u
Terminal Configuration
The control circuit terminals should be arranged as shown in
.
MA MB MC
M1 M2 M5
M3 M4 M6
E(G) HC H1 H2 DM+ DM- IG R+ R- S+ S-
S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP
V+ AC V- A1 A2 A3 FM AM AC MP RP AC
A
B
E
D
C
A – Terminal Block (TB 2)
B – Terminal Block (TB 5)
C – Terminal Block (TB 1)
D – Terminal Block (TB 3)
E – Terminal Block (TB 4)
Figure 3.33 Control Circuit Terminal Arrangement
n
Wire Size and Torque Specifications
Select appropriate wire type and gauges from
. For simpler and more reliable wiring, use crimp ferrules on the wire
ends.
Refer to
for ferrule terminal types and sizes.
Table 3.12 Wire Gauges
Terminal
Block
Terminal
Scre
w
Size
Tightening
Torque
N
•
m
(lb. in)
Bare Wire Terminal
Ferrule-Type Terminal
Wire Type
Recomm.
wire size
mm
2
(AWG)
Applicable
wire size
mm
2
(AWG)
Recomm.
wire size
mm
2
(AWG)
Applicable
wire size
mm
2
(AWG)
TB1, TB2,
TB3, TB4
FM, AC, AM,
P1, P2, PC, SC,
A1, A2, A3, +V,
-V, S1-S8, MA,
MB, MC, M1,
M2, HC, H1,
H2, DM+, DM-,
IG, R+, R-, S+,
S-, RP, MP
M3
0.5 to 0.6
(4.4 to 5.3)
0.75 (18)
Stranded wire:
0.2 to 1.0
(24 to 17)
Solid wire:
0.2 to 1.5
(24 to 16)
0.5 (20)
0.25 to 0.5
(24 to 20)
Shielded wire,
etc.
E(G)
1.0 (16)
TB5
E(G)
M3.5
0.5 to 1.0
(4.4 to 8.9)
1.25 (12)
0.5 to 2
(20 to 14)
–
–
n
Ferrule-Type Wire Terminals
Yaskawa recommends using CRIMPFOX 6, a crimping tool manufactured by PHOENIX CONTACT, to prepare wire ends
with insulated sleeves before connecting to the drive. See
d1
d2
8 mm
L
(0.31 in.)
Figure 3.34 Ferrule Dimensions
3.9 Control Circuit Wiring
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
109
3
Electrical Installation