IM 05F01D02-03E (1)
This manual contains a parameter map as a guideline for setting parameters, and lists of parameters for recording User
Settings.
Contents
1. Basic Key Operation Sequence and Parameter Map
2. Lists of Parameters
1. Basic Key Operation Sequence and Parameter Map
NOTE
Changing the registered value of a setup parameter
may cause the registered value of an operating pa-
rameter to be initialized automatically. Thus, when
you have changed a setup parameter, always check
that the registered value of the operating parameter
is appropriate. If it is initialized to default, reset it to
the required value.
P V
AL1
2
3
4
S E T / E N T
P V
AL1
2
3
4
S E T / E N T
P V
AL1
2
3
4
S E T / E N T
P V
AL1
2
3
4
S E T / E N T
P V
AL1
2
3
4
S E T / E N T
P V
AL1
2
3
4
S E T / E N T
Yes
No
Alarm-4 setpoint
C
B
Menu
Displayed only for UM350-
ⵧ
1, UM350-
ⵧ
2, UM330-
ⵧ
1, UM330-
ⵧ
2
Menu
A
If you become unsure of key operation during parameter
setting, hold down the key for more than
3 seconds. This returns you to the display at
power-on (i.e., operating display).
?
SET/ENT
SET/ENT
key
SET/ENT
SET/ENT
key
SET/ENT
key
SET/ENT
key
Alarm-3 setpoint
Alarm-1 setpoint
Alarm-2 setpoint
PV peak value
PV bottom value
PV input bias
PV input filter
Nothing is displayed.
Displays the
operating
parameter menu
symbol “OP.PA.”
Displays a setpoint.
Displays a
parameter
symbol.
SET/ENT
Determine PV input type first.
Settings herein are described in “
2. Setting PV Input Type
(Setting First at Power-on) ” in
Initial Settings User’s Manual
.
or key
Password input
(No password is required
when PWD = 0.)
Description of Operating Parameter Setting Display
Description of Operating Parameter Menu Display
Power on
Display?
IN = OFF
Displays PV.
To switch the parameter display, press the key.
Display example
Display example
After PV input type (IN), input parameters
such as PV input unit (UNIT), maximum
value of PV input range (RH), and
minimum value of PV input range (RL)
will be displayed.
Press the key to register
the value.
2.
1.
Use the or key to set a numerical
value. See
Instrument Input Range Codes
in
Initial Settings User’s Manual
.
Blinks during
change.
Press this key for more
than 3 seconds to
move to the operating
parameter setting
display.
SET/ENT
key
Press this key for
more than 3 seconds
to move to the
operating
display.
SET/ENT
key
Operating Display
Operating Parameter Setting Display
B
C
Displayed first after power on.
Menu
Displayed only for indicators
with communication functions
or
key
A
SET/ENT
key
SET/ENT
key
SET/ENT
key
SET/ENT
key
Alarm-2 type
Alarm-3 type
Alarm-1 hysteresis
Alarm-2 hysteresis
Alarm-3 hysteresis
Alarm-1 delay timer
Alarm-2 delay timer
Alarm-3 delay timer
Alarm-4 hysteresis
Alarm-4 type
Key lock
Alarm-4 delay timer
P V
AL1
2
3
4
S E T / E N T
P V
AL1
2
3
4
S E T / E N T
Displays a setpoint.
Displays a parameter.
Nothing is displayed.
Displays a menu, such as
FUNC or I/O.
This parameter is not to be set.
Displayed only for UM350-
ⵧ
1,
UM350-
ⵧ
2, UM330-
ⵧ
1, UM330-
ⵧ
2.
Displayed only for UM350-
ⵧ
1,
UM350-
ⵧ
2, UM330-
ⵧ
1, UM330-
ⵧ
2.
Displayed only for UM350-
ⵧ
1,
UM350-
ⵧ
2, UM330-
ⵧ
1, UM330-
ⵧ
2.
1. Setting display can be switched (moved) using the key.
2. A numerical value is changed by
(1) Using the or key to change a displayed value (decimal point blinking) and
(2) Pressing the key to register it.
3. Pressing the key on an operating display (for more than 3 seconds) brings you to the
operating parameter setting display.
4. Pressing the key on the operating parameter setting display (for more than 3 seconds)
returns you to the operating display.
5. Pressing the key on the setup parameter setting display (for more than 3 seconds)
returns you to the operating display. You cannot return to the operating parameter setting
display from the setup parameter setting display.
Basic Key Operation Sequence
SET/ENT
SET/ENT
SET/ENT
SET/ENT
SET/ENT
Description of Setup Parameter Menu Display
Description of Setup Parameter Setting Display
Alarm/Communication
related
Input related
Alarm-1 type
Protocol selection
Baud rate
Stop bit
Data length
Address
Minimum response time
Parity
PV input type
(PV INPUT terminals)
PV input unit
Maximum value of PV input range
PV input decimal point position
(displayed at voltage input)
Selection of
PV input burnout action
Presence/absence of PV input
reference junction compensation
Maximum value of PV input scale
(displayed at voltage input)
Minimum value of PV input scale
(displayed at voltage input)
Minimum value of PV input range
Retransmission output type
Maximum value of
retransmission output scale
Minimum value of
retransmission output scale
DI function selection
SELECT display-1 registration
SELECT display-2 registration
SELECT display-3 registration
SELECT display-4 registration
Password setting
Press this key for
more than 3 seconds
to move to the
operating
display.
SET/ENT
key
Setup Parameter Setting Display
IM 05F01D02-03E
User’s
Manual
4th Edition: Jan 31, 2005
Models UM350 / UM330
Digital Indicator with Alarms
User’s Manual
Parameters