YOKOGAWA MLD User Manual Download Page 2

 
 

IM 61A01A01-01E-A 

Model 

Suffix  Codes 

Description 

MLD 

 

Field Mounted Loop Indicator (Digital) 

  Input Signal 

   -A 

 

4 to 20 mA DC 

Mounting 


2  

2” Horizontal Pipe 
2” Vertical Pipe (or wall mount) 

Housing 

           /1 
           /2 
 
 
 

Cast Aluminum Alloy - (Standard Housing) 
SUS316 Cast Stainless Steel and ASTM CF-8M 

Electrical 
Connection 

          /00 
          /20 

/30 
/40 

ANSI ½ NPT female, without blind plug 
ANSI ½ NPT female, 316 Stainless Steel blind plug 
ISO M20 female, without blind plug 
ISO M20 female, 316 Stainless Steel blind plug 

Ex Protection 

  /FF1 
  /CF1 

FM Explosion Proof 
CSA Explosion Proof 

Optional Specifications 

Coating 

                /X1 
                /X2 

Epoxy resin coating 
Polyurethane-Epoxy Anti-corrosion coating 

Paint 

                /P1 
                /P2 
                /P3 
                /P4 
                /P5 
                /P6 

      /P7 

  Light Blue (RAL # 5012) 

Orange (RAL # 2008) 
Red (

Munsell # 7.5 R4/14

Mint Green 
Silver (RAL # 9006) 
Yellow (RAL # 1018) 
Gray (RAL # 7046) 

Calibration 

     /ENG 

Engineering Unit Calibration (MLD Only) 

Stainless Steel Tag 

     /SST 

      
/SSW 

Stainless Steel tag screw attached to housing 
Stainless Steel tag wired to housing 

Stainless Steel Tag 

     /SSW 

Stainless Steel tag wired to housing 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.  PREFACE 

 
 

The Model MLD field mounted indicator receives a DC current signal from electronic transmitters and 
indicates process measurement values. This instruction manual gives instructions on handling, mounting, 
and wiring of the MLD indicator.  

 

2. MODEL CODE AND SPECIFICATIONS 

 
 

       STANDARD  SPECIFICATIONS 

 

 

Voltage  Drop:

   

1.8V typ., 2V max. 
 

Scale:

 

0- 1999  w / d ec i m al 
 

Accuracy:

  

± 0.05% of full scale (1999) ±1 count 
 

Operating  Temperature  Range:

   

-20 to 60°C 
 

Temperature drift:

  ±0.3 Count/°C  

 

Insulation Resistance:

  Between input  

terminals and case 100 Mohm at 500 V DC  
 

Dielectric Strength:

  Between input terminals  

and case: 1000 VAC for 1 minute.  
 

Mounting:

 Nominal 2” (50mm) pipe mount or  

surface. 
 

Explosion Protection Type:

 FM, CSA,  

EXPLOSIONPROOF CL1, DIV1, GROUPS 
A,B,C,D, DUST-IGNITIONPROOF CLII / III,  
GROUPS E,F,G 
 

Case and Cover:

  Die cast aluminum or 316  

Stainless Steel, baked polyurethane paint. Moss  
Green (Stainless Steel is unpainted); NEMA 4X 
 

Electrical  Connection:

  ½ x 14 NPT or        

M20 x 1.5 
 

Weight:

  2.7 lbs 

 
 

       ORDERING INSTRUCTIONS 
 

1. 

Model and Suffix codes.

 

2.

 

Option Codes

 

 

       Example Ordering Instructions: 

       MLD-A1/1/00/FF1/ENG/SST       Field Mounted Indicator (Digital), 4 to 20 mA DC, 2” Horizontal Pipe, FM Explosion Proof  
       0-200 InH2O    

           Scale in Engineering Units. Please specify Scale and Engineering units when ordering /ENG  

       FT-201 

 

           Specify Tag Number when ordering /SST or /SSW 

Summary of Contents for MLD

Page 1: ...IM 61A01A01 01E A 4th Edition User s Manual IM 61A01A01 01E A Model MLD Loop Powered Process Indicator ...

Page 2: ...s a DC current signal from electronic transmitters and indicates process measurement values This instruction manual gives instructions on handling mounting and wiring of the MLD indicator 2 MODEL CODE AND SPECIFICATIONS STANDARD SPECIFICATIONS Voltage Drop 1 8V typ 2V max Scale 0 1999 w decimal Accuracy 0 05 of full scale 1999 1 count Operating Temperature Range 20 to 60 C Temperature drift 0 3 Co...

Page 3: ...ng is a NEMA 4X Explosion Proof housing so it can be mounted outside in the field Do not install the unit in the following conditions Extreme Temperatures beyond the temperature rating of the instrument High vibration areas above the vibration rating of the instrument Extremely corrosive environments MOUNTING EXAMPLES ...

Page 4: ...an example of the MLD Loop Indicator connected to an EJA Pressure Transmitter Note The EJA Transmitter below can be replaced with any 4 20mA 2 wire device The Loop Indicator is available in FM Explosion Proof and CSA Explosion Proof types for hazardous locations Wire sealing is required for these approvals The following diagrams show some wire sealing examples For Flameproof type use Flameproof Pa...

Page 5: ...IM 61A01A01 01E A MOUNTING IN HAZARDOUS LOCATIONS ...

Page 6: ...eading 4mA Adjustment 20mA Adjustment Minimum 20mA Adjustment Maximum SW1 SW2 SW3 SW4 SW5 000 1200 1999 OFF OFF OFF OFF OFF 000 600 1200 ON OFF OFF OFF OFF 000 400 600 OFF OFF ON OFF OFF 000 200 400 ON ON ON OFF OFF 000 100 200 ON ON ON ON OFF 5 Set the Decimal value as follows a If tenths ex XXX X set SW8 on b If hundredths ex XX XX set SW7 on c If thousandths ex X XXX set SW6 on 6 The values to ...

Page 7: ... be the need for the customer to change the angle of the display The following are procedures for the display rotation Display Rotation 1 Remove power from the unit 2 Remove the glass cover from the display side 3 Remove the 2 screws holding the mounting plate to the standoffs 4 Rotate the display to the desired position can be rotated in 90 degree increments 5 Replace and tighten firmly the 2 scr...

Reviews: