For example, registering “231” for C.S1 allows you to change alarm-1 
setpoint in operating display. 
Numbers for registering alarm SP parameter for operating display: 

Alarm-1 setpoint: 231

Alarm-2 setpoint: 232 

Alarm-3 setpoint: 233 

Above numbers are alarm setpoint parameters for target setpoint-1 (1.SP).
See User’s Manual (Reference) (CD-ROM). 

(C.S1)

(C.S2)

(C.S3)

(C.S4)

Key lock

OFF: No key lock
1: Change to any parameter prohibited

Prohibits any operating parameter or setup parameter from being 
changed.  
The setpoint of the LOCK parameter itself can be changed, however.

2: Change to and display of operating parameters prohibited

Turns off the display for setting operating parameters, thus 
prohibiting any change to the parameter settings.
(Hold down the SET/ENT key for more than 3 seconds to show the 
password check display.)

3: Disables the A/M key on the instrument’s front panel.

(LOCK)

Password setting 

0: Password not set 
1 to 9999 

0

(PWD)

Ref.6.1(1)

Ref.7.1(2)

Ref.7.1(1)

Useful Operating Displays (SELECT Display)

Registering frequently changed parameters in the SELECT display after ordinary operating displays will allow you to change settings easily.
A maximum of four displays can be registered.

Setting method:
Set the parameter numbers (D register numbers) you wish to register
for setup parameters C.S1 to C.S4.

Alarm parameter for target setpoint-1

Registration number

Alarm-1 setpoint parameter

Alarm-2 setpoint parameter

Alarm-3 setpoint parameter

231

232

233

For any registration number other than those above, see User’s Manual
(Reference) (CD-ROM version).

 Heating/Cooling Control (for a Heating/Cooling Controller Only)

In heating/cooling control, the controller outputs the result of computation after splitting it into heating-purpose and cooling-purpose signals.
In addition, the controller can perform PID control or on-off control on the heating and cooling sides separately.  When performing on-off
control, set the proportional band to “0”.
The controller splits the result of computation (0 to 100%) into heating-side and cool-
ing-side signals, as described below.

• 0% to 50% of the computation result is presented as a 0% to 100% cooling-side

output.

• 50% to 100% of the computation result is presented as a 0% to 100% heating-side

output.

Heating/cooling control provides two methods in which either none of the heating- and
cooling-side outputs are presented or both of the heating- and cooling-side outputs are
presented, as shown in the following figures.

0

0

Cooling-side 
output

Cooling-side 
output

Heating-side 
output

Heating-side 
output

Output (%)

100

Output (%)

100

Deadband (negative)

Deadband (positive)

100(%)

100(%)

50

50

0

0

Value of control output before split into heating- and 

cooling-side outputs

Value of control output before split into heating- and 

cooling-side outputs

Precautions in Heating/Cooling Control

• Keep the ratio of the heating-side proportional band (P) to the cooling-side proportional band (Pc) equal to or below 5.
• If neither the heating side nor the cooling side is performing on-off control, setting the integral time (I or Ic) of one side to “0” results in

the Integral Time parameters of both sides being set to “OFF”,
irrespective of the integral time setting of the other side.

 Cycle Time

A cycle time can only be set if the type of control output is time propor-
tional PID relay output or time proportional voltage pulse output.

A cycle time refers to one period consisting of on- and off-state time
lengths. The ratio of the on-state time to the off-state time differs ac-
cording to the value of the control output. The figure on the right shows
on-to-off time ratios of the control output when the cycle time is set to
10 seconds. Setting a shorter cycle time allows the controller to perform
elaborate control at short time intervals. This significantly reduces the
on- and off-state times, however it shortens the service life of a relay.

PV input value

Control output

Interval of auto-tuning

Auto-tuning is 
complete when the 
3rd peak arrives.

