LIMIT CONTROLLER

Model: TC10-L

  Quick Guide . IM 05C01E81-11EN 

rd

 edition - February 2020

Yokogawa Electric Corporation

2-9-32 Nakacho, Musashino-shi, Tokyo 180-8750 Japan
internet site:

www.yokogawa.com

EU Declaration of conformity and Manual retrieval

TC10-L is a panel mounting, Class II instrument.  It has been de-
signed with compliance to the European Directives.  All information 
about the controller use can be found in the Engineering Manual: 
IM 05C01E81-12EN and the Communication Manual: IM 05C01E81-13EN 
and General Specification: GS 05C01E81-11EN.
The EU Declaration of Conformity and the manual of the controller 
can be downloaded (free of charge) from the web-site: 

www.yokogawa.com/ns/tc10/im/

The Authorised Representative for this product in the EEA is:

Yokogawa Europe BV

 (Address: Euroweg 2 , 3825 HD Amersfoort, 

The Netherlands) is the Authorised Representative of 
Yokogawa Electric Corporation for this Product in the EEA.

Safety Precautions

The following general safety precautions must be observed during 
all phases of operation, service and repair of this instrument. 
If this instrument is used in a manner not specified in this manual, 
the protection provided by this instrument may be impaired.  Also, 
YOKOGAWA Electric Corporation assumes no liability for the customer’s 
failure to comply with these requirements.  The following symbol is 
used on the instrument.
This manual is an essential part of the product; keep it in a safe place for 
future reference.  This manual is intended for the following personnel:
- Engineers responsible for installation, wiring, and maintenance of 

the equipment.

- Personnel responsible for normal daily operation of the equip-

ment.

WARNING

Calls attention to actions or conditions that could cause serious or 
fatal injury to the user or damage to the instrument, and indicates 
precautions that should be taken to prevent such occurrences. The 
user must refer to the Engineering manual for special instructions.

 

AC

 

AC/DC

 

The equipment wholly protected by double insulation or 
reinforced insulation.

WARNING

- Whenever a failure or a malfunction of the device may cause dan-

gerous situations for persons, things or animals, please remember 
that the plant must be equipped with additional devices which 
will guarantee safety.

- We warrant that the products will be free from defects in material 

and workmanship for 18 months from the date of manufacturing. 
Products and components that are subject to wear due to conditions 
of use, service life and misuse are not covered by this warranty.

Safety, Protection and Modification of the Product

- In order to protect the system controlled by this product and the 

product itself, and to ensure safe operation, observe the safety 
precautions described in the Engineering manual. Use of the 
instrument in a manner not prescribed herein may compromise 
the product’s functions and the protection features inherent in 
the device. We assume no liability for safety, or responsibility for 
the product’s quality, performance or functionality should users 
fail to observe these instructions when operating the product.

- Installation of protection and/or safety circuits with respect to a 

lightning protector; protective equipment for the system controlled 
by the product and the product itself; foolproof or failsafe design 
of a process or line using the system controlled by the product  or 
the product itself; and/or the design and installation of other 
protective and safety circuits are to be appropriately implemented 
as the customer deems necessary.

- This product is not designed or manufactured to be used in critical 

applications that directly affect or threaten human lives. Such 
applications include nuclear power equipment, devices using 
radioactivity, railway facilities, aviation equipment, air navigation 
facilities, aviation facilities, and medical equipment. If so used, 

it is the user’s responsibility to include in the system additional 
equipment and devices that ensure personnel safety.

- Modification of the product is strictly prohibited.
- This product is intended to be handled by skilled/trained person-

nel for electric devices.

- Overvoltage category: II

WARNING

- This instrument is for Measurement Category No. 1.  Do not use it 

for measurements in locations falling under Measurement Catego-
ries No. 2, No. 3 and No. 4.

Cable

entrance

Internal wiring

Outlet

IV

III O

T

II

No. EN 61010-2-030

Description

No. 1 O (Other)

For measurements performed on circuits not directly 
connected to MAINS.

No. 2 Measurement 

Category II

For measurements performed on circuits directly 
connected to the low-voltage installation.

No. 3 Measurement 

Category III

For measurements performed in the building instal-
lation.

No. 4 Measurement 

Category IV

For measurements performed at the source of the 
low-voltage installation.

How to Connect Wires

WARNING

- Wiring work must be carried out by a person with basic electrical 

knowledge and practical experience.

- Be sure to turn OFF the power supply to the controller before wiring 

to avoid an electric shock. Use a tester or similar device to ensure 
that no power is being supplied to a cable to be connected.

- As a safety measure, always install a circuit breaker (an IEC 60947 

compatible product, 5 A, 100 V or 220 V AC) in an easily accessible 
location near the instrument.  Moreover, provide indication that the 
switch is a device for turning off the power to the instrument.

- Install the power cable keeping a distance of more than 1 cm from 

other signal wires.

- The power cable is required to meet the IEC standards concerned or the 

requirements of the area in which the instrument is being installed.

- Wiring should be installed to conform to NEC (National Electrical 

Code: ANSI/NFPA-70) or the wiring construction standards in 
countries or regions where wiring will be installed.

- For control relay output, alarm relay output, and power terminal 

connections, use heat-resistant cables.

- Recommended tightening torque: 0.5 Nm.

