u
Subchart A-3: Operation with Permanent Magnet Motors
Flowchart A3 in
describes the setup procedure for running a PM motor in Open Loop Vector Control. PM motors
can be used for more energy-efficient operation in reduced or variable torque applications.
Note:
1.
Although the drive sets parameters for the PG encoder during Auto-Tuning, sometimes the direction of the motor and direction of the
PG get reversed. Use parameter F1-05 to switch the direction of the PG so that it matches the motor direction.
2.
Realign the Z Pulse if the PG encoder is replaced. Set T2-01 to 3 to recalibrate the drive for the new encoder.
4.4 Start-Up Flowcharts
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
151
4
Start-Up Programming & Operation
Summary of Contents for U1000 iQpump Drive
Page 705: ......