background image

4

IM05C01E12-01E

 IMPORTANT

To use dynamic auto tune control,
(1) be sure to turn on the final control element, such as a heater, before starting the control, and
(2) make sure the controlled loop is a closed loop.
If you do not follow these precautions, improper PID constants may be written into the controller. If this occurs,
carry out the following:
• Set the parameter CTL at PID.
• Set the PID constants at the factory-set defaults (P = (upper range-limit - lower range-limit) 

×

 5%; I = 240 s.; and D = 60 s.)

• Set the parameter CTL at SLF.
If the control still doesn’t work properly, stop using the dynamic auto tune control function. Change the param-

eter CTL setting to PID and execute auto-tuning to obtain the PID constants.

Note: The alarms numbered 1 to 10 have no waiting 

action, while alarms 11 to 20 have a waiting 
action.
The waiting action turns off the PV and deviation 
alarms that occur from the start of the control 
operation until a stable state is reached.

Hysteresis

Temperature setpoint

Deviation setting

Measured value

Opn (on)

Cls (off)

Hysteresis

Hysteresis

Hysteresis

Hysteresis

Temperature setpoint

Temperature setpoint

Deviation setting

Measured value

Cls 
(on)

Opn
(off)

Cls

(on)

Hysteresis

Alarm setting

Measured value

Opn (off)

Opn (off)

Cls (on)

Hysteresis

Alarm setting

Measured value

Opn (off)

Cls (on)

7

17 

(See note.)

6

16 

(See note.)

De-energized 

on deviation 

low limit

1

11 

(See note.)

PV

high limit

No alarm

Deviation 

high and low 

limit

2

12 

(See note.)

PV

low limit

8

18 

(See note.)

Deviation 

within high- 

and -low-

limit

3

13 

(See note.)

Deviation 

high limit

9

19 

(See note.)

De-energized 

on PV

high limit

4

14 

(See note.)

Deviation 

low limit

10

20 

(See note.)

25

24

De-energized 

on PV

low limit

Break timer 

function

Heater

disconnection

alarm

23

Timer 

function

5

15 

(See note.)

De-energized 

on deviation 

high limit

21

The contact is closed at input 
burnout.

Fault 

diagnosis 

alarm

22

FAIL

output

OFF

Measured value

Opn (off)

Opn (off)

Cls (on)

Deviation setting

Hysteresis

Cls (on)

Measured value

Temperature setpoint

Deviation setting

Cls (on)

Hysteresis

Opn (off)

Measured value

Temperature setpoint

Deviation setting

Hysteresis

Opn (on)

Cls

(off)

Alarm setting

Measured value

Hysteresis

Cls (off)

Opn (on)

Alarm setting

Measured value

Measured value

Temperature setpoint

Hysteresis

Deviation setting

Opn (on)

Cls (off)

The output contact is opened in the following events:

• Program error
• ROM error
• RAM error
• power failure

External contact

(TMR)         Opn

Opn

(off)

Opn

Opn
(off)

Cls (on)

Timer setting

Time

The output contact closes when the timer setting has passed 
since external contact was closed. Then, the output contact  
opens immediately when external contact is opened.

External contact

(TMR)         Opn

Cls (off)

Opn

Cls
(off)

Opn (on)

Timer setting

Time

The output contact opens when the timer setting has passed 
since the contact was closed. Then, the output contact closes
 immediately when external contact is opened.

The controller starts measuring the current from   
the heater disconnection detector when 100 
milliseconds have passed after turning on the 
output.

Cls

Cls
(on)

Heater current

Alarm setting

Opn (off)

Abnormal

Alarm output = ON

Normal

Low limit alarm 
setpoint

In this area, the alarm output is turned 
off even when a measured value falls 
below the low limit alarm setpoint.

Time

Power-on

°

C

Taken as 

normal.

Waiting action

Cls

Blinking

• A/D converter error
• RJC error
• EEPROM error

Blinking

Alarm type

Alarm 

type code

Closed contact

during alarm

Open contact

during alarm

 Alarm Function List

Action

“Opn” and “Cls” indicate that the relay contact is 

opened and closed; “(on)” and “(off)” indicate that 

the lamp is on and off; and white triangles indicate 

temperature control setpoints.

Alarm 

type code

Closed contact

during alarm

Open contact

during alarm

Action

“Opn” and “Cls” indicate that the relay contact is 

opened and closed; “(on)” and “(off)” indicate that 

the lamp is on and off; and white triangles indicate 

temperature control setpoints.

