1-5
IM 04L51B01-20EN
GX/GP/GM Configuration
OPC-UA Server Function
Path
GX/GP:
MENU
key >
Browse
tab >
Setting
> Setting menu
Communication (Ethernet)
settings
>
Server settings
>
Server list
Web application:
Config.
tab >
Communication (Ethernet) settings
>
Server settings
Server list
Hardware configurator:
Communication (Ethernet) settings
>
Server settings Server list
Description
OPC-UA
Setup Item
Selectable Range or Options
Default Value
On/Off
Off/On
Off
Port number
1 or 65535
4840
On/Off
Select
On
to use the OPC-UA server function.
Option
Description
On
The OPC-UA server function is enabled.
Off
The OPC-UA server function is disabled.
Port number
Set the port that the OPC-UA server will use. Unless specified otherwise, you do not need to
change this number.
Others
Communication Security
For details on the GX/GP/GM communication security settings, see below.
GX/G
P: Sectio
n 1.24, “Confi
guring the Security Functions,” in the GX/GP User’s Manual
GM: Sectio
n 2.27, “Con
figuring the Security
Functions,” in the GM User’s Manual
For details on advanced security (/AS), see below.
GX/GP: Section 2.1, “Enabling the Advanced Security Function,” in the GX/GP Advanced
Security Manual.
GM: Section 2.1, “Registering Users and Setting the Signature Method,” in the GM
Advanced Security Manual.