background image

  

Correct

Conductor

Primary current

Incorrect

Using an magnetic

-shielded conductor

Using two parallel 

conductors

Current flows in 

both directions

Direction of current

Figure 3.  Insertion of a Conductor

4. 

Check that power is being supplied to the instrument, and then apply the primary current.

5. 

Read the measured values. The following calculation is used to determine the current flowing 

through the primary conductor.

 

Example: When the output current from the instrument's secondary connector (pin 6) is 100 mA.

 

 

CT2000A: 100 mA x 2000 = 200 A

Note

•  If the operation status LED is off even when power is being supplied to the instrument, the 

protection function may be activated. Immediately stop the primary current.

•  Only pass conductors through the primary conductor feed-through hole if the current that you 

want to measure is flowing through the conductors and their current directions are the same. 

Correct measurements cannot be taken if you pass conductors with magnetic shielding or 

conductors whose current directions are opposite of each other through the feed-through hole.

•  Make sure the primary wiring and secondary wiring do not interfere with each other. The 

secondary wiring may be affected by the primary wiring because it uses a very small current. 

Make the secondary wiring as short as possible and maintain its distance from the primary 

wiring, without allowing them to be parallel to each other. We recommend AWG24 or higher for 

the secondary wiring material. Twisted-pair may be better than shielded cable for measurement 

applications such as inverters.

 

The instrument outputs current. Connect the instrument to a measuring instrument with 

current input. To connect the instrument to a measuring instrument with voltage input, use an 

appropriate shunt resistor to connect the instrument to the voltage input terminals.

 

Configure your setup so that the load resistance of the measuring instrument connected to the 

secondary signal output is within the specification range.

 

Correct measurements may not be possible in places where there is an extremely strong 

external magnetic field besides the magnetic fields produced by the primary current of the 

object to be measured or where there is a strong electric field.

Power Off If Abnormal Behavior Occurs

  If you notice smoke or unusual odors coming from the instrument, immediately turn off the 

measuring instrument supplying the power. Then, contact your nearest YOKOGAWA dealer.

Status circuit diagram

  

Active Low Output

Operation status

I

CEmax

 : 30 mA

I

CEmin

 : 2 mA

Collector

DC

Power

Supply

R

3

8

+

-

V

+ : 4..+24 V

R

min

(kΩ) =

R

max

(kΩ) =

V

+(V) - 0.4 V

30 mA

V

+(V) - 0.4 V

2 mA

D-Sub

(9 pin)

Emitter

CT2000A

USER SIDE

Photocoupler operation:

ON :   CT2000A is OK

 

(normal mode)

OFF :   CT2000A is not OK

  Operation status output

Status 

Operation Status (8-pin) Output Note

Normal 

Less than 0.7 V 

The LED turns on.

Overloaded  V+

The LED turns off. A low frequency signal is output 

as a secondary signal output.

Overload Protection

  The overload occurs when the primary current Ip exceeds a trip level such that the fluxgate detector 

becomes completely saturated and, consequently, the current sensor will switch from normal 

operation to overload mode.

  This trip level is guaranteed to be greater than Ipm (3000Apeak) and its actual value depends on 

operating conditions such as temperatures and measuring resistance.

  During the overload mode, the current sensor generates and outputs a low frequency signal.

  The measuring operation resumes when the primary current returns in the measuring range 

between –Ipn and +Ipn (2000Arms).

Test Winding Connector

  The test winding connector is used to test the operation of the current sensor.

  When a current is applied between the positive and negative Ip test pins, a current that corresponds 

to the test current winding number of 200 and current transformation ratio of 2000:1 is output from 

the secondary signal output pin.

  Example:  When 1 A is applied between the positive and negative Ip pins, 100 mA is output from the 

secondary signal output pin.

Note

To measure the current of the primary conductor that has been passed through the through hole, 

do not connect anything to the test winding Ip+ or Ip- pin. If connected, errors may be induced in 

the sensor output.

5. Specifications

Item

Specification

Current Rating

DC: 0 to 2000 A

AC: 3000 Apeak

Output Current

Primary rated current at 2000 A is 1A.

Current Transformation Ratio

2000:1

Direction of Current

Per the arrow printed on the main unit.

Accuracy

DC: ±(0.05% of 30 μA)

50/60 Hz: ±(0.05% of 30 μA) sine wave

Standard Conditions

 

Voltage to earth: 0V

 

Conductor position: center

 

Conductor: φ25 mm; length,300 mm or more; straight

Accuracy warranty period

12 months

Effect of Position of Conductor

Add ±(0.01% of reading)

Measurement Band (-3dB)

DC to 40 kHz 

Temperature Coefficient

In the -40 to 18°C, 28 to 85°C ranges: 0.01%/°C

Max. Allowable Continuous Input 3000 Apeak

Derating of Max. Allowable Input For the maximum allowable continuous current with respect to 

frequency, see figure 4.

Instantaneous Max. Allowable Input

(0.1 sec. or less, reference value)

10000 Apeak

Maximum Rated Voltage

1000 Vrms, CAT III

Load Resistance

0 to 1Ω(power supply voltage: ±14.25 V, 25°C)

Operating 

environment

Temperature

-40 to 85°C

Humidity

20 to 80%RH (no condensation)

Altitude

2000 m or less

IM CT2000A-01EN 2/2

Storage 

environment

Temperature

-40 to 85°C

Humidity

 20 to 80% RH (No condensation)

Altitude

2000 m or less

External Dimensions

Approx. 230.5(W) x 219.5(H) x 75.5(D) mm

(excluding the connector,  conductor guide, and protrusions)

Diameter of Primary Current Hole

φ70 mm

Secondary Connector

D-Sub 9 pin

Test Wiring Connector

M8 circular 3 pin

Test current: 1 A max.

Number of test windings: 200

Weight

Approx. 4.2 kg.

Power Supply Voltage

±(15 V ± 5%)

Maximum Rated Power Consumption Approx. 35 VA

Current Consumption (at Power 

Supply Voltage)

Approx. (225 mA + output current)

Recommended fastening torque

•Flat mounting

M6×4 steel screws 5.5 Nm

M6×4 steel screws 5.5 Nm

•Straight mounting

Safety standard

1

Compliant standards

  EN61010-1  1000 Vrms

  Measurement Category: CAT III

2

  Pollution degree 2

3

Emissions

1

Compliant standards

  EN61326-1 ClassB, EN55011 ClassB, Group1

Immunity

1

Compliant standards

  EN61326-1 Table 2 (for industrial locations)

Environmental standards

1

EU RoHS Directive compliant

1  Applies to products with CE marks. For information on other products, contact your nearest YOKOGAWA dealer.

2  This instrument is measurement category III product. Do not use it for Measurement Categories IV.

  Measurement category O applies to measurement of other circuits that are not directly connected to a main power 

supply.

  Measurement category II applies to electrical equipment that is powered through a fixed installation, such as a 

wall outlet wired to a distribution board, and to measurement performed on such wiring.

  Measurement category III applies to measurement of facility circuits, such as distribution boards and circuit 

breakers.

  Measurement category IV applies to measurement of power source circuits, such as entrance cables to buildings 

and cable systems, for lowvoltage installations.

3  Pollution Degree applies to the degree of adhesion of a solid, liquid, or gas which deteriorates withstand voltage or 

surface resistivity. Pollution degree 2 applies to normal indoor atmospheres (with only non-conductive pollution).

Figure 4.  Derating of Primary Current by Frequency

Frequency [Hz]

Maximum 

Allowable Input Current [Arms]

1

10

100

1000

10000

1

10

100

1000

10000

100000

23°C

85°C

190.5

145

45.3

153

204

230.5

65

69.5

75.5

219.5

Φ70

+1

0

4-Φ7x9 hole

20

124.3

1.4

(2)

31
26

68.5

204

4-Φ7x9 hole

(2)

3.5

Figure 5.  External Dimensions

Unless otherwise specified, tolerances are 

±

3% (however, tolerances are 

±

0.3 mm when below 10 mm).

Unit: mm

6.   Servicing

If you encounter any problems during use, or if the instrument does not appear to be operating 

normally,  contact your nearest YOKOGAWA dealer.

7. Warranty

If you experience a breakdown in the instrument due to faulty manufacturing or accidents during 

shipping,  contact your nearest YOKOGAWA dealer.

8. Appendix
  Waste Electrical and Electronic Equipment (WEEE), Directive

 

(This directive is valid only in the EU.)

 

This product complies with the WEEE Directive marking requirement. This marking 

indicates that you must not discard this electrical/electronic product in domestic 

household waste.

 

Product Category

 

With reference to the equipment types in the WEEE directive, this product is classified 

as a “Monitoring and Control instruments” product.

 

When disposing products in the EU, contact your local Yokogawa office in Europe. Do 

not dispose in domestic household waste.

  Authorized Representative in the EEA

  Yokogawa Europe B. V. is Authorized Representative of Yokogawa Test & Measurement Corporation 

in the EEA for this Product. To contact Yokogawa Europe B. V., see the separate list of worldwide 

contacts, PIM 113-01Z2.

  Disposing of the Instrument

  When disposing of the instrument, follow the laws and ordinances of your country or region.

Reviews: