![YASKAWA Varispeed V7 Series Quick Start Manual Download Page 19](http://html1.mh-extra.com/html/yaskawa/varispeed-v7-series/varispeed-v7-series_quick-start-manual_3559756019.webp)
19
Step 3 – Initializing parameters
To initialize the drive parameters to factory defaults, set parameter n001 = 12.
This will set the V7 to accept start/stop commands in what in termed “2-wire control”, i.e. 1
wire for a motor forward/stop command, and 1 wire for a motor reverse/stop command.
Step 4 – Set the motor rated current
This parameter is used for the electronic thermal function for motor overload detection (OL1). By correctly
setting this, the V7 will protect an overloaded motor from burning out.
Read the rated current (in amps) on the motor nameplate, and enter this into parameter n036. The example
to the below shows entering a value of 1.8Amps.
Key
sequence
Indicator
Display
example
Explanation
Power On
Press the Mode Key repeatedly until the PRGM
indicator is lit.
Press the Enter Key. The data of n001 will be displayed.
Use the Increment or Decrement Key to set n001 to 12.
The display will be lit.
Press the Enter Key so that the set value will be entered
and the data display will be lit.
In approx.
1 s.
The parameter number will be displayed.
Key
sequence
Indicator
Display
example
Explanation
Displays the parameter number.
Use the Increment or Decrement Key until n036 is
displayed.
Press the Enter Key. The data of n036 will be displayed.
Use the Increment or Decrement Key to set the rated
motor current. The display will flash.
Press the Enter Key so that the set value will be entered
and the data display will be lit.
In approx.
1 s.
The parameter number will be displayed.
Summary of Contents for Varispeed V7 Series
Page 2: ......