3-6
<Toc> <Ind>
<3. Procedures for Setting PR300 Functions>
IM 77C01E01-10E
3.2.2
Pulse Unit
[Procedure]
(1)
Write a pulse unit value to the D register in the table below. The data type is integer.
(2)
After writing that value, write 1 to the pulse output writing status register, D0211.
D Register
D0209
D0211
Reference No.
40209
40211
H No.
00D0
00D2
Description
Pulse unit
Pulse output writing status
(D0208, D0209, and D0210
are validated)
Effective Range
1 to 50,000
Unit:
100 Wh/pulse
If other than 1: Invalid
If 1: Writing is executed
Initial value of pulse unit: 10 (1000 Wh/pulse)
[Example]
To set the pulse unit to 100 Wh/pulse, write “0001.”
For station number 01, use PC link communication (without checksum) and the random
write command as shown below:
[Command]
[STX]01010WRW02D0209,0001,D0211,0001[ETX][CR]
[Response]
[STX]0101OK[ETX][CR]
NOTE
•
A pulse unit value can be set for the PR300 with pulse output.
•
To set the pulse unit value via communication, set it to 1/100 the value of the displayed
(true) value (e.g., set it to 5 when setting the pulse unit value to 500 Wh/pulse).