A5-1
IM 34M06C11-01E
A5.
Maintenance and Inspection
A5.1
Replacing Modules
Spare Modules
Always have spare modules on hand for immediate countermeasures against failures in
the FA-M3.
Procedure for Replacing a Module
Be sure to turn off the power before replacing any module. When replacing a module,
do not change the type and location of the module.
Module replacement
Turn off power of unit
Replace
module
Turn on power
End
FA050101.VSD
Figure A5.1 Module Replacement Procedure
Note the module replacement
Perform the following checks before replacing a module when there is an error:
- Check whether the load conforms to the specifications.
- Check whether the surge protector, if any, is functioning normally.
- Check for cabling errors such as wrong polarity orientation of a diode.
Note
The FA-M3 will fail again after replacing any module when there is a problem with the
external wiring, no surge protector is installed or a diode is connected in the reverse
polarity. Be sure to solve problems with the external equipment before replacing the
module.
Summary of Contents for FA-M3V e-RT3 Plus
Page 2: ...Blank Page ...
Page 14: ...Blank Page ...
Page 20: ...Blank Page ...
Page 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Page 22: ...Blank Page ...
Page 34: ...Blank Page ...
Page 160: ...Blank Page ...
Page 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Page 220: ...Blank Page ...
Page 232: ...Blank Page ...
Page 242: ...Blank Page ...
Page 252: ...Blank Page ...
Page 254: ...Blank Page ...
Page 268: ...Blank Page ...
Page 274: ...Blank Page ...