IM 05C01E22-10E
4-1
Chapter 4 MODBUS Communication
4.
MODBUS Communication
4.1
Overview
Maximum overall cable length of 1200 m for a maximum of 31 substations
Personal computer
Figure 4-1 Connection of Slaves in MODBUS Communication
Use of the MODBUS communication enables UT150L to communicate with a wide variety of devices
such as PCs. In this communication, you use such device to read/write data from/into D registers,
(internal registers) of the UT150L.
Hereafter, PCs are generally called “host devices.”
See Also
Chapter 5 for information on the D registers.
For the MODBUS communication of the UT150L, we provide the ASCII mode (ASCII system) and
RTU mode (binary system) for the communication mode.
Table 4-1 ASCII and RTU Modes
Item
Number of data bits
Message start mark
Message end mark
Length of message (Note 1)
Error detection
Note 1: When the length of a message in the RTU mode, it is assumed to be “N.”
Note 2: When the communication rate is 9600 bps, 1
9600
24 sec or less.
Data time intervals
ASCII Mode
7 bits (ASCII)
1 second or less
2N + 1
CR + LF
: (colon)
Longitudinal redundancy check: LRC
24 bit time or less (Note 2)
Not necessary
Not necessary
8 bits (binary)
RTU Mode
N
Cyclic redundancy check: CRC-16
In the MODBUS communication, a higher-level device identifies each UT150L with a communication
address of 1 to 99. Some of the commands used let you specify broadcast that requires no address
numbers. For more information on broadcast specifications, see subsection 4.2.2.
Summary of Contents for UT150L
Page 1: ...User s Manual Model UT150L Communication Functions IM 05C01E22 10E IM 05C01E22 10E 3rd Edition...
Page 2: ......
Page 8: ...IM 05C01E22 10E vi Appendix Table of ASCII Codes Alphanumeric Codes App 1 Revision Record i...
Page 12: ...IM 05C01E22 10E 1 4...
Page 14: ...IM 05C01E22 10E 2 2...
Page 38: ...IM 05C01E22 10E 3 24...
Page 48: ...IM 05C01E22 10E 4 10...
Page 54: ...IM 05C01E22 10E 6 2...
Page 56: ...IM 05C01E22 10E App 2...
Page 58: ......
Page 59: ......