PID control based on 

PID constants determined 

by auto-tuning

On

Off

On

Setpoint

Time

Start of 

auto-tuning

On

Off

2-minute interval of 
temperature rise

140

°

temperature difference

2 . S P = 6 4 0

°

C

1 . S P = 5 0 0

°

C

70

°

C/min 

(140

°

C/2 min) rate of 

temperature change

1 . S P

2 . S P

Switching from 1.SP to 2.SP parameter

Time

Maximum value of PV 

input range (RH)

Reference point 2 

(2.RP)

Minimum value of PV 

input range (RL)

Reference point 1 

(1.RP)

Zone 3: 
Operated with 3rd group of 
PID constants

Zone 2: 
Operated with 2nd group of 
PID constants
Zone 1: 
Operated with 1st group of 
PID constants

PV input value

Setpoint

S E T / E N T

key

S E T / E N T

key

SP display

OUT display

S E T / E N T

key

Ordinary operating displays (example)

Alarm-1 setting 

display (example)

Useful 

operating display

 (SELECT display)

P V

MAN

A / M

S P

AL1

2

3

SP

2

3

4

S E T / E N T

P V

MAN

A / M

S P

AL1

2

3

SP

2

3

4

S E T / E N T

P V

MAN

A / M

S P

AL1

2

3

SP

2

3

4

S E T / E N T

PID computation

0% to 100%

Heating/cooling 

computation

0% to 50%

Cooling-side 

output limiter

Cooling-side MV 

output 0% to 100%

Heating-side MV 

output 0% to 100%

50% to 100%

Heating-side 

output limiter

PV

SP

Manual MV output

Communication

On

Off

Cycle time

On

Off

Cycle time

Relay’s Behavior when Cycle Time = 10 sec

For 20% of Control Output

For 50% of Control Output For 80% of Control Output

On-state duration: 2 sec
Off-state duration: 8 sec

On-state duration: 5 sec
Off-state duration: 5 sec

On-state duration: 8 sec
Off-state duration: 2 sec

10 sec

10 sec

10 sec

When using target setpoint ramp setting function, PV tracking works
in case of the above conditions [2] to [5].

NOTE

Summary of Contents for UT351

Page 1: ...resistance between three wires should be equal However 10 wire for a maximum range of 150 0 to 150 0 C Wire resistance effect 0 1 C 10 Allowable input voltage 10 V DC for thermocouple mV or RTD input...

Page 2: ...rtional PID relay contact output is configured at factory before shipment 23 24 RS 485 communication Wiring can only be carried out for controllers with communication functions Maximum baud rate 9600...

Page 3: ...F 199 9 to 750 0 F 32 to 4200 F 32 to 2500 F 32 to 3400 F 32 to 3600 F 199 9 to 999 9 F 199 9 to 300 0 F 300 to 1560 F 199 9 to 999 9 F 0 1 of instrument range 1 digit Note1 Note2 RTD Pt100 37 150 0 t...

Page 4: ...PV MAN A M SP AL1 2 3 SP 2 3 4 SET ENT PV MAN A M SP AL1 2 3 SP 2 3 4 SET ENT Displays PV Displays target setpoint Displays target setpoint MAN lamp ON Displays output value Displays output value sym...

Page 5: ...lit Closed lit Closed lit Hysteresis Open unlit Alarm setpoint PV 2 12 Deviation high and low limits Target SP PV Hysteresis Hysteresis Deviation setpoint Closed lit Open unlit Closed lit 7 17 Deviati...

Page 6: ...n which the target setpoint is changed SPH SPL PCMD Control output cycle time Heating side control output cycle time in heating cooling control Cooling side control output cycle time 1 to 1000 second...

Page 7: ...SET ENT Displays PV Displays target setpoint Displays menu OP PA Displays menu STUP Displays menu FUNC Displays parameter PCMD Blinks during change Displays PV Displays target setpoint Setting the Hig...

Page 8: ...en Setting Example 2 Change by Deviation C Time PV green PV red PV red Setpoint SP 50 C PV High limit for PV color change parameter PCCH 10 C Low limit for PV color change parameter PCCL 5 C 60 C 45 C...

Reviews: