5. Display and Push Buttons
The EJA564E has a high contrast display for optimal readout. The menu is controlled by 3 push buttons.
Navigate with the up and down through menus and measuring values.
Enter a menu and confirm selections with the menu button.
Display EJA564E
5.1
Display Readout
When the transmitter is powered, a startup screen with the software version and the pressure range appears for
a few seconds. After the startup screen the transmitter will automatically continue to the main screen with the
actual measurement reading.
5.2
Summary Programming Points
PROGRAM POINT
NAME
FUNCTION
P100
Menu-Exit menu
Start and exit
P101
ZERO value
Zero adjustment (ZERO 4 mA) with or without test pressure
P102
SPAN value
Span adjustment (SPAN 20 mA) with or without test pressure
P103
MOUNT correction
Cancel mounting position effect
P104
UNITS
Selection of engineering units
P105
REVERSE mA
Output selection: 4-20 mA or 20-4 mA
P106
DAMPING
Adjustable damping: 0.00 to 25.00 seconds
P107
TEMP UNITS
Temperature unit selection: Celsius or Fahrenheit
P108
DEVICE SETUP
Configuration: Protection, HART, Display mode, Display update
P109
READOUT
Readout options on display: Current, Unit, percentage and temperature
P110
BURST MODE
Continuously broadcast a standard HART reply message
Push the up button to browse through various menus
and adjusting values.
Push the down button to browse through various
menus and adjusting values.
Push the menu button to enter menus or confirm a
selection.