4.3 The Drive and Programming Modes
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
83
S
ta
rt
-U
p Pr
og
ra
mmin
g
&
O
p
er
at
io
n
4
◆
Switching Between LOCAL and REMOTE
Entering the run command using the LED operator is referred to as LOCAL, while entering the run command from an
external device via the control circuit terminals or network option card is referred to as REMOTE.
WARNING!
Sudden Movement Hazard. The drive may start unexpectedly if the Run command is already applied when switching from
LOCAL mode to REMOTE mode when b1-07 = 1, resulting in death or serious injury. Be sure all personnel are clear of rotating
machinery and electrical connections prior to switching between LOCAL mode and REMOTE mode.
There are two ways to switch between LOCAL and REMOTE.
Note: 1.
After selecting LOCAL, the LO/RE light will remain lit.
2.
The drive will not allow the user to switch between LOCAL and REMOTE during run.
■
Using the LO/RE Key on the LED Operator
■
Using Input Terminals S1 through S6 to Switch between LO/RE
Switch between LOCAL and REMOTE using one of the digital input terminals S1 through S6 (set the corresponding
parameter H1-01 through H1-06 to “1”).
Follow the example below to set the digital input terminals.
Note: 1.
For a list of digital input selections,
Refer to Parameter List on page 317
2.
Setting a multi-function input terminal to a value of 1 disables the LO/RE key on the LED operator.
◆
Parameters Available in the Setup Group
■
Setup Mode (STUP)
Parameters used for this drive are classified into A to U. To simplify the drive setup, frequently used parameters are
selected and input into Setup Mode.
1.
To set a parameter, the Setup Mode must be displayed first. Press the Up/Down key until
is displayed.
2.
Select the parameter and change the setting.
lists parameters available in the Setup group. If the
desired parameter cannot be set in the Setup mode, use the Parameter Setting mode.
Note:
When parameter A1-02 (Control Method Selection) is changed, some parameter set values are also changed automatically.
Note:
Use the “Par” menu in the Programming mode to access parameters not listed in the Setup Group.
Table 4.4 Setup Group Parameters
Step
Display/Result
1.
Turn on the power to the drive. The initial display appears.
2.
Press
. The LO/RE light will light up. The drive is now in Local.
To set the drive for REMOTE operation, press the
key again.
Parameter
Name
Parameter
Name
A1-02
Control Method Selection
E1-01
Input Voltage Reference
b1-01
Frequency Reference Source 1
E1-03
V/f Pattern Selection
b1-02
Run Command Source 1
E1-04
Maximum Output Frequency
b1-03
Stop Method Selection
E1-05
Maximum Voltage
C1-01
Acceleration Time 1
E1-06
Base Frequency
C1-02
Deceleration Time 1
E1-09
Minimum Output Frequency
C6-01
Duty Selection
E1-13
Base Voltage
C6-02
Carrier Frequency Selection
E2-01
Motor Rated Current
d1-01
Frequency Reference 1
E2-04
Number of Motor Poles
d1-02
Frequency Reference 2
E2-11
Motor Rate Capacity
d1-03
Frequency Reference 3
H4-02
Terminal AM Gain Setting
d1-04
Frequency Reference 4
L1-01
Motor Protection Function Selection
d1-17
Jog Frequency Reference
L3-04
Stall Prevention Selection during Deceleration
STOP