<Toc>
<1. Installation>
1-7
IM 05E01D02-41E
1st Edition : May 31,2000-00
1.4
Hardware Specifications
PV Input Signals
•
Number of inputs: 1 (terminals
11
-
12
-
13
)
•
Input type: Universal input system. The input type can be selected with the software.
•
Sampling period: 250 ms
•
Burnout detection: Functions at TC, RTD, standard signal (0.4 to 2 V or 1 to 5 V)
Upscale, downscale, and off can be specified.
For standard signal, burnout is determined to have occurred if it is 0.1 V or less.
•
Input bias current: 0.05
A (for TC or RTD b-terminal)
•
Measurement current (RTD): About 0.13 mA
•
Input resistance: 1 M
or more for thermocouple or mV input
About 1 M
for DC voltage input
•
Allowable signal source resistance: 250
or less for thermocouple or mV input
Effects of signal source resistance: 0.1
V/
or less
2 k
or less for DC voltage input
Effects of signal source resistance: About 0.01%/100
•
Allowable wiring resistance: for RTD input
Maximum 150
/wire: Conductor resistance between three wires should be equal
However, 10
/wire for a maximum range of -150.0 to 150.0
C.
Wire resistance effect:
0.1
C /10
•
Allowable input voltage:
10 V DC for thermocouple, mV, or RTD input
20 V DC for DC voltage input
•
Noise rejection ratio: 40 dB (50/60 Hz) or more in normal mode
120 dB (50/60 Hz) or more in common mode
•
Reference junction compensation error:
1.0
C (15 to 35
C)
1.5
C (0 to 15
C, 35 to 50
C)
•
Applicable standards: JIS, IEC, DIN (ITS-90) for thermocouples and RTD
Loop Power Supply
Power is supplied to a two-wire transmitter.
(15 V DC: terminals
14
-
15
)
A resistor (10 to 250
) connected between the controller and transmitter converts a
current signal into a voltage signal, which is then read via the PV input terminal.
Supply voltage: 14.5 to 18.0 V DC, max. 21 mA (provided with a protection circuit
against a field short-circuit)
Retransmission Output
Either PV, program setpoint, or control output is output.
Either the retransmission output or the loop power supply can be used with terminals
14
-
15
.
•
Number of outputs: 1 (terminals
14
-
15
)
•
Output signal: 4-20 mA DC
•
Load resistance: 600
or less
•
Output accuracy:
0.3% of span under standard operating conditions (23
2
C,
55
10% RH, power frequency of 50/60 Hz)