Model and suffix codes

Model Code

Suffix codes

Description

TC10

L

H C

o

R

o

D

o

F /GK Temperature Controller

Fixed code

L

Always "-L"

Power supply H

100 to 240 VAC

Fixed code

C

Always "C"

Retransmission

N

None

A

Measured value retransmission 

out 4 to 20 mA 

Limit control output

R

Limit control relay output

Alarm output 1,2

N

None

R

Alarm output: 2 points (OP3 relay 

+ OP4 SSR)

Fix code

D

Always “D”

Serial communication

N

None

S

RS485 Modbus

Fixed code

F

Always “F”

Option Code

/GK Panel gasket for IP65

NOTE about the structure of this document

The usual installation sequence is the reverse of the operator 
sequence.
During installation, the first step is the wiring  procedure followed 
by the complete configuration. At this point you can set the operator 
parameter and  than you can use the instrument.
This document follows this structure.

PV

SP

Process Value

(in eng. units)

Set Point

Param. value

or

State/Function

(Editing mode)

Limit
Control

High
Limiter

Exceeded
indication

Unit
(°C/°F)

DISPLAY AND KEYS

Access to:

- Operator visualizations

-

Parameters

Editing

-

Configuration

Editing

Increase the displayed
value or select the
next element of the
list
Decrease the displayed
value or select the
previous element
Exit from Operator
commands/Parameter
setting/Configuration

Confirming operation
(Pressed when OUT LED lit
and EX LED is OFF.)

Operator Mode

Editing Mode

Confirm and go to
Next parameter

EX

OUT

PK

HI

AL1

AL2

-L

Alarms
active

Output

(PV, max or min, time)

DIMENSIONS

Overall dimensions (L x H x D): 48 x  48 x 73 mm

(1.89 x 1.89 x 2.87 in.)

Panel Cut-out (L x H):

45

+0.6

x 45

+0.6

mm

(1.78

+0.023

x 1.78

+0.023

in.)

Mounting requirements

This instrument is intended for permanent installation, for indoor

use only, in an electrical panel which encloses the rear housing,

exposed terminals and wiring on the back.

Select a mounting location having the following characteristics:

1.

It should be easily accessible;

2.

There is minimum vibrations and no impact;

3.

There are no corrosive gases;

4.

There are no water or other fluids (i.e. condensation);

5.

The ambient temperature is in accordance with the operative

temperature (0 to 50°C);

6.

The relative humidity is in accordance with the instrument

specifications (20 to 90%);

The instrument can be mounted on panel with a maximum

thickness of 8 mm.

When the maximum front protection (IP65) is desired, the optional

gasket must be mounted.

This is mandatory for FM approval

MOUNTING

65 mm min.

2.56 in min.

45

+0.6

mm

1.78

+0.023

in

65 mm min.

2.56 in min.

45

+0.6

mm

1.78

+0.023

in

7.

Installation altitude: less than 2000 m;

8.

Pollution category: 2;

!

RS485

TERMINALS

Pin connector

1.4 mm max.

(0.055 in.)

Stripped wire
L:

5.5 mm
(0.21 in.)

L

ELECTRICAL CONNECTIONS

Thermo-

couple

OP3

Limiter

OP4
(note)

Output 4: 0-12V DO

Analogue input

mV, V

mA

Note: Terminal 4 can be programmed as:

- 0 to 12 V SSR Drive Output (OP4) connecting

the load between terminals 4 and 16;

- 12 Vdc (20 mA) transmitter power supply

connecting the 2 wire transmitter between
terminals 4 and 1; for 3 wire transmitter connect
terminal 4 to transmitter power supply input and
terminal 1 and 2 to transmitter signal output.

Neutral

Line

12VDC
(note)

PV

4 to 20 mA
3 wiretransmitter

12VDC
(note)

PV

Pt100

Pt1000

4 to 20 mA
2 wiretransmitter

OP1

Output 1: 4-20 mA

Output
(OP 2)

100 to 240 V AC

(-15 to +10 %)

6.5 VA max

50/60 Hz

Relay output 2,3: 2A, 250 V AC, resistive load
Linear output     : 0/20 mA , 0/10 V

DI1
10 V,
6 mA

P

3

AS

(default: 0)

3

Increase the displayed value
or select the next element

Confirm and go to
Next parameter

Decrease the displayed value
or select the previous element

To exit the

parameter setting

config.

procedure press the       key

Parameters setting

CONFIGURATION PARAMETERS SETTING

Press the       key

for 3 seconds

-L

-L

-L

Go to the groups
Go to the next group

for more than 6 seconds

InP Group

N

Param.

Description

Range value or selection list elements

Dec.

point

1

SEnS

Measuring input 

J = TC J 
crAL = TC K, 
S = TC S, 
r = TC R
t  = TC T, 
n = TC N
Pt1 = PT 100,
Pt10 = PT 1000,
0.60 = 0 to 60 mV,
12.60 = 12 to 60 mV,
0.20 = 0 to 20 mA,
4.20 = 4 to 20 mA,
0.5 = 0 to 5 V,
1.5 = 1 to 5 V, 
0.10= 0 to 10 V
2.10 = 2 to 10 V,

dP

2

dP 

Decimal point figure
Note: For TC and RTD inputs the decimal figure must be 0 or 1 only.

0 to 3

dP

3

SSc

Initial scale readout
NOTE: This parameter will be shown only when a linear input has been selected (mV, V or mA). 

-1999 to 9999

dP

4

FSc

Full scale readout
NOTE: This parameter will be shown only when a linear input has been selected (mV, V or mA). 

-1999 to 9999  (E.U.)

dP

5

unit

Engineering unit
NOTE: This parameter will be shown only when a TC or RTD  input has been selected.

°c or °F

6

FiL

Digital filter on the measured value.
Note: This filter will affect the measured value but also the control action the analogue retransmission and the alarms 
behaviour.

0( oFF) to 20.0 (s)

1

7

bS

PV input bias

-100 to 100 % of the input span

dP

8

di.A

Digital Input action

0 = DI1 direct 
1 = DI1 reverse