■  Parameters to be set

Control Type

Parameter Symbol Name of Parameter

Setting Range

CNT

Control type

PID: PID control

ONOF: ON/OFF control (1 point of hysteresis)

ONOF2: ON/OFF control (2 points of hysteresis)

H/C: Heating/cooling control

Note:  Some setpoints may not be displayed depending on the model and suffix codes.

Input Function

Parameter Symbol Name of Parameter

Setting Range

IN

PV input type

OFF: Disable

K1: -270.0 to 1370.0 

0

C / -450.0 to 2500.0

 

0

F

K2: -270.0 to 1000.0 

0

C / -450.0 to 2300.0

 

0

F

K3: -200.0 to 500.0 

0

C / -200.0 to 1000.0

 

0

F

J: -200.0 to 1200.0 

0

C / -300.0 to 2300.0

 

0

F

T1: -270.0 to 400.0 

0

C / -450.0 to 750.0

 

0

F

T2: 0.0 to 400.0 

0

C / -200.0 to 750.0

 

0

F

B: 0.0 to 1800.0 

0

C / 32 to 3300

 

0

F

S: 0.0 to 1700.0 

0

C / 32 to 3100

 

0

F

R: 0.0 to 1700.0 

0

C / 32 to 3100

 

0

F

N: -200.0 to 1300.0 

0

C / -300.0 to 2400.0

 

0

F

E: -270.0 to 1000.0 

0

C / -450.0 to 1800.0

 

0

F

L: -200.0 to 900.0 

0

C / -300.0 to 1600.0

 

0

F

U1: -200.0 to 400.0 

0

C / -300.0 to 750.0

 

0

F

U2: 0.0 to 400.0 

0

C / -200.0 to 1000.0

 

0

F

W: 0.0 to 2300.0 

0

C / 32 to 4200

 

0

F

PL2: 0.0 to 1390.0 

0

C / 32.0 to 2500.0

 

0

F

P2040: 0.0 to 1900.0 

0

C / 32 to 3400

 

0

F

WRE: 0.0 to 2000.0 

0

C / 32 to 3600

 

0

F

JPT1: -200.0 to 500.0 

0

C / -300.0 to 1000.0

 

0

F

JPT2: -150.00 to 150.00 

0

C / -200.0 to 300.0

 

0

F

PT1: -200.0 to 850.0 

0

C / -300.0 to 1560.0

 

0

F

PT2: -200.0 to 500.0 

0

C / -300.0 to 1000.0

 

0

F

PT3: -150.00 to 150.00 

0

C / -200.0 to 300.0

 

0

F

0.4-2V: 0.400 to 2.000 V

1-5V: 1.000 to 5.000 V

4-20: 4.00 to 20.00 mA

0-2V: 0.000 to 2.000 V

0-10V: 0.00 to 10.00 V

0-20: 0.00 to 20.00 mA

-1020: -10.00 to 20.00 mV

0-100: 0.0 to 100.0 mV

UNIT

PV input unit

-: No unit, C: Degree Celsius

-: No unit, - -: No unit, - - -: No unit, F: Degree Fahrenheit

RH

Maximum value of 

PV input range

Depends on the input type.

- For temperature input -

Set the temperature range that is actually controlled. 

(RL<RH)

- For voltage / current input -

Set the range of a voltage / current signal that is applied.

The scale across which the voltage / current signal is 

actually controlled should be set using the maximum value 

of input scale (SH) and minimum value of input scale (SL).

(Input is always 0% when RL = RH.)

RL

Minimum value of 

PV input range

SDP

PV input scale 

decimal point 

position

0: No decimal place

1: One decimal place

2: Two decimal places

3: Three decimal places

4: Four decimal places

SH

Maximum value of 

PV input scale

-19999 to 30000, (SL<SH), | SH - SL | ≤ 30000

SL

Minimum value of 

PV input scale

Note 1: SDP, SH, and SL are displayed only for voltage/current input.

Note 2: W: W-5%Re/W-26%Re (Hoskins Mfg.Co.), ASTM E988

Output Function

Parameter Symbol Name of Parameter

Setting Range

OT

Output type selection

Upper two digits

Lower two digits

Control output or Heating-

side control output (Lower 

two digits)

00: OFF

01: OUT terminals (voltage 

pulse)

02: OUT terminals (current)

03: OUT terminals (relay)

06: OUT2 terminals (relay)

07: RET/OUT2 terminals 

(voltage pulse)

08: RET/OUT2 terminals 

(current)

Cooling-side control output 

(Upper two digits)

00: OFF

01: OUT terminals (voltage 

pulse)

02: OUT terminals (current)

03: OUT terminals (relay)

06: OUT2 terminals (relay)

07: RET/OUT2 terminals 

(voltage pulse)

08: RET/OUT2 terminals 

(current)

CT

Control output cycle 

time

Heating-side control 

output cycle time 

(in Heating/cooling 

control)

0.5 to 1000.0 s

CTc

Cooling-side control 

output cycle time

4.  Adjusting Valve Position Automatically 

 

(for a Position Proportional Type Controller Only)

The following operating procedure describes how to input feedback signals from the 

control valve and adjust the fully-open and fully-closed positions of the control valve 

automatically. The fully-open and fully-closed positions of the valve can be adjusted 

automatically by inputting feedback signals from the valve. To adjust the valve posi-

tion, you need to carry out the connection and bring the controller into manual mode. 

For the connection, see “6. Terminal Wiring Diagrams” in "Installation and Wiring", 

and for the manual mode, see “5. Switching between AUTO and MAN” in "Opera-

tions." The automatic adjustment can be done in program pattern operation and local 

operation.

CTL menu is displayed.

OUT menu is displayed.

OFF blinks.

1.

2.

3.

4.

5.

6.

7.

Show the Operation Display.

MAN 

is lit

* When a password is set, PASS is displayed. 

If the correct password is not entered, setup  

parameters cannot be changed. 

Hold down the keys for 3 seconds.

Press the Right arrow key until OUT menu 

appears.

Press the SET/ENTER key.

Press the SET/ENTER key.

Press the SET/ENTER key.

The parameter V.AT (automatic valve 

position adjustment) is displayed.

Press the Up arrow key.

ON is displayed.

Blinks during the change. 

ON has been registered and the automatic 

adjustment of the valve position starts.

V.AT blinks during the automatic 

adjustment. 

After the adjustment is completed, press 

the DISPLAY key or DISP key once to 

return to the Operation Display.

●  

When the adjustment is completed normally, the indication 

  automatically returns to OFF.

●  

When VAT.E appears on PV display, it indicates an error. 

    Check the wiring for feedback input and perform the automatic 

adjustment again. To perform a valve adjustment manually, see 

User’s Manual.

5.  Setting Alarm Type

The following operating procedure shows an example of changing the alarm-1 type 

(factory default: PV high limit alarm) to PV low limit alarm (setpoint: 02) (These 

alarms work irrespective of the operation mode.)

MODE menu is displayed.

ALRM menu is displayed.

1.

2.

3.

Show the Operation Display.

Hold down the key for 3 seconds.

Press the Right arrow key until ALRM menu appears.

Press the SET/ENTER key.

4.

5.

6.

Symbol

Press the SET/ENTER key.

Press the SET/ENTER key.

The parameter AL1 (alarm-1 type) is 

displayed.

The last digit of the setpoint blinks.

Change the setpoint using the Up/Down arrow keys 

to increase and decrease the value and the 

Left/Right arrow keys to move between digits. 

The alarm-1 type setpoint 02 (PV low limit) is 

registered.

After the setup is completed, press the DISPLAY 

key once to return to the Operation Display.

Stand-by action

Energized/De-energized

Latch action

● 

To change the alarm type, change the last 2 digits of the 

5-digit value.

● 

Stand-by action and excitation are turned on or off by 

selecting 1 or 0. (See “  Setting Display of Alarm Type.”)

● 

For the latch action, see User ’s   Manual.

Press the Up/Down arrow keys to display the 

parameter needs to be changed.

MODE menu is displayed.

ALRM menu is displayed.

1.

2.

3.

Show the Operation Display.

Hold down the key for 3 seconds.

Press the Right arrow key until ALRM menu appears.

Press the SET/ENTER key.

4.

5.

6.

Symbol

Press the SET/ENTER key.

Press the SET/ENTER key.

The parameter AL1 (alarm-1 type) is 

displayed.

The last digit of the setpoint blinks.

Change the setpoint using the Up/Down arrow keys 

to increase and decrease the value and the 

Left/Right arrow keys to move between digits. 

The alarm-1 type setpoint 02 (PV low limit) is 

registered.

After the setup is completed, press the DISPLAY 

key once to return to the Operation Display.

Stand-by action

Energized/De-energized

Latch action

● 

To change the alarm type, change the last 2 digits of the 

5-digit value.

● 

Stand-by action and excitation are turned on or off by 

selecting 1 or 0. (See “  Setting Display of Alarm Type.”)

● 

For the latch action, see User ’s   Manual.

Press the Up/Down arrow keys to display the 

parameter needs to be changed.

フ ィ ー ド バ ッ ク 入 力 上 限

フ ィ ー ド バ ッ ク 入 力 下 限

P V

変 化 率 警 報

自 己 診 断 警 報

Hysteresis

Alarm setpoint

PV

SP or Target SP

Hysteresis

PV

Deviation setpoint

SP or Target SP

Deviation 

setpoint

PV

Hysteresis Hysteresis

Open 

(

unlit

)

Closed 

(lit)

SP or Target SP

PV

Deviation setpoint

Hysteresis

-

-

SP or Target SP

PV

Hysteresis Hysteresis

Deviation 

setpoint

Open 

(

unlit

)

SP or 

Target SP

Alarm setpoint

Hysteresis

SP or 

Target SP

Hysteresis

Alarm setpoint

Alarm setpoint

Output

Hysteresis

Closed

(lit)

Hysteresis

Alarm setpoint Output

Alarm setpoint

Hysteresis

PV

Hysteresis

Alarm setpoint

PV

SP or Target SP

Hysteresis

PV

Deviation setpoint

SP or Target SP

Deviation 

setpoint

PV

Hysteresis Hysteresis

SP or Target SP

PV

Deviation setpoint

Hysteresis

SP or Target SP

PV

Hysteresis Hysteresis

Deviation 

setpoint

Closed 

(unlit)

SP or 

Target SP

Alarm setpoint

Hysteresis

SP or 

Target SP

Hysteresis

Alarm setpoint

Alarm setpoint

Hysteresis

PV

Alarm setpoint

Output

Hysteresis

Hysteresis

Alarm setpoint Output

Setting Display of Alarm Type 

Stand-by Action

Energized (0) / De-energized (1)

Alarm type

Without (0) or With (1) 

Stand-by action

Latch action (0/1/2/3/4)

See 

User’s

 Manual.

PV low limit 

alarm setpoint

Treated

as normal

ºC

Power-on

Time

The alarm output does not turn on

in this region even if the PV valule

is below PV low limit alarm setpoint.

Normal

Abnormal

The alarm output

turns on.

No alarm (00)

Alarm Action (De-energized)

PV high limit (01)

Analog input PV high limit (19)

PV low limit (02)

Analog input PV low limit (20)

SP high limit (03)

Target SP high limit (09)

SP low limit (04)

Target SP low limit (10)

Deviation high limit (05)

Target SP deviation high 

limit (11)

Deviation low limit (06)

Target SP deviation low limit (12)

Deviation high and low 

limits (07)

Target SP deviation high and 

low limits (13)

Deviation within high and low 

limits (08) 

Target SP deviation within high 

and low limits (14)

Control output high limit (15)

Cooling-side control output 

high limit (17)

Control output low limit (16)

Cooling-side control output 

low limit (18)

Feedback input high limit (27)

Feedback input low limit (28)

PV velocity (29)

Fault diagnosis alarm (30)

FAIL (31)

Alarm Type (Alarm Setpoint)

Alarm Action (Energized)

Open 

(

unlit

)

Open 

(

unlit

)

Open 

(

lit

)

Closed 

(lit)

Open 

(

unlit

)

Open 

(

lit

)

Closed 

(unlit)

Closed 

(unlit)

Open 

(

lit

)

Closed 

(unlit)

Closed 

(unlit)

Open 

(

lit

)

Open 

(

lit

)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Open 

(

unlit

)

Open 

(

unlit

)

Open 

(

unlit

)

Open 

(

unlit

)

Open 

(

unlit

)

Open 

(un

lit

)

Open 

(

lit

)

Open 

(

lit

)

Open 

(

lit

)

Open 

(

lit

)

Open 

(

lit

)

Open 

(

lit

)

Closed 

(unlit)

Closed 

(unlit)

Closed 

(unlit)

Closed 

(unlit)

Closed 

(unlit)

Closed 

(unlit)

Burnout of PV input, ADC failure, RJC error.

For the factory default, the contact output is turned ON in normal operation, 

OFF at the time of FAIL. Control output: OFF or 0%, Alarm output: OFF

Note 1: “Open/closed” shows status of relay contact, and “lit/unlit” shows status of EV (event) lamp.
Note 2:        Positive setpoint,        Negative setpoint

フ ィ ー ド バ ッ ク 入 力 上 限

フ ィ ー ド バ ッ ク 入 力 下 限

P V

変 化 率 警 報

自 己 診 断 警 報

Hysteresis

Alarm setpoint

PV

SP or Target SP

Hysteresis

PV

Deviation setpoint

SP or Target SP

Deviation 

setpoint

PV

Hysteresis Hysteresis

Open 

(

unlit

)

Closed 

(lit)

SP or Target SP

PV

Deviation setpoint

Hysteresis

-

-

SP or Target SP

PV

Hysteresis Hysteresis

Deviation 

setpoint

Open 

(

unlit

)

SP or 

Target SP

Alarm setpoint

Hysteresis

SP or 

Target SP

Hysteresis

Alarm setpoint

Alarm setpoint

Output

Hysteresis

Closed

(lit)

Hysteresis

Alarm setpoint Output

Alarm setpoint

Hysteresis

PV

Hysteresis

Alarm setpoint

PV

SP or Target SP

Hysteresis

PV

Deviation setpoint

SP or Target SP

Deviation 

setpoint

PV

Hysteresis Hysteresis

SP or Target SP

PV

Deviation setpoint

Hysteresis

SP or Target SP

PV

Hysteresis Hysteresis

Deviation 

setpoint

Closed 

(unlit)

SP or 

Target SP

Alarm setpoint

Hysteresis

SP or 

Target SP

Hysteresis

Alarm setpoint

Alarm setpoint

Hysteresis

PV

Alarm setpoint

Output

Hysteresis

Hysteresis

Alarm setpoint Output

Setting Display of Alarm Type 

Stand-by Action

Energized (0) / De-energized (1)

Alarm type

Without (0) or With (1) 

Stand-by action

Latch action (0/1/2/3/4)

See 

User’s

 Manual.

PV low limit 

alarm setpoint

Treated

as normal

ºC

Power-on

Time

The alarm output does not turn on

in this region even if the PV valule

is below PV low limit alarm setpoint.

Normal

Abnormal

The alarm output

turns on.

No alarm (00)

Alarm Action (De-energized)

PV high limit (01)

Analog input PV high limit (19)

PV low limit (02)

Analog input PV low limit (20)

SP high limit (03)

Target SP high limit (09)

SP low limit (04)

Target SP low limit (10)

Deviation high limit (05)

Target SP deviation high 

limit (11)

Deviation low limit (06)

Target SP deviation low limit (12)

Deviation high and low 

limits (07)

Target SP deviation high and 

low limits (13)

Deviation within high and low 

limits (08) 

Target SP deviation within high 

and low limits (14)

Control output high limit (15)

Cooling-side control output 

high limit (17)

Control output low limit (16)

Cooling-side control output 

low limit (18)

Feedback input high limit (27)

Feedback input low limit (28)

PV velocity (29)

Fault diagnosis alarm (30)

FAIL (31)

Alarm Type (Alarm Setpoint)

Alarm Action (Energized)

Open 

(

unlit

)

Open 

(

unlit

)

Open 

(

lit

)

Closed 

(lit)

Open 

(

unlit

)

Open 

(

lit

)

Closed 

(unlit)

Closed 

(unlit)

Open 

(

lit

)

Closed 

(unlit)

Closed 

(unlit)

Open 

(

lit

)

Open 

(

lit

)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Open 

(

unlit

)

Open 

(

unlit

)

Open 

(

unlit

)

Open 

(

unlit

)

Open 

(

unlit

)

Open 

(un

lit

)

Open 

(

lit

)

Open 

(

lit

)

Open 

(

lit

)

Open 

(

lit

)

Open 

(

lit

)

Open 

(

lit

)

Closed 

(unlit)

Closed 

(unlit)

Closed 

(unlit)

Closed 

(unlit)

Closed 

(unlit)

Closed 

(unlit)

Burnout of PV input, ADC failure, RJC error.

For the factory default, the contact output is turned ON in normal operation, 

OFF at the time of FAIL. Control output: OFF or 0%, Alarm output: OFF

Note 1: “Open/closed” shows status of relay contact, and “lit/unlit” shows status of EV (event) lamp.
Note 2:        Positive setpoint,        Negative setpoint

Note that the SP in reset-mode is SSP (Starting target setpoint).

6.   Setting Alarm Setpoint

The following operating procedure shows an example of setting the alarm-1 setpoint 

to 180.0. (These alarms work irrespective of the operation mode.)

Before setting the alarm setpoint, check the alarm type.

To change the alarm type, see “5. Setting Alarm Type.” 

Display the parameter that need to 

be changed.

Blinks during the change. 

1.
2.

3.

4.

5.

6.

Show the Operation Display.

Display MODE menu with the same procedure as described in 

Setting Alarm Type.

Press the Right arrow key.

AL menu is displayed.

Press the SET/ENTER key.

Press the SET/ENTER key.

Press the SET/ENTER key.

The parameter A1 is displayed.

A1 to A8 represent the alarm-1 to -8 

setpoints.

Each parameter can be changed in the 

Parameter Setting Displays of alarms using 

arrow keys.

Up/Down arrow keys: changing parameters

The setpoint has been registered.

After the setup is completed, press 

the DISPLAY key once to return to 

the Operation Display.

Change the setpoint using the Up/Down 

arrow keys to increase and decrease the 

value and the Left/Right arrow keys to 

move between digits.

Initializing parameter values

Parameters that you have changed can be initialized to factory default values or user 

default values. For details, see “Parameter Initialization” in the User’s Manual.

Changing the parameter display levels

This operation guide does not explain all the parameters. To display all the param-

eters, you need to change the parameter display level to professional setting mode. 

For details, see “Setting Security Functions” in the User’s Manual.

Summary of Contents for UP35A

Page 1: ...AP option is specified 4 program patterns 40 program segments max 20 segments per pattern provided with retransmission output or 15 V DC loop power supply 3 DIs and 3 DOs Type 1 Basic control 0 Standa...

Page 2: ...dards JIS IEC DIN ITS 90 for TC and RTD Contact Input Specifications Number of inputs See the table of Model and Suffix Codes Input type No voltage contact input or transistor contact input Input cont...

Page 3: ...xiliary relay to perform ON OFF control The use of inductance L loads such as auxiliary relays motors and solenoid valves causes malfunction or relay failure always insert a CR filter for use with alt...

Page 4: ...t 1 output PV event 1 output Common Common Common UP 104 105 106 107 108 109 PV PV input TC input RTD input Voltage mV V input A Current mA input B b Equipped as standard 202 203 201 202 203 202 203 2...

Page 5: ...PID control Other setup Operation NO NO NO YES YES YES Set the other parameters as needed Programming Set the program pattern PID tuning Input setup Output setup Installation and wiring Power ON Contr...

Page 6: ...ess the Right arrow key until ALRM menu appears Press the SET ENTER key 4 5 Press the SET ENTER key The parameter AL1 alarm 1 type is displayed The last digit of the setpoint blinks Press the Up Down...

Page 7: ...row keys to move between digits Change the setpoint using the Up Down arrow keys to increase and decrease the value and the Left Right arrow keys to move between digits Press the Down arrow key until...

Page 8: ...22 Segment write error The total number of segments exceeded 20 40 when the option AP is specified ERR23 Segment insert error New segment cannot be inserted because the number of segments in a pattern...

Page 9: ...ld down the PARAMETER key for 3 seconds to display MODE menu Press the SET ENTER key The parameter HOLD Pause cancel release of program operation is displayed during program operation Press the Down a...

Page 10: ...rogram operation is displayed during program operation Other operating procedures for disabling the hold mode 1 Press the RUN key for 1 second during hold mode operation In this case the controller re...

Page 11: ...17 Cooling side OUT high limit 18 Cooling side OUT low limit Add 100 for de energized For example when the PV high limit is de energized the setting is 101 OFF See Pro gram ming in this manual STD to...

Page 12: ...PARAMETER or PARA key and Left arrow key simultaneously for 3 sec DISPLAY or DISP key PARAMETER or PARA key SET ENTER key Move to the Operation Parameter Setting Display Hold down the PARAMETER or PA...

Page 13: ...Net Communication Setting Parameter E3 terminal Area Menu symbol DNET Parameter symbol Name of Parameter Setting Range Initial value User setting Display level BR Baud rate 125K 125k bps 250K 250k bps...

Page 14: ...AR 0020 for operation parameter error only Operation parameter error Operation parameter data is corrupted Initialized to user default value PAR 0040 for program pattern error only Program pattern err...

Reviews: