B.19 Parameters Changed by Motor Code Selection (for PM Motors)
The following tables show parameters and default settings that change with the motor code selection E5-01 when Open Loop
Vector for PM motors is used.
u
Yaskawa SMRA Series SPM Motor
Table B.18 200 V, 1800 r/min Type Yaskawa SMRA Series SPM Motor Settings
No.
Name
Unit
Default Settings
E5-01
Motor Code Selection (for PM Motors)
−
0002
0003
0005
0006
0008
Voltage Class
V
200
200
200
200
200
Rated Power
kW
0.4
0.75
1.5
2.2
3.7
Rated Speed
r/min
1800
1800
1800
1800
1800
E5-02
Motor Rated Power (for PM Motors)
kW
0.4
0.75
1.5
2.2
3.7
E5-03
Motor Rated Current (for PM Motors)
A
2.1
4.0
6.9
10.8
17.4
E5-04
Number of Motor Poles (for PM Motors)
–
8
8
8
8
8
E5-05
Motor Stator Resistance (r1) (for PM
Motors)
Ω
2.47
1.02
0.679
0.291
0.169
E5-06
Motor d-Axis Inductance (Ld) (for PM
Motors)
mH
12.7
4.8
3.9
3.6
2.5
E5-07
Motor q-Axis Inductance (Lq) (for PM
Motors)
mH
12.7
4.8
3.9
3.6
2.5
E5-09
Motor Induction Voltage Constant 1 (Ke)
(for PM Motors)
mVs
/rad
0
0
0
0
0
E5-24
Motor Induction Voltage Constant 2 (Ke)
(for PM Motors)
mV/
(r/min)
62.0
64.1
73.4
69.6
72.2
E1-04
Maximum Output Frequency
Hz
120
120
120
120
120
E1-05
Maximum Voltage
V
200.0
200.0
200.0
200.0
200.0
E1-06
Base Frequency
Hz
120
120
120
120
120
E1-09
Minimum Output Frequency
Hz
6
6
6
6
6
C5-17
Motor Inertia
kgm
2
0.0007
0.0014
0.0021
0.0032
0.0046
n5-02
Motor Acceleration Time
s
0.064
0.066
0.049
0.051
0.044
Table B.19 200 V, 3600 r/min Type Yaskawa SMRA Series SPM Motor Settings
No.
Name
Unit
Default Settings
E5-01
Motor Code Selection (for PM Motors)
−
0103
0105
0106
0108
Voltage Class
V
200
200
200
200
Rated Power
kW
0.75
1.5
2.2
3.7
Rated Speed
r/min
3600
3600
3600
3600
E5-02
Motor Rated Power (for PM Motors)
kW
0.75
1.5
2.2
3.7
E5-03
Motor Rated Current (for PM Motors)
A
4.1
8.0
10.5
16.5
E5-04
Number of Motor Poles (for PM Motors)
–
8
8
8
8
E5-05
Motor Stator Resistance (r1) (for PM
Motors)
Ω
0.538
0.20
0.15
0.097
E5-06
Motor d-Axis Inductance (Ld) (for PM
Motors)
mH
3.2
1.3
1.1
1.1
E5-07
Motor q-Axis Inductance (Lq) (for PM
Motors)
mH
3.2
1.3
1.1
1.1
E5-09
Motor Induction Voltage Constant 1 (Ke)
(for PM Motors)
mVs
/rad
0
0
0
0
E5-24
Motor Induction Voltage Constant 2 (Ke)
(for PM Motors)
mV/
(r/min)
32.4
32.7
36.7
39.7
E1-04
Maximum Output Frequency
Hz
240
240
240
240
E1-05
Maximum Voltage
V
200.0
200.0
200.0
200.0
E1-06
Base Frequency
Hz
240
240
240
240
E1-09
Minimum Output Frequency
Hz
12
12
12
12
C5-17
Motor Inertia
kgm
2
0.0007
0.0014
0.0021
0.0032
B.19 Parameters Changed by Motor Code Selection (for PM Motors)
594
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
Summary of Contents for U1000 iQpump Drive
Page 705: ......