Alarm type

(SP value display)

Target 
setpoint

Minimum value (SPL) to maximum value (SPH) of target setpoint range
Unit: 

°

C/

°

F

SPL

CTL

Control mode

ONF(0): On/off control
PID(1): PID control
SLF(2): Dynamic auto tune control (cannot be set for heating/cooling control)

SLF(2) :for standard type;
PID(1) : for 

heating/cooling type

AT

Auto-tuning

OFF(0): Stop auto-tuning
ON(1): Start auto-tuning

OFF(0)

P

Proportional 
band

1

°

C/

°

F to the temperature that corresponds to 100% of the 

measured input range (scale) span

5% of measured 
input range (scale) 
span

I

Integral time

1 to 3600 seconds; 
OFF(0): no integral action

240 seconds

D

Derivative 
time

1 to 3600 seconds; 
OFF(0): no derivative action

60 seconds

MR

Manual reset

–100 to 100%

50.0% for standard type; 
0.0% for 
heating/cooling type

COL

Cooling-side 
gain

0.01 to 9.99 times

1.00 times

DB

Deadband

0% of measured 
input range (scale) 
span

HYS

Hysteresis for 
on/off control

0

°

C/

°

F to the temperature that corresponds to 100% of the 

measured input range (scale) span 

0.5% of measured 
input range (scale) 
span

CT

Control output
 cycle time

1 to 240 seconds

30 seconds

CTC

Cooling-side 
control output 
cycle time

1 to 240 seconds

30 seconds

SP1

Target 
setpoint 1

Minimum value (SPL) to maximum value (SPH) of target 
setpoint range
Unit: 

°

C/

°

F

There are also optional engineering units for voltage input.

SPL

SP2

Target 
setpoint 2

SPL

FL

PV input filter

OFF(0), 1 to 120 seconds

OFF(0)

BS

PV input bias

–100 to 100% of measured input range (scale) span

0% of measured 
input range (scale) 
span

LOC

Key lock

T1

Timer
setting 1

0.0 to 99.59
Unit: minutes and seconds or hours and minutes
Set the timer time unit using parameter TTU.

For example, 15.25 sets 15 minutes and 25 seconds.
(T1 is for AL1, and T2 is for AL2)

0.00

T2

Timer 
setting 2

0.00

(2) Operating Parameters : Parameters changed rather frequently during operation.

HC

Heater disconnection 
current measured 
value

“HC” is not a parameter to be set. The current value (0 to 80) of heater disconnection 
detector is displayed.    Unit: A (ampere)
Settings: When the display value is – – – –, the heater current is not being measured.

A1

Alarm 1
setpoint

Max. value of 
measured input range 
(scale) (PV alarm)

A2

Alarm 2
setpoint

Min. value of 
measured input range 
(scale) (PV alarm)

IN

Measured 
input type

1 to 23, 31 to 48 (See input range code list.)
OFF(0): No input
(If no input type is specified at the time of ordering, you must set the input type.)

OFF(0), or the input 
range code specified 
with order

DP

Decimal point 
position of 
measured input

0: No decimal place (nnnn)
1: One decimal place (nnn.n)
2: Two decimal places (nn.nn)
3: Three decimal places (n.nnn)

1

RH

Maximum value 
of measured 
input scale

(RL + 1) to 9999

100.0

RL

Minimum value 
of measured 
input scale

–1999 to (RH –1)

0.0

SPH

Maximum value 
of target setpoint 
range

(SPL+1

°

C) to the maximum value of the measured input range 

(scale) ; Unit: 

°

C/

°

F

Maximum value of 
measured input 
range (scale)

SPL

Minimum value 
of target setpoint 
range

Minimum value of measured input range (scale) to (SPH –1

°

C)

Unit: 

°

C/

°

F

Minimum value of 
measured input 
range (scale)

UPR

Setpoint ramp-
up-rate

OFF(0)
or a value from the minimum to the maximum value of the 
measured input range (scale)
Unit: 

°

C/min or 

°

C/hour,  

°

F/min or 

°

F/hour

Set the ramp-rate time unit using parameter TMU.

OFF(0)

DNR

Setpoint ramp-
down-rate

OFF(0)

AL1

Alarm 1 type

OFF(0) or a value from 1 to 22 (see the table of alarm function 
list), and either
23 or 24 (if the timer function [/EX option] is included), and
25 (if the heater disconnection function [/HBA option] is included)

1
(PV high limit alarm)

AL2

Alarm 2 type

OFF(0) or a value from 1 to 22 (see the table of alarm function 
list), and either
23 or 24 (if the timer function [/EX option]) is included)

2
(PV low limit alarm)

HY1

Alarm 1 
hysteresis

0 to 100% of measured input range (scale) span
Unit: 

°

C/

°

F

0.5% of measured 
input range (scale) 
span

HY2

Alarm 2 
hysteresis

SC

SUPER 
function

ON(1): Uses the SUPER function
OFF(0): Does not use SUPER function
Note: Not displayed when on/off control

OFF(0)

DR

Direct/reverse 
action

0: Reverse action
1: Direct action
Note: Not displayed for heating/cooling type

0

ADR

Controller 
address

1 to 99
However, the number of controllers that can be connected per 
host device is 31 at the maximum.

