YOKOGAWA ADMAG AXG4A User Manual Download Page 8

IM 01E21A21-02EN

 

<2. Safety Instrumented Systems Installation>

6

2.2.6   Proof Test

A proof test is a periodic test to verify that the Safety Instrumented Function work without fails.

It is mandatory to have a proof test in order to detect any failure which is not detected by the diagnostic of the 

product, which prevents any action of the Safety Instrumented Function (SIF) from its intention.

The frequency of the proof tests (or the proof test interval) is to be determined in the reliability calculations for 

the SIFs for which this product is applied. The actual proof tests must be carried out “more frequently” or “as 

frequently as specified” in the calculation in order to preserve required safety integrity of the SIF.

Proof test results are required to be documented. And this documentation should be a part of the plant safety 

management system. Failures that are detected should be reported to YOKOGAWA.

The personnel carrying out the proof test of products should be trained in SIS operations including bypass 

procedures, maintenance of this product, and company management of change procedures.

Disable the write protect function before proof test. After the proof test, enable the write protect function.

Table 2.2.5  Abbreviated Proof Test

Testing method

Tool required

Expected outcome

Remarks

Loop test for “Analog output”

1.   Bypass the safety PLC or take other 

appropriate action to avoid a false trip.

2.   Make a note of the “AO1 alarm out” when the 

proof test is carrying out.

3.   After setting the “AO1 alarm out” to “>21.6 mA” 

via BRAIN or HART communication, actually 

generate an alarm and verify that the current 

value is above 21.6 mA.

4.   After setting the “AO1 alarm out” to “<2.4 mA” 

via BRAIN or HART communication, actually 

generate an alarm and verify that the current 

value is less than 2.4 mA.

5.   Clear the all alarm.

6.   Return the setting of “AO1 Alarm out” to the 

value you noted in Step 2.

7.   Remove the bypass and otherwise restore 

normal operation.

For BRAIN:

BRAIN 

configuration tool

For HART:

HART 

configuration tool

Proof Test Coverage;

ADMAG TI Multi (Non-IS) 

Option = 68.6%

ADMAG TI IS Option = 

69.5%

The output 

needs to be 

monitored to 

assure that 

this product 

communicates 

the correct signal

Table 2.2.6  Extended Proof Test

Testing method

Tool required

Expected outcome

Remarks

Loop test for “Analog output”

1.   Bypass the safety PLC or take other 

appropriate action to avoid a false trip.

2.   Make a note of the “AO1 alarm out” when the 

proof test is carrying out.

3.   After setting the “AO1 alarm out” to “>21.6 mA” 

via BRAIN or HART communication, actually 

generate an alarm and verify that the current 

value is above 21.6 mA.

4.   After setting the “AO1 alarm out” to “<2.4 mA” 

via BRAIN or HART communication, actually 

generate an alarm and verify that the current 

value is less than 2.4 mA.

5.   Clear the all alarm.

6.   Return the setting of “AO1 Alarm out” to the 

value you noted in Step 2.

7.   Perform a two-point calibration in the 

maximum and minimum flow ranges.

8.   Check current output when there is no flow in 

the meter.

9.   Check current output when there is typical flow 

in the meter.

10.  Remove the bypass and otherwise restore 

normal operation.

For BRAIN:

BRAIN 

configuration tool

For HART:

HART 

configuration tool

Proof Test Coverage;

ADMAG TI Multi (Non-IS) 

Option = 83.0%

ADMAG TI IS Option = 

83.7%

The output 

needs to be 

monitored to 

assure that 

this product 

communicates 

the correct signal

Summary of Contents for ADMAG AXG4A

Page 1: ...ADMAG TI Series AXG AXW Magnetic Flowmeter Safety Manual IM 01E21A21 02EN 2nd Edition IM 01E21A21 02EN AXG AXW Magnetic Flowmeter User s Manual ...

Page 2: ...e 4 2 2 Using this product for an SIS Application 4 2 2 1 Safety Function 4 2 2 2 Safety Accuracy 4 2 2 3 Diagnostic Response Time 4 2 2 4 Setup 5 2 2 5 Required Parameter Setting 5 2 2 6 Proof Test 6 2 2 7 Repair and Replacement 8 2 2 8 Startup Time 8 2 2 9 Firmware Update 8 2 2 10 Reliability Data 8 2 2 11 Lifetime Limits 8 2 2 12 Environmental Limits 8 2 2 13 Application Limits 8 2 3 Definition...

Page 3: ...First Optional Code EC IM 01E21A11 01EN ADMAG TI Series AXG AXW Magnetic Flowmeter Read Me First IM 01E21A21 01Z1 ADMAG TI Series AXG AXW Magnetic Flowmeter Safely Manual IM 01E21A21 02EN this manual ADMAG TI Series AXG AXW Magnetic Flowmeter BRAIN Communication Type IM 01E21A02 01EN ADMAG TI Series AXG AXW Magnetic Flowmeter HART Communication Type IM 01E21A02 02EN AXG AXG4A AX01C ADMAG TI Series...

Page 4: ...0 400 For AXW 025 032 040 050 065 080 100 125 150 200 250 300 350 400 For AXW G or AXW W 500 600 700 800 900 10L Precautions Related to the Protection Safety and Alteration of the Product The following safety symbol marks are used in this manual and product WARNING A WARNING sign denotes a hazard It calls attention to procedure practice condition or the like which if not correctly performed or adh...

Page 5: ... any question arises or errors are found or if any information is missing from this manual inform the nearest YOKOGAWA sales office The specifications covered by this manual are limited to those for the standard type under the specified model number break down and do not cover custom made products Note that changes in the specifications construction or component parts of the product may not immedi...

Page 6: ...ety Function This product is used as a Type B of Low demand mode in the SIS application F Safety PLC Measuring Device Actuator F0201 ai This product converts Flow velocity Volume flow Mass flow and Flow noise for AXG only to current And it outputs Analog Output 1 at I O 1 terminal as its safety functions Other functions display etc are out of its scope Use this Analog Output 1 to connect the safet...

Page 7: ...t fail when this product is detected its alarm BRAIN H30 DENSITY SEL HART Menu Path Device root menu Detailed setup Process variables Density Density value select Set this parameter as Fixed value when the Analog Output 1 is used for mass flow measurement BRAIN P22 NEW PASSWORD HART Menu Path Device root menu Detailed setup Protection New password Set a password of 8 characters no lowercase letter...

Page 8: ...rm and verify that the current value is above 21 6 mA 4 After setting the AO1 alarm out to 2 4 mA via BRAIN or HART communication actually generate an alarm and verify that the current value is less than 2 4 mA 5 Clear the all alarm 6 Return the setting of AO1 Alarm out to the value you noted in Step 2 7 Remove the bypass and otherwise restore normal operation For BRAIN BRAIN configuration tool Fo...

Page 9: ...Menu Path Device root menu Detailed setup Process variables PV flow select Select Mass above menu An alarm which was set at Analog Output 1 is generated and appeared at the result of above work 2 Set parameters through BRAIN or HART communication protocol in order to generate an alarm at Analog Output 1 by making a condition of scale out at its low limit side of current value BRAIN G04 AO1 ALM OUT...

Page 10: ...PFDavg calculation of the entire safety instrumentation function according to the SIL to be applied is required When using the transmitter of this flowmeter in a redundant configuration the use of a common cause factor β factor of 5 is suggested If the owner operator of the plant would institute common cause failure training and more detailed maintenance procedures for avoiding common cause failur...

Page 11: ...onstration for each phase of the life cycle that the output deliverables of the phase meet the objectives and requirements specified by the inputs to the phase The verification is usually executed by analysis and or testing Validation The demonstration that the safety related system s or the combination of safety related system s and external risk reduction facilities meet in all respects the Safe...

Page 12: ...ual No IM 01E21A21 02EN Edition Date Page Revised Item 1st June 2017 New publication 2nd Feb 2022 1 2 5 6 8 Revise Table 1 1 Document title and No Add IMPORTANT 2 2 5 Add and Revise the explanation 2 2 6 Add and Revise the explanation 2 2 7 2 2 10 and 2 2 11 Add and Revise the explanation Delete SIL declaration and FMEDA report ...

Reviews: