Electrical Connections
1. Remove the handle at the right side plate of the outdoor unit (one screw).
2. Open the cable clamp, then connect the power cables to the terminals. Make sure each wire is securely connected. Make
sure the wiring matches on both the terminals of the outdoor unit, and the indoor unit on the terminals. Do not cross wire.
(See wiring diagrams below)
3. Secure the power connection wire using the wire clamp.
4. Ensure wire has been firmly attached will.
5. Reinstall the handle.
Including an air switch with suitable capacity, please note the following table. Air switch should be included magnet buckle and
heating buckle function, it can protect the circuit-short and overload. (Caution: please do not use the fuse only for protect the
circuit)
Air-conditioner
Circuit Breaker Size
WMMS-30CH-V2B(59)5
20A
WMMS-36CH-V2B(59)5
25A
WMMS-42CH-V2B(59)5
35A
WMMS-48CH-V2B(59)5
45A
WMMS-60CH-V2B(59)5
45A