1.2

Setting the Voltage Range

This section explains how to set the voltage range by taking as an example the case when the voltage range is changed from 300 V to 600 V.

Using

or

, show the Voltage 

Range screen.

The Specification Change Confirmation screen 

appears.

Measured Value screen

Startup screen

VT Ratio screen

2

1

3

Phase and Wire System screen

6

Specification Change Confirmation screen

Specification Change Confirmation screen

4

The PR300 shows the station number for about 5 

seconds, then the Measured Value screen * appears.

The Phase and Wire System screen appears.

7

The Voltage Range screen appears.

The Voltage Range Setting screen appears.

5

8

9

Voltage Range screen

Voltage Range Setting screen

Voltage Range Setting screen

Turn on the PR300.

Hold down

for at least 3 seconds.

The parameter         (VT ratio) appears.

Using              or            , show

on 

the lower display. 

Press

once.

Press

once.

Current value

Parameter symbol for voltage range

Setpoint

Simultaneously hold down

+

for at least 3 seconds.

Press

once to blink the setpoint.

Using 

or 

, select the setpoint.

2. Setting the VT and CT Ratios

NOTE

Set the VT and CT ratios so that the value of “secondary rated
power 

 VT ratio 

 CT ratio” is smaller than 10 GW. If this value

exceeds 10 GW, the updated VT or CT ratio will not be
incorporated but revert to the current value before change.

2.1

Setting the VT Ratio

This section explains how to set the VT ratio by taking as an example the

case when the VT ratio is changed from the initial value (1) to 4.

Prior to proceeding to the following steps, ensure that the PR300 is turned

on, and the Measured Value screen is displayed.

1

Measured Value screen

VT Ratio screen

1

2

VT Ratio Setting screen

VT Ratio Setting screen

VT Ratio Setting screen

VT Ratio screen

3

4

If you do not operate any key for more than 5 
minutes on the Parameter screen, the PR300 
automatically returns to the Measured Value screen.

Setting completed.

Hold down

for at least 3 seconds.

The parameter        (VT ratio) appears.

Current value

Press

once.

The screen changes to the one for setting the 

parameter        and the alterable digit blinks.

Using

or

, change the setpoint.

Setpoint

To move to the digit to be changed, use the following 
keys:

To the left
To the right

Press

once to blink the setpoint.

5

To return to the Measured Value screen, hold down
       .

When proceeding to set the CT ratio, press             once 
and start from step 

3

 in Section 2.2, “Setting the CT Ratio.”

Press

once while the setpoint is blinking.

The setpoint is confirmed and the PR300 returns to the VT Ratio screen.

To re-set the parameter:

Press any key other than           while all digits of the setpoint are

blinking.

 

The PR300 returns to the initial setting screen.

Parameter (VT Ratio) Setting Types and Ranges

Parameter Symbol

Parameter Name

Setting Type Setting Range (Details)

Initial Value

(Factory-set

Value)

VT ratio

Integral

numeric

value

1 to 6000

1

2.2

Setting the CT Ratio

This section explains how to set the CT ratio by taking as an example the

case when the CT ratio is changed from the initial value (1.00) to 10.00.

Prior to proceeding to the following steps, ensure that the PR300 is turned

on, and the Measured Value screen is displayed.

To return to the Measured Value screen, hold down
        .

Measured Value screen

VT Ratio screen

1

2

3

CT Ratio screen

5

CT Ratio Setting screen

The alterable digit blinks.

6

CT Ratio Setting screen

CT Ratio Setting screen

CT Ratio screen

Setting completed.

CT Ratio Setting screen

4

Current value

Setpoint

Hold down

for at least 3 seconds.

The parameter        (VT ratio) appears.

Press

once.

The parameter        (CT ratio) appears.

Press

once.

The screen changes to the one for setting the parameter

        and the decimal point blinks.

Press

once to fix the position of the decimal point.

To move the decimal point, use the following keys:

To the left 

To the right

Using

or

, change the setpoint.

To move to the digit to be changed, use the following keys:

To the left 

To the right

To re-set the parameter:

Press any key other than           while all digits of the setpoint are

blinking.

 

The PR300 returns to the initial setting screen.

If you do not operate any key for more than 5 
minutes on the Parameter screen, the PR300 
automatically returns to the Measured Value screen.

Press

once to blink the setpoint.

7

Press

once while the setpoint is blinking.

The setpoint is confirmed and the PR300 returns to the CT Ratio screen.

Parameter (CT Ratio) Setting Types and Ranges

Parameter Symbol

Parameter Name

Setting

Type

Setting Range (Details)

Initial Value

(Factory-set

Value)

CT ratio

Floating-point

numeric

value

1.00

0.05 to 32000

Voltage Range Setting screen

11

Measured Value screen

Setting completed.

Voltage Range screen

When proceeding to set the phase and wire system, press    

or 

to show the Phase and Wire System screen, 

with this screen (figure on the left) shown as is. After 

showing the Phase and Wire System screen, start from step 

6

 

in Section 1.1, “Setting the Phase and Wire System.”

Hold down

for at least 3 seconds.

10

To re-set the parameter:

Press any key other than
          while all digits of the setpoint are blinking.
The PR300 returns to the initial setting screen.

Press

once while the setpoint is blinking.

The PR300 shows the Startup screen for about 5 seconds, 

then the Measured Value screen appears.

The setpoint is confirmed and the PR300 returns to the 

Voltage Range screen.

NOTE

The voltage range of single-phase three-wire system is fixed at

300V (between P0 and P1, P0 and P2). The voltage range
cannot be selected.

Select the voltage range of three-phase four-wire system, by

the phase voltage (between P0 and P1, P0 and P2, P0 and P3).

Range of Voltage Range Options

Parameter Symbol

Parameter Name

Setting 

Type

Setting Range (Details)

Initial Value

(Factory-set 

Value)

Voltage range

Selection

150V

300V

600V

300V

* The initial value of the Measured Value screen (display pattern) is Upper

display: Current (phase switch indication), Middle display: Voltage (phase

 

switch indication), and Lower display: Active power.  For the display

 

pattern setting procedures, refer to the PR300 Power and Energy Meter

 

User's Manual (IM 77C01E01-01E).