u
Three-Phase 400 V Class Drive Models 4A0361 to 4A0590
Table A.6 Power Ratings Continued (Three-Phase 400 V Class)
Item
Specification
CIMR-Z
o
4A
0361
0414
0480
0590
Maximum
Applicable
Motor
Capacity
Input Voltage
460 V or higher
HP
300
350
400
500
kW
220
260
300
370
Input Voltage
lower than 460 V
HP
250
300
340
400
kW
185
220
250
300
Input
Input Current (A)
361
414
480
590
Rated Voltage
Rated Frequency
Three-phase 380 to 480 Vac 50/60 Hz / 510 to 680 Vdc
Allowable Voltage Fluctuation
-15 to 10%
Allowable Frequency Fluctuation
±5%
Minimum Power Supply Capacity (kVA)
316
375
400
491
Output
Rated Output Capacity (kVA)
Input Voltage
460 V or higher
276
316
382
470
Input Voltage
lower than 460 V
250
287
333
409
Rated Output Current (A)
362
414
480
590
Overload Tolerance
110% of rated output current for 60 s
140% of rated output current for 0.5 s
Carrier Frequency
User adjustable between 1 and 5 kHz
(Maximum Frequency varies with Rated Output Capacity)
Maximum Output Voltage (V)
Three-phase 380 to 480 V (proportional to input voltage)
Maximum Output Frequency (Hz)
240 Hz
Harmonics
Reduction
DC Link Choke
Built-in
EMC
Filter (IEC/EN 61800-3 Category 2)
External
connections, and power supply impedance.
<4> Rated motor capacity is calculated with a rated output voltage of 460 V.
<5> Rated motor capacity is calculated with a rated output voltage of 400 V.
<6> Carrier frequency is set to 2 kHz. Current derating is required to raise the carrier frequency.
A.1 Power Ratings
YASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual
273
A
Specifications
Summary of Contents for Z1000 CIMR-ZU*A Series
Page 399: ......