<6. PROCEDURES FOR CONVERTER OPERATION>
6-27
IM 12E04A02-02E
The following is the setting key operations.
(Example of display)
1. Select FUNCTION "2." in the <PROGRAM1>
=> OFF (stop)
mode. The current set status is displayed.
2. Press the [>] key to select on/off.
=> ON (execution)
F6601.ai
ON
OFF
3. Press the [ENT] key to enter the setting.
=> ON
The
display
fl
ashes once.
(16) Local Range Setting (FUNCTION "3.")
If automatic range switching and remote range switching are not selected, this function selects
the output range. Contact outputs (A1, A2, A3, A4) operate by the selected output range.
For the relationship between output ranges and contact outputs, see Table 6.10.
The following shows the setting key operations.
(Example of display)
1. Select FUNCTION "3." in the <PROGRAM1>
=> _ _1 (Range 1)
mode. The current set range is displayed with a code.
2. Press the [>] key to select the code.
=> _ _2 (Range 2)
F6602.ai
_ _1
_ _2
(Range 1)
(Range 2)
_ _3
(Range 3)
3. Press the [ENT] key to enter the setting.
=> _ _2
The
display
fl
ashes once.
(17) Setting Output Hold in Maintenance (FUNCTION "4.")
This function sets execution/stop of output hold in maintenance (<MAINT.> or <PROGRAM1, 2>
mode). If "execution" is selected, the output value immediately before operation holds when the
maintenance mode is selected.
The following shows the setting key operations.
(Example of display)
1. Select FUNCTION "4." in the <PROGRAM1>
=> ON (execution)
mode. The current set status is displayed.
2. Press the [>] key to select on/off.
=> OFF (stop)
F6601.ai
ON
OFF
3. Press the [ENT] key to enter the setting.
=> OFF
The
display
fl
ashes once.
Immediately after setting, the setting status of the analog output becomes effective.
When on (hold) is selected, the HOLD lamp is lit while the output is held.
In addition, even if off (no-hold) is selected, FUNCTION "5." setting has priority provided that "_
_2" (hold) or "_ _3" (preset) is selected in the operation of FUNCTION "5." (the next item).
3rd Edition : May. 31, 2010-00
Summary of Contents for TB400G-A1 Series
Page 49: ...Blank Page ...
Page 59: ...Blank Page ...
Page 119: ...Blank Page ...
Page 125: ...Blank Page ...
Page 127: ...Blank Page ...
Page 133: ...Blank Page ...