1

BPS

Baud rate

2.4(0): 2400 bps
4.8(1): 4800 bps
9.6(2): 9600 bps

9.6(2)

PRI

Parity

NON(0): Disabled
EVN(1); Even parity
ODD(2): Odd parity

EVN(1)

STP

Stop bit

1 or 2 bits

1 bit

DLN

Data length

7 or 8 bits
• 8 bits when ladder, MODBUS (RTU)
• 7 bits when MODBUS (ASCII)

8 bits

PSL

Protocol 
selection

0: PC-link communication
1: PC-link communication with sum check
2: Ladder communication
3: MODBUS in ASCII mode
4: MODBUS in RTU mode

0

(3) Setup Parameters : Parameters rarely changed in normal use after once having been set.

0: No key lock
1: Prevents operations from being changed except for the 

changing of SP in the operating display

2: Prevents all parameter changing operations
–1: Set 

-1

 to enter the setup parameter setting display.

      But if  

LOC=1 or 2

 is already set, the parameter value can 

not be changed by setting 

LOC=-1

 only. To change the 

parameter value, set 

LOC=0

 at first (for disabling keylock), 

then set 

LOC=-1

 once again.

0

TMU

Setpoint ramp-
rate time unit

0 : 

°

C or 

°

F / hour

1 : 

°

C or 

°

F / min

1

DIS

EOT

TTU

RTH

RTL

External Contact Inputs

21

22

23

SP2
STOP

TMR
STOP

COM

TMR
STOP

SP2
STOP

Parameter DIS

0

1

2

SP1/SP2

switching
SP2 

when DI=ON

Timer starts 

when DI=ON
Timer stops 

when DI=OFF

Timer starts 

when DI=ON
Timer stops 

when DI=OFF

RUN/STOP

switching
STOP 

when DI=ON

SP1/SP2

switching
SP2 

when DI=ON

RUN/STOP

switching
STOP 

when DI=ON

3

4

5

UT150 UT152

UT155

DI-function 
selection

Output in STOP 
mode

Timer time unit

Maximum value 
of retransmission 
output
Minimum value 
of retransmission 
output

In STOP mode by contact input, fixed control output can be 
generated.
0 : 0%, 1 : 100%

0 : hour.minute
1 : minute.second

(Displayed at voltage input)

(Displayed at voltage input)

(Displayed at voltage input)

Temperature input : Within measured input range

Voltage input : RTL+1digit to max. value of measured input 
(scale)(RH)
Min. value of measured input (scale)(RL) to RTH-1digit
However, RTL<RTH

Maximum value of 
measured input range 
(scale)

Minimum value of 
measured input range 
(scale)

0

0

1

 

Parameter Lists

(1) Target Setpoint (SP) and Timer Setting 1 and 2

Code

Name

Setting range and unit

Default

User setting

Code

Setting range and unit

Default

User setting

Code

Name

Setting range and unit

Default

User setting

 PV alarm    Unit: 

°

C/

°

F

Setting range: minimum value to maximum value of 
measured input range (scale)

 Deviation alarm    Unit: 

°

C/

°

F

Setting range: –100 to 100% of the measured input range (scale) span

 Heater disconnection alarm    Unit: A (ampere) 

Setting range: OFF(0), 1 to 80 
(can be set for the alarm 1 setpoint only)

 PID control    Unit: 

°

C/

°

F

Setting range: –(proportional band setting) to +(proportional band setting)

 On/off control    Unit: 

°

C/

°

F

Setting range: –50 to +50% of measured input range (scale)span

Name

Numbers in ( ) are the parmeter setpoints that apply when the 
communication function is used. Ex. OFF(0), ON(1)

 What is Dynamic Auto Tune Control?

Dynamic auto tune control is one of the features offered by the temperature controller.
When the controller is turned on or the measured input value (PV) starts “hunting”, this mode of control monitors
the behavior of the PV and/or OUT (control output value) to automatically determine the optimum PID constants.
This means that the PID constants may be changed automatically. If this is not desirable for your system, operate the
controller in the normal “PID control”.
If you want to automatically determine the PID constants at the initial startup of the controller, first define the target
setpoint (SP) and then turn the controller off once and then back on again. Do not use dynamic auto tune control for
a system where there is interference or continual disturbances.

 

Description of Parameters

This section describes the parameter functions specific to the UT150/UT152/UT155 temperature controllers.
(The functions described in other sections of this manual and the general functions are not discussed.)

