Three-Phase 200 V / 400 V Class
L3
L2
PE
L1
Drive
D
E
C
B
G
H
F
A
D
D
A
I
A – Ground the cable shield
B – Enclosure panel
C – Metal plate
D – Grounding surface (remove any
paint or sealant)
E – Drive
F – Motor cable (braided shield cable,
max. 10 m)
G – Motor
H – Cable clamp
I – Ground plate (scrape off any
visible paint)
Figure D.4 EMC Filter and Drive Installation for CE Compliance (Three-Phase 200 V / 400 V Class)
u
EMC Guidelines Compliance for Models 4
o
0477 to 4
o
0930
Use drives with stand-alone EMC filters to comply with EMC guidelines.
Refer to EMC Filters on page 654
o
0477
to 4
o
0930 for EMC filter selection.
Drives with stand-alone EMC filters (4
o
0477 to 4
o
0930) are tested according to European standards EN
61800-3:2004+A1:2012 and comply with EMC guidelines. Use drives with stand-alone EMC filters to comply with EMC
guidelines.
n
EMC Filter Installation
Installation Method
Verify the following installation conditions to ensure that other devices and machinery used in combination with drive models
4
o
0477 to 4
o
0930 also comply with EMC guidelines.
1.
Install an EMC filter to the input side specified by Yaskawa for compliance with European standards.
2.
Place the drive in the enclosure.
3.
Use braided shield cable for the drive and motor wiring, or run the wiring through a metal conduit.
4.
Keep wiring as short as possible. Ground the shield on both the drive side and the motor side.
5.
Make sure the protective earthing conductor complies with technical standards and local safety regulations.
D.2 European Standards
652
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual