3.5 Control Circuit Wiring
u
Control Circuit Connection Diagram
when wiring terminals on the Z1000 Bypass and drive control circuits.
u
Control Circuit Terminal Block Functions
WARNING! Sudden Movement Hazard. Always check the operation and wiring of control circuits after being wired. Operating a Z1000
Bypass with untested control circuits could result in death or serious injury.
WARNING! Sudden Movement Hazard. Confirm the drive I/O signals and external sequence before starting test run. Setting parameter
Z1-01 may change the I/O terminal function automatically from the default setting.
Refer to Application Selection on page 108
. Failure
to comply may result in death or serious injury.
The functions of the control circuit terminals are shown in
.
The control circuit terminals on Terminal Board A2 are arranged as shown in
12. SHIELD
11. SHIELD
10. IG24
9. IG24
8. DI-8
7. DI-7
6. DI-6
5. DI-5
4. DI-4
3. DI-3
2. DI-2
1. DI-1
TB2
TB3
4. SHIELD
3. TXRX-
2. TXRX+
1. IG5
TB1
12. DO-10 NO
11. DO-10 C
10. DO-10 NC
9. DO-9 NO
8. DO-9 C
7. DO-9 NC
6. DO-8 NO
5. DO-8 C
4. DO-8 NC
3. DO-7 NO
2. DO-7 C
1. DO-7 NC
Figure 3.19 Control Circuit Terminal Board A2 Arrangement
Table 3.7 Z1000 Bypass Control Circuit Terminal Board A2
Type
Signal Name
Description
Specification
Digital Inputs
DI-1
Digital Input 1
Dry contact rated, photocoupler sinking input to IG, 24 Vdc 8 mA,
ground fault protected
DI-2
Digital Input 2
DI-3
Digital Input 3
DI-4
Digital Input 4
DI-5
Digital Input 5
DI-6
Digital Input 6
DI-7
Digital Input 7
DI-8
Digital Input 8
IG24
Isolated Ground
Digital Input Common
3.5 Control Circuit Wiring
70
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual