IM 01C22T01-01E
2-12
2. HART COMMUNICATOR OPERATION
(10) Unit for Displayed Temperature
When the instrument is shipped, the temperature units
are set to
C
(Centigrade). Follow the procedure below
to change this setting.
The unit changed here corresponds the unit for
Snsr
temp
.
F0225.EPS
(ENTER)
EJA:
Snsr temp unit
C
C
F
HELP
SEND
ESC
ENTER
Select F (Fahrenheit), and Press
ENTER (F4).
1. Device setup
4. Detailed setup
1. Sensors
2. Temp sensor
2. Snsr temp unit
Example: Change the unit for the temperature display.
(11) Unit for Displayed Static Pressure
Follow the procedure to change the static pressure unit.
Changing this parameter also changes the unit for the
static pressure display.
F0226.EPS
(ENTER)
EJA:
Static Pres unit
mmH2O
mmH2O
mmHg
psi
bar
HELP
SEND
ESC
ENTER
Select kPa and Press ENTER (F4).
Select SEND (F2) to send the data.
(SEND)
1. Device setup
4. Detailed setup
1. Sensors
3. Static Pres sensor
2. Static Pres unit
Example: Change the static pressure unit from mmH
2
O to
kPa.
inH
2
O
inHg
ftH
2
O
mmH
2
O
mmHg
psi
bar
mbar
g/cm
2
kg/cm
2
Pa
kPa
torr
atm
(12) Test Output
This feature can be used to output a fixed current from
3.2 mA (–5%) to 21.6 mA (110%) for loop checks.
1
F0227.EPS
Set the control loop in manual
mode, and press OK (F4).
EJA:
WARN-loop should be
removed from
automatic control
DEL
SET
ABORT
OK
EJA:
Choose analog output
level
1 4mA
2 20mA
3 Other
4 End
DEL
SET
ABORT
ENTER
2
Select Other, and press ENTER
(F4).
Supplementary explanation.
1. 4 mA:
Outputs a 4 mA current signal
2. 20 mA:
Outputs a 20 mA current signal
3. Other:
Sets a desired output using the
alphanumeric keys
4. End: Exits
EJA:
Output
4.000
HELP
DEL
ABORT
ENTER
3
Enter 12, and press ENTER (F4).
A fixed current of 12 mA is output.
EJA:
Fld dev output is
fixed at 12.000 mA
DEL
ABORT
4
Press OK (F4).
HELP
SEND
OK
×
2
(ENTER)
×
3
(ENTER)
(ENTER)
(OK)
(OK)
‘1 2’
(OK)
EJA:
Choose analog output
level
1 4mA
2 20mA
3 Other
4 End
DEL
ABORT
5
To finish the loop test, select End,
and press ENTER (F4).
HELP
SEND
ENTER
EJA:
NOTE-loop may be
returned to automatic
control
DEL
ESC
6
Press OK (F4).
HELP
SEND
OK
Example: To output 12 mA (50%)
1. Device setup
2. Diag/Service
2. Loop test