< 4. OPERATION >
4-2
IM 12A0V2-E
4.2
ST401G-FC4-N-A/AZC
¨
,
ST401G-FC5-N-A/
AZC
¨
Open ball valve (BV1) completely. (BV3) closed. Adjust ball valve (BV2) and needle valve (NV1)
and make the flow rate into free available chlorine detector between 0.1 and 2.5 L/min.
(BV3) is used for manual zero adjustment and washing. To stabilize the zero filter with water,
refer to Section 6.1.7 of IM 12F5A1-01E or Section 3.8 of IM 12F05B10-02EN.
Refer to Figure 4.2 for piping.
(VP40)
Drain
=
=
=
=
=
=
=
=
=
=
BV2
NO
COM
NC
F1
SV1
X
NV1
FCC
=
X
(VP16)
Measuring water
=
FCD
BV1
PR1
BV3
PVC tray
<Tubing materials>
=
=
X
X
Ø22 / Ø15 soft tube with net
VP16 pipe
pipe
VP40
Ø6 / Ø4 Polyethylene tube
BV1,2,3 : Ball valve
PR1
: Pressure-reducing valve
FCC
: Free available chlorine converter
FCD
: Free available chlorine detector
NV1
: Needle valve
F1
: Activated charcoal filter
SV1
: 3-way solenoid valve
*1: When -FC5 is specified, SV1 displayed
as S3 on the converter screen.
Figure 4.2
Piping diagram of ST401G-FC4-N-A/AZC
¨
, ST401G-FC5-N-A/AZC
¨
(With free available chlorine analyzer, auto zero calibration)