Tr
oub
les
hoot
in
g
5
Cause
Possible Solutions
—
Correct the settings for E1-04, -06, -07 and -09 (or E-04,
-06, -07, -09 for motor 2).
LED Operator Display
Error Name
oPE11
Carrier Frequency Setting Error
Correct the setting for the carrier frequency.
Cause
Possible Solutions
The following simultaneous contradictory settings:
C6-05 is greater than 6 and C6-04 is greater than C6-03
(carrier frequency lower limit is greater than the upper
limit). If C6-05 is less than or equal to 6, the drive
operates at C6-03.
Correct the parameter settings.
Upper and lower limits between C6-02 and C6-05
contradict each other.
oPE13
Pulse Monitor Selection Error
Incorrect setting of monitor selection for Pulse Train
(H6-06) .
Cause
Possible Solutions
Scaling for the Pulse Train
monitor is set to 0 (H6-07 =
0) while H6-06 is not set to
101, 102, 105, or 116.
Change scaling for the Pulse Train monitor or set H6-06
to 101, 102, 105, or 116..
LED Operator Display
Error Name