YOKOGAWA UD310 User Manual Download Page 3

IM 05F01F12-01E 3rd Edition  Mar. 14, 2016-00

3

7. 

Key Operations

 WARNING

To prevent electric shock, the manual setter should be mounted on the panel so as not 

to accidentally touch the terminals when power is being applied.

(1) You can move between parameter setting displays using the 

 key.

(2) To change the parameter setpoint, 

(i)  Change the display value with the 

 or 

 key (the period flashes).

(ii) Press the 

 key to register the setpoint.

(3) In the operating display, pressing the 

 key for at least 3 seconds retrieves the operating 

parameter setting display.

(4) In the operating parameter setting display, pressing the 

 key for at least 3 seconds transfers 

back to the operating display. 

  Registering the key-lock parameter LOC to “–1” retrieves the setup parameter setting display.

(5) In the setup parameter setting display, pressing the 

 key for at least 3 seconds transfers back 

to the operating display.

 CAUTION

Changing certain setup parameters may automatically initialize the operating 

parameters. Therefore, after you change the setup parameters, always check the 

operating parameter setpoints to find out if appropriate values have been set for them. If 

the operating parameters have been initialized, set them to their appropriate values.

 CAUTION

At power-on, the manual setter displays the operating display, but if the measured input 

type setting remains OFF, “IN” appears. In this case, press the 

 key to display the 

measured input range code you want to use, then press the 

 key to register it. (Refer 

to the flowchart below.)

is displayed

?

When measured input range code has been already set, 

the operating display shown below appears.

Yes

No

Note: If no key is pressed for a period 

of two minutes or more while in 

the operating or setup parameter 

setting display, the manual setter 

automatically returns to operating 

display.

• Displayed when AL1, AL2 = 1 to 20

LOC=

When 

–1

When LOC=–1,

transfers to the

setup parameter

setting display

Press the 
           key 
to move 

between items.

When “In” appears, press the
key to display the measured input 
range code you want to use, then 
press the           key to register it. 
After this operation, the manual 
setter shows the operating 
display.

CAUTION

Set 

-1

 to enter the setup parameter setting display. But 

if  

LOC=1 or 2

 is already set, the parameter value can 

not be changed by setting 

LOC=-1

 only. To change the 

parameter value, set 

LOC=0

 at first (for disabling 

keylock), then set 

LOC=-1

 once again.

Operating Display

Set the parameters 

as follows not to 

display a measured 

input value.

Measured input type (IN):

DC voltage input (20 to 23)

PV/SP display (PVD) 

: OFF

TIP

Power ON

A

Operating Parameter Setting Display

Setup Parameter Setting Display

A1
A2

FL

BS

LOC

SPH

SPL

Displayed when DC voltage 

input range code (20 to 23) 

is set

DP

RH

RL

IN

AL1

AL2

HY1

HY2

PVD

CAUTION

A

RTH

RTL

Measured input 

value(PV)

Target setpoint(SP)

No display

Target setpoint(SP)

Press the

        key

for at least

3 seconds.

Press the 
           key 
to move 

between items.

Press the

          key for

at least 3 seconds.

(To operating 

display)

Note

Press the

          key for

at least 3 seconds.

(To operating 

display)

Note

At first

When parameter PVD=ON

(factory-set default)

When parameter PVD=OFF

● UD310 Measured Input Type and Ranges

Input type

Range (°C)

Range 

code (°C)

Range (°F)

Range 

code (°F)

For example, to select 

thermocouple type J (°F), 

set the range code to 35.

Unspecifed

OFF

Thermocouple

K

–270 to 1370°C

1

–300 to 2500°F

31

0.0 to 600.0°C

2

32.0 to 999.9°F

32

0.0 to 400.0°C

3

32.0 to 750.0°F

33

–199.9 to 200.0°C

4

–300 to 400°F

34

J

–199.9 to 999.9°C

5

–300 to 2100°F

35

T

–199.9 to 400.0°C

6

–300 to 750°F

36

E

–199.9 to 999.9°C

7

–300 to 1800°F

37

R

0 to 1700°C

8

32 to 3100°F

38

S

0 to 1700°C

9

32 to 3100°F

39

B

0 to 1800°C

10

32 to 3200°F

40

N

–200 to 1300°C

11

–300 to 2400°F

41

L

–199.9 to 900.0°C

12

–300 to 1600°F

42

U

–199.9 to 400.0°C

13

–300 to 750°F

43

Platinel 2

0 to 1390°C

14

32 to 2500°F

44

RT

D Pt100

–199.9 to 850.0°C

15

–199.9 to 999.9°F

45

0.0 to 400.0°C

16

32.0 to 750.0°F

46

–199.9 to 200.0°C

17

–300 to 400°F

47

–19.9 to 99.9°C

18

–199.9 to 999.9°F

48

JPt100

–199.9 to 500.0°C

19

DC voltage

0 to 100mV

0.0 to 100.0

User-scalable

20

0 to 5V 0.000 to 5.000

21

1 to 5V 1.000 to 5.000

22

0 to 10V

0.00 to 10.00

23

 IMPORTANT

The manual setter is shipped with the parameters set at the factory-set defaults. Check 

the default values against the “Parameter Lists” in the following page, and change the 

parameter setpoints that need to be changed.

