1-39
IM 04L42B01-01E
Overview of Functions
1
2
3
4
5
6
7
8
9
10
11
12
13
App
Index
1.6 Event Action and Remote Control Functions
(/R1 and /PM1 Options)
A specified action is carried out when an event occurs. This function is called
event
action
. The remote control function (/R1 and /PM1 options) allows you to specify actions
to be performed when the terminal receives a contact input or an open collector signal.
The remote control function is configured using the event action function.
For the setting procedure, see section 7.1.
Events
• Events
Select from the following events.
Event
Level/Edge
*1
Description
Remote
Level/Edge
ON/OFF of the remote control input.
Output relay
Level/Edge
Activated/Deactivated condition of the alarm output
relay.
Relay-Off
*3
Internal switch
Level/Edge
The value, 0 (off) or 1 (on), of the internal switch.
Switch-Off
*3
Timer
Edge
Timer timeout.
Match time timer
Edge
When the time matches.
Alarm
Level/Edge
The state in which any alarm is occurring and the state
in which no alarm is occurring.
Alarm-Off
*3
USER key
Edge
The operation of pressing the USER key.
Event edge switch
*2
Edge
Can be caused by:
• The Edge Switch soft key in the FUNC key menu.
• A dedicated communication command or Modbus
communication.
• The custom display
Event level switch
*2
Level
You can view the status of the switch in the event level
switch status display. Can be caused by:
EventLevelSwitch-
Off
*3
• A dedicated communication command or Modbus
communication.
• The custom display.
*1 For a description of level and edge, see “Miscellaneous” in this section.
*2 This function is available for release numbers 3 and later.
*3 This function is available for release numbers 4 and later.
• Output Relay, Internal Switch, Alarm, Event Level Switch
The output relay, internal switch, alarm, and event level switch have two states, state
A and state B, which are explained in the table below. In explanations, “Output relay”
and similar states are referred to as “ON events,” and “Relay-Off” and similar states
are referred to as “OFF events.”
Event
State A
State B
Output relay
Deactivated
Activated
Internal switch
OFF
ON
Alarm
No alarms
At least one alarm
Event level switch
OFF
ON
When Edge Is Selected
An ON event occurs when state A changes to state B. An OFF event occurs when
state B changes to state A.
When Level Is Selected
If the action states that correspond to states A and B during an ON event are called
“state 2” and “state 1,” respectively, the action states that correspond to states A and
B during an OFF event will be state 1 and state 2, respectively.
See “Miscellaneous” and “Level and Edge” in this section.
Summary of Contents for Daqstation DX2000
Page 2: ......
Page 98: ...Blank...
Page 132: ...Blank...
Page 224: ...Blank...
Page 292: ...Blank...
Page 324: ...Blank...
Page 348: ...13 24 IM 04L42B01 01E 13 7 External Dimensions See the DX2000 Operation Guide IM04L42B01 02E...
Page 366: ...Blank...