YOKOGAWA JUXTA VJT6 Series User Manual Download Page 3

 CAUTION

 

Do not use output-2 for the isolated single-output 

type.

 

The power line and input/output signal lines should 

be installed away from noise-generating sources.  

Other wise accuracy cannot be guaranteed.

 

Make sure to earth ground the ground terminal 

through minimum resistance. The length and 

thickness of the grounding cable should be as 

short and thick as possible.  Directly connect the 

lead from the ground terminal (terminal no. 8) of 

the product to the ground.  Do not carry out daisy-

chained inter-ground terminal wiring.

 

The product is sensitive to static electricity; 

exercise care in operating it.  Before you operate 

the product, touch a nearby metal part to discharge 

static electricity.

 

If the ambient temperature is 50 °C or more, please 

use the cable that the rated temperature is 70 °C or 

more.

4.  RJC Sensor

 CAUTION

The product works normally when the RJC sensor 

“A1167HT” (see the figures below) is connected to the 

socket. If another RJC sensor is connected, it does not 

work normally. Make sure that the correct RJC sensor 

is connected referring to the figures below.

The RJC sensor for the product

(For the VJT6 with style of 3.00 

or higher)

The RJC sensor for the VJT6 with 

former style

“Not available for the VJT6 with 

style of 3.00 or higher”

Part number: A1167HT

Part number: E9786WA

  The style of VJT6 is indicated on the nameplate attached to 

the side face of the main unit.

5.  MAINTENANCE

The product starts running immediately when the power is turned 

on; however, it needs 10 to 15 minutes of warm-up before it 

meets the specified performance. 

5.1  Calibration Apparatus 

 • Calibrator (YOKOGAWA Meters & Instruments‘ CA150 or 

equivalent): 1

 • Temperature sensor (Yokogawa Meters & Instruments‘ 

B9108WA or equivalent): 1

 • Digital multimater (YOKOGAWA DM7560 or equivalent): 1 

 •

Precision resistor of 250 Ω ± 0.01%, 1 W 

5.2  Calibration Procedure 

1.  Connect the instruments as shown below.  First adjust the 

output-1 signal and then the output-2 signal. 

10

11

3 2 1

4

5

6

7

8

9

11

10

8

Temperature sensor (B9108WA)

1

3

+

2

5

R

-

+

7

9

R

Calibrator

R: 250 

 precision resistor

     for current output

Power supply

Output-2

Input

Output-1

L+

N- GND

Digital

multimater

-

+

Digital

multimater

2.  Use the calibrator and apply input signals equivalent to 0, 25, 

50, 75, and 100% of the input span to the product. 

3.  Check to see the corresponding output voltages are 0, 25, 50, 

75, and 100% respectively and within the specified accuracy 

rating.  “R” is used for current output. 

 • If the output signals are out of the accuracy rating range, 

adjust the output signal level using the zero and span 

adjustment volumes on front face of the product.

  

Zero-adjustment volume

Output-1

Span-adjustment volume

Zero-adjustment volume

Output-2

Span-adjustment volume

3

IM 77J01T06-01E

11th Edition