4.  DESCRIPTION OF FRONT PANEL AND 

CONNECTION OF HANDY TERMINAL 

4.1  Front Panel 

The communications connector in the front panel is used for 

setting up parameters through the Handy Terminal. The alarm-1 

and alarm-2 LEDs light up if an alarm occurs (those LEDs are 

provided only when the output-2 is specified for alarm output (the 

output-2 suffix code is T).)

Alarm indicator lamp

(for alarm 1)

Communication connector

Alarm indicator lamp

(for alarm 2)

4.2  Connector for Communication

Use the connector for communication when setting the 

parameters using a PC (VJ77 Parameters Setting Tool) or the 

Handy Terminal.

< How to connect with the setting tool>

JUXTA communication 

cable with  5-pin 

connector

Modular jack 

conversion

adapter

Dedicated adapter

Dedicated cable

<How to connect with the setting tool>

JUXTA

VJ Series

PC with the

VJ77 installed

JHT200

Handy Terminal

 • Use the VJ77 of version R2.02.01 or later.

 •

The modular jack conversion adapter does not come with the 

JHT200 Handy Terminal.  It is sold separately.

5.  SETTING PARAMETERS 

Set the parameters using a PC (VJ77 Parameter Setting Tool) or 

the Handy Terminal. Refer to “7. LIST OF PARAMETERS” in this 

manual and the User’s Manual for VJ77 PC-based Parameters 

Setting Tool (IM 77J01J77-01E) or the User’s Manual for JHT200 

Handy Terminal (IM 77J50H01-01EN).

5.1  Settings Related to Inputs and Outputs

5.1.1  Input Type 

  Set by selecting input type from among VOLTS (DC voltage) 

and CURRENT (DC current) in 

[D12: INP TYPE]

5.1.2  Input Range 

  Set the 0% value of input range to 

[D24: INPUT1 L_RNG]

 

and the 100% value of input range to 

[D25: INPUT1 H_RNG]

 

within the numerically specified range.

 NOTE

In case the input range is changed after factory-ship, 

the instrument may not work within the rated accuracy 

range depending on the changed input range. Perform 

the adjustment following the maintenance of this 

instruction manual after changing the input range.

5.1.3  Software Filter

  Set the software filter in 

[D57: S/W FILTER]

.

  OFF, LOW, MIDDLE, HIGH (default value: OFF)

  When LOW, MIDDLE, or HIGH is selected, a first-order filter 

equivalent to 100 ms, 300 ms, or 1 s is inserted in the input.

5.1.4  Direction of Output Action

  Analog output signals can be reversed. To reverse the signal 

from output-1, set 

[D50: OUT1 DR]

 to REVERSE.  For 

output-2, set 

[D51 OUT2 DR]

 to REVERSE.  To return the 

output-1 signal to normal, set 

[D50: OUT1 DR]

 to DIRECT.  

For output-2, set 

[D51: OUT2 DR]

 to DIRECT.

5.1.5 

External Input Resistance Correction

 

For current input, set the external resistance to 

[D13: IN 

RESIST]

. There is a difference between this value and the 

actual external resistance. If this difference causes an error, 

the input can be corrected.

  To perform correction, wire as shown in the figure below, apply 

a stable input equivalent to 100%, and set 

[P40:RESISTOR 

ADJ]

 to EXECUTE.

  If you need perform correction again such as when the 

external resistance is changed, reset the correct value. To do 

so, set 

[P40: RESISTOR ADJ]

 to RESET.

  

A current 

generator

VJH7

R

External resistor

R

1

3

5.2  Settings Related to Communication 

Function 

Set the following parameters when output-2 is specified 

for communication function. For more information on the 

communication function, see the Instruction Manual for VJ Series 

Communication Function (IM 77J1J11-01E). 

5.2.1  Communication Protocol 

  Set the communication protocol by selecting from among PC-

LINK, PC-LINK WITH SUM, MODBUS ASCII, MODBUS RTU, 

and LADDER in 

[F01: PROTOCOL]

5.2.2  Communication Address 

  Set the address number of the isolator numerically in a range 

of 1 to 99 in 

[F02: ADDRESS]

5.2.3  Baud Rate 

  Set the baud rate by selecting from among 1200, 2400, 4800, 

9600, 19200 and 38400 bps in 

[F03: BAUD RATE]

.

5.2.4  Parity 

  Select and set NONE, EVEN, or ODD in 

[F04: PARITY]

5.2.5  Data Length 

  Select and set 7 bits or 8 bits in 

[F05: DATA LEN]

5.2.6  Stop Bit 

  Select and set 1 bit or 2 bits in 

[F06: STOP BIT]

5.2.7  Input Decimal Point Position

  Number of digits of decimal places (setting of D register 

[D0003]) can be set. 

Select and set among 0 to 5 digits in 

[F07: INPUT DEC PT]

.

5.3  Settings Related to Alarm Output 

Set the following parameters when output-2 is specified for alarm 

output. 

5.3.1  Alarm Setpoints 

  Set the alarm setpoints of alarm-1 and alarm-2 in 

[E03: SET 

POINT1]

 and 

[E04: SET POINT2]

 numerically. 

 •

Setting range: A range of 0 to 100% of input range 

 •

Setting resolution: 0.1% 

5.3.2  Direction of Alarm Action 

  Select the direction of alarm-1 action and that of alarm-2 

action from among HIGH ALM (high-limit alarm) and LOW 

ALM (low-limit alarm) and set each in 

[E05: ALM1 ACTION]

 

(direction of alarm-1 action) or 

[E06: ALM2 ACTION]

 

(direction of alarm-2 action). 

 •

To activate alarm status when input signal ≥ alarm setpoint, 

select HIGH ALM. 

 •

To activate alarm status when input signal ≤ alarm setpoint, 

select LOW ALM. 

3

IM 77J01H07-01E

5th Edition