IM 04L4B0-8E
In Case of CompactLogix, etc.
• Command: CIP Data Table Read/Write
The DX supports the following commands:
Target PLC
Command name
CompactLogix, etc.
CIP Data Table Read/Write
• Specifying data to be accessed
Specify which of the data in the DX should be accessed. For Logix, data can be
accessed by a "tag name".
For an external input channel, separate access destinations are used for reading and
writing.
Data to be accessed
Tag name
Type
Number
Data type
INT16
Data type
INT32
Data type
FLOAT
Measurement
channel
int[000]
int[000]
real[000]
2
int[00]
dint[00]
real[00]
• • •
• • •
• • •
• • •
47
int[1046]
dint[1046]
real[1046]
48
int[047]
dint[047]
real[047]
Computation
channel
0
int[2000]
dint[2000]
real[2000]
02
int[200]
dint[200]
real[200]
• • •
• • •
• • •
• • •
159
int[2058]
dint[2058]
real[2058]
160
int[2059]
dint[2059]
real[2059]
Communication
input data
C01
int[000]
dint[000]
real[000]
C02
int[00]
dint[00]
real[00]
• • •
• • •
• • •
• • •
C59
int[3058]
dint[3058]
real[3058]
C60
int[3059]
dint[3059]
real[3059]
External input
channel
(for writing)
20
int[4000]
dint[4000]
real[4000]
202
int[400]
dint[400]
real[400]
• • •
• • •
• • •
• • •
49
int[428]
dint[428]
real[428]
440
int[429]
dint[429]
real[429]
External input
channel
(for reading)
20
int[4500]
dint[4500]
real[4500]
202
int[4501]
dint[4501]
real[4501]
• • •
• • •
• • •
• • •
49
int[478]
dint[478]
real[478]
440
int[479]
dint[479]
real[479]
"• • •" stands for data in numerical order.
Explicit Message