This section explains how to set and register parameter setpoints.

The procedure for changing Target Setpoint(SP) and Alarm 1 Setpoint(A1) can be found on 

"Changing Target Setpoint(SP)" and "Changing Alarm 1 Setpoint(A1)".

You can set the other parameters in the same way.

The following instructions assume that the manual 

setter is already receiving power.

SP (target setpoint) value will be output in 3 

seconds after the change.

Check alarm type before setting the alarm setpoint.

Factory-set settings:

 

Alarm 1 type : OFF

 

Alarm 2 type : OFF

Step 1:

Confirm that the manual 
setter shows the operating 
display during normal 
operation (PV and SP are 
displayed on the indicators).

Step 1:

Confirm that the manual 
setter shows the operating 
display during normal 
operation (PV and SP are 
displayed on the indicators).

Step 2:

Press the         or         key 
to change the SP display 
value to the required 
setpoint. In this example, 
SP is changed to 200°C.

Step 2:

To enter the operating 
parameter setting display, 
press the         key for at 
least 3 seconds.

Press for at least 3 seconds.

Step 3:

Press the         or         key to 
change the current A1 
setpoint to a required 
setpoint. In this example, A1 
is changed to 200°C.

The period flashes while the setpoint is being changed.

Step 4:

Press the      key once to 
register the setpoint.
The period goes out.
A1 is now changed.
Another press of the
        key calls up the Alarm 2 
setpoint(A2) display.
To return to the operating
display, press the          key for at least 3 seconds.

The period goes out.

n

 Changing Target Setpoint (SP)

n

 Changing Alarm 1 Setpoint (A1)

Measured input range

Target setpoint range

(Factory-shipped settings)

Target setpoint range

(after scaling)

SPL

SPL

Minimum value 

of measured input 

range (scale)

Maximum value 

of measured input 

range (scale)

SPH

4mA

20mA

SPH

Manual setting output

(4 to 20mA)

8.  Troubleshooting

Is the manual setter defective?

Completely inactive?

Normal?

Contact us for repair

Problem solved

Cancel the setting

Key operation failure?

Is the key

locked?

Normal?

Correct it

Check the terminal connection 

of the power supply

Check key-lock 

setting

Display failure?

I/O signal failure?

Turn the power off, 

then on

Verify the I/O spec. 

of manual setter

Verify the spec. of 

I/O destinations

Check the power 

supply voltage

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

No

No

No

No

No

No

No

In the event of an abnormality, perform the following checks as outlined by the flowchart.

 Error Display during Operation

(1) If the manual setter displays one of the following, carry out the appropriate remedy for the 

particular error.

Display

Error content

Remedy

P.Er The parameter is abnormal

Check the setpoints of all the parameters and set them at 

their proper values.

B.o Input burnout

Check the sensor wiring and correct it.

Not display when the setup parameter PVD=OFF.

OOO

PV over-scale

(PV exceeds its effective range.)

Check the measured input type and scale settings and 

correct them.

Not display when the setup parameter PVD=OFF.

UUU

PV under-scale

(PV falls below its effective range.)

No PV display

Set the setup parameter PVD=ON to display PV.

(2) The manual setter needs to be repaired if any of the indications in the table below appear.

  In these cases, do not try to repair the manual setter yourself. 

  Order a new manual setter or contact us for repair.

Display

Error content

Display

Error content

Unknown (at power-on)

CPU failure

Flashing “Err” (at power-on) RAM or ROM failure

All extinguished (at power-on) Power source failure

Flashing “Err”

(during operation)

A/D converter failure, 

RJC failure, or EEPROM failure

“Err” (at power-on)

Calibration abnormal

 When Power Failure Occurred during Operation

● 

  Momentary power failures shorter than 20ms(or shorter than 1ms when “/V24” is specified) have 

no effect on the manual setter operation (i.e., normal operation continues).

● 

 

For power failures of 20ms or longer(or 1ms or longer when “/V24” is specified), however the 

status will be as follows.  

(The manual setter action at power recovery is the same as at power-on.)

 • Alarm action: Continues (but alarms with a waiting action enter the waiting state once)

 • Setting parameters: Maintained

Reviews: