10
YASKAWA
TOEPC71061782C GA800 Drive Installation & Primary Operation
No.
Description
4
Rated output current
Note:
Refer to the tables for the rated output current by model.
5
EMC noise filter
A: No internal EMC filter
6
Enclosure Protection Design
•
A: IP00/UL Open Type
•
W: IP55/UL Type 12 Heatsink External Mounting
7
Environmental specification
A: Standard
M: Humidity-resistant and dust-resistant
■
Rated Output Current
, and
give the rated output current values.
Note:
•
These output current values are applicable for drives that operate at standard specifications.
•
Derate the output current in applications that:
–
Increase the carrier frequency
–
Have high ambient temperature
–
Install drives side-by-side.
•
Use
C6-01 [Normal / Heavy Duty Selection]
to select Normal Duty rating (ND) or Heavy Duty rating (HD).
Table 4.2 Rated Output Current: 6-Phase/12-Pulse 400 V Class
Model
Heavy Duty Rating (HD)
[C6-01 = 0]
Normal Duty Rating (ND)
[C6-01 = 1]
(Default)
Maximum Applicable Motor
Output
kW (HP)
Rated Output Current
A
Maximum Applicable Motor
Output
kW (HP)
Rated Output Current
A
T103
45 (60)
91
55 (75)
103
T140
55 (75)
112
75 (100)
140
T168
75 (100)
150
90 (125)
168
T208
90 (125)
180
110 (150)
208
T250
110 (150)
216
150 (200)
250
T302
150 (200)
260
185 (250)
302
T371
185 (250)
304
220 (300)
371
T414
220 (300)
371
260 (350)
414
T477
260 (350)
414
300 (400)
477
T568
300 (400)
477
335 (450)
568
T605
335 (450)
605
370 (500)
675
T720
370 (500)
605
450 (600)
720
5
Common Drive Specifications
Note:
•
To get the OLV, CLV, and AOLV specifications, do Rotational Auto-Tuning.
•
To get the longest product life, install the drive in an environment that meets the necessary specifications.