Parameter

Function

Parameter

Function

Control mode

CTL

Select one from the following:
a. Dynamic auto tune control (SLF) 

(See note)

b. PID control (PID)
c. On/off control (ONF)
Note: Dynamic auto tune control is not available 

for heating/cooling control.

Read the section below this table to find out more 
about dynamic auto tune control.

PV input bias

BS

This function adds a bias value to the measured input value, 
and the result is used for display and control computation.

This function is useful for carrying out fine adjustment when 
the PV value is within the required accuracy but it differs 
from the value obtained by other equipment.

Manual reset

MR

You can set this parameter only for control 
without an integral action (when registered as 
CTL=PID and I=OFF). The controller outputs the 
manual reset (MR) value when PV=SP. For 
example, if you set MR=50%, the controller 
outputs (OUT) 50% when PV=SP.

Cooling-side
gain 

COL

Maximum/minimum 
value of measured 
input scale

RH, 
RL

For heating/cooling control, you can set the ratio 
between the cooling-side output and heating-side 
output.
For example, if you set COL=2.0 and the heating-
side output is 10% at a certain deviation (SP-PV), 
then the cooling-side output will be 20% when the 
cooling-side also reaches that deviation.

Deadband

DB

You can only set a deadband for heating/cooling 
control. In a positive deadband, there are neither 
heating-side nor cooling-side outputs. In a 
negative deadband, there are both heating-side and 
cooling-side outputs, which overlap each other.

Maximum/minimum 
value of  
target setpoint range  

SPH, 
SPL

Using the SPH and SPL parameters, you can limit 
the setting range of the target setpoint (SP) within 
the measured input range(scale).

This function prevents SP from being mistakenly 
set at too large or too small a value (beyond the 
setting range). 

Hysteresis for 
on/off control 

HYS

For on/off control (CTL=ONF), you can set a 
hysteresis around the on/off point (SP) to prevent 
chattering.

Setpoint ramp
up/ramp-down 
rate

UPR, 
DNR

To prevent a sudden change in SP, or to change SP at a 
constant rate, ramp-up and ramp-down rates can be set 
separately. This function operates at the following events.
a. SP change
b. SP1/SP2 switching
c. Power-on
At power-on, SP starts from
the current PV value.

Set the ramp-rate time unit using parameter TMU.

The cycle time is the period of on/off repetitions 
of a relay or voltage pulse output in time 
proportional PID control. The ratio of the ON time 
to the cycle time is proportional to the control 
output value.

Hysteresis for 
alarm 1 and 2 

HY1,  
HY2

The alarms are output as relay outputs. Since a 
relay has a limited life, excessive on/off actions 
will shorten the life of the alarm. To prevent this, 
you can set a hysteresis to prevent excessive 
on/off actions for both alarm 1 and alarm 2.

PV input filter

FL

This function should be used when the PV display value 
may fluctuate greatly, for example, when the measured 
input signal contains noise. The filter is of the first-
order lag type, and FL sets the time constant. If a larger 
time constant is set, the filter can remove more noise.

SUPER  
function   
selection  

SC

The SUPER function is effective in the following cases:
a. An overshoot must be suppressed.
b. The rise-up time needs to be shortened.
c. The load often varies.
d. SP is changed frequently.
Note 1: The SUPER function will not work when 

on/off control is selected, or I or D 
constants is set at OFF in PID control.

Note 2: For some types of systems, the SUPER 

function may not be so useful.  If this is 
the case, turn off the function.

Decimal point 
of measurement
input

DP

For DC voltage input, the input signal can be scaled for the 
particular engineering unit. For example, if you set the input 
type (IN) at range code 22, the initial range is 0.0 to 100.0.
a. Using DP, set the decimal point position fit for the 

engineering unit you want to use. (In the example below, 
the 2 digits to the right of the decimal point)

b. Next, register the scale values of the measured input scale using 

RH and RL. (In the example below, RH=10.00 and RL=0.00)

Initial scale

100.0 (5V)

0.0 (1V)

10.00 (RH)

0.00 (RL)

Measured input scale 

(after being scaled)

Register the decimal point position using DP.

On/off point (SP)

Hysteresis

ON

OFF

Cycle time

t ON

t OFF

Input

HYS

HYS

ON

OFF

ON

OFF

Deadband

DB (+)

Deadband

DB (+)

0

SP

PV

100%

100

0

SP

100

PV

100%

Cooling 

side

Heating 

side

100%

         

0%

1. When the deadband of a heating/

cooling type is positive
(Proportional band [P] control)

2. When both the heating and cooling 

sides are under on-off control

PV value inside the controller

measured input value

PV bias

+

=

Ramp-rate
for n

°

C/min. 

or n

°

C/h.

Control output 
/ cooling-side 
control output
cycle time

CT 
CTC

2-seconds filter

10-seconds filter

Reviews: