HOA Keypad Display
Fault Name
CPF00 or CPF01
Control Circuit Error
Cause
Possible Solution
There is a self-diagnostic error in the control
circuit
• Cycle power to the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a
Yaskawa representative for instructions on replacing the control board.
Connector on the operator is damaged
Replace the operator.
HOA Keypad Display
Fault Name
CPF02
A/D Conversion Error
An A/D conversion error or control circuit error occurred.
Cause
Possible Solution
Control circuit is damaged
• Cycle power to the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a
Yaskawa representative for instructions on replacing the control board.
HOA Keypad Display
Fault Name
CPF03
Control Board Connection Error
Connection error between the control board and the drive
Cause
Possible Solution
There is a connection error
• Turn off the power and check the connection between the control board and the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a
Yaskawa representative for instructions on replacing the control board.
Drive fails to operate properly due to noise
interference
• Check the various options available to minimize the effects of noise.
• Counteract noise in the control circuit, main circuit, and ground wiring.
• Use only recommended cables or other shielded line. Ground the shield on the controller side or
the drive input power side.
• Ensure that other equipment such as switches or relays do not cause noise. Use surge suppressors
if required.
• Separate all communication wiring from drive power lines.
HOA Keypad Display
Fault Name
CPF06
EEPROM Memory Data Error
Error in the data saved to EEPROM
Cause
Possible Solution
There is an error in EEPROM control circuit
• Turn off the power and check the connection between the control board and the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a
Yaskawa representative for instructions on replacing the control board.
The power supply was switched off while
parameters were being saved to the drive
Reinitialize the drive using parameter A1-03.
HOA Keypad Display
Fault Name
CPF07
Terminal Board Connection Error
CPF08
Cause
Possible Solution
There is a faulty connection between the terminal
board and the control board
• Turn off the power and check the connection between the control board and the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a
Yaskawa representative for instructions on replacing the control board.
HOA Keypad Display
Fault Name
CPF20 or CPF21
Control Circuit Error
Cause
Possible Solution
Hardware is damaged
• Cycle power to the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a
Yaskawa representative for instructions on replacing the control board.
5.4 Fault Detection
